Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
XB4BS9442 – Emergency stop switching off, Harmony XB4, metal, red mushroom 40mm, 22mm, trigger latching key release, 1NC
XB4BS9442
Emergency stop switching off, Harmony XB4, metal, red mushroom 40mm, 22mm, trigger latching key release, 1NC

This Harmony XB4 emergency stop / shutdown 40mm mushroom head modular red push button operates with a latched key release (key no.455) mechanism. It has a metal bezel. This emergency stop / shutdown button, also called EMS (Emergency Machine Stop) and EMO (Emergency Off), is easily installed into a standard 22mm diameter cut-outs and connected with simple screw-clamp connections. It is clearly distinguishable visually at a distance thanks to a clear color and a prominent 40mm mushroom shape. It is impact resistant, dust resistant, water resistant and vibration resistant thanks to its IP66, making it ideal for operation in harsh environments.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Reset key release
Range Of Product Harmony XB4
Mounting Diameter 22 mm
Type Of Operator trigger action and mechanical latching
Product Or Component Type
  • emergency stop push-button
  • emergency switching off push-button
Shape Of Signaling Unit Head round
Fixing Collar Material zamak
Head Type standard
Key Withdrawal Position center
Connections - Terminals
  • screw clamp terminals, <= 2 x 1.5 mm² with cable end EN 60947-1
  • screw clamp terminals, >= 1 x 0.22 mm² without cable end EN 60947-1
Sale Per Indivisible Quantity 1
Bezel Material chromium plated metal
Contact Operation slow-break
Operator Profile red mushroom Ø 40 mm, unmarked
Device Short Name XB4
Type Of Keylock key 455
Contacts Usage standard contacts
Height 47 mm
Terminals Description Iso N°1 (21-22)NC
Short-Circuit Protection 10 A cartridge fuse gG EN/IEC 60947-5-1
Operating Travel
  • 1.5 mm NC changing electrical state)
  • 4.3 mm total travel)
Contacts Material silver alloy (Ag/Ni)
Positive Opening with EN/IEC 60947-5-1 appendix K
[Ith] Conventional Free Air Thermal Current 10 A EN/IEC 60947-5-1
Net Weight 0.133 kg
[Uimp] Rated Impulse Withstand Voltage 6 kV EN 60947-1
Device Presentation complete product
Resistance To High Pressure Washer 7000000 Pa 55 °C 0.1 m
Electrical Durability
  • 1000000 cycles, AC-15, 2 A 230 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
  • 1000000 cycles, AC-15, 3 A 120 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
  • 1000000 cycles, AC-15, 4 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
  • 1000000 cycles, DC-13, 0.2 A 110 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
  • 1000000 cycles, DC-13, 0.5 A 24 V 3600 cyc/h 0.5 EN/IEC 60947-5-1 appendix C
[Ui] Rated Insulation Voltage 600 V 3)EN 60947-1
[Ie] Rated Operational Current
  • 3 A 240 V, AC-15, A600 EN/IEC 60947-5-1
  • 6 A 120 V, AC-15, A600 EN/IEC 60947-5-1
  • 0.1 A 600 V, DC-13, Q600 EN/IEC 60947-5-1
  • 0.27 A 250 V, DC-13, Q600 EN/IEC 60947-5-1
  • 0.55 A 125 V, DC-13, Q600 EN/IEC 60947-5-1
  • 1.2 A 600 V, AC-15, A600 EN/IEC 60947-5-1
Mechanical Durability 300000 cycles
Electrical Reliability
  • λ < 10exp(-6) 5 V 1 mA in clean environment EN/IEC 60947-5-4
  • λ < 10exp(-8) 17 V 5 mA in clean environment EN/IEC 60947-5-4
Width 40 mm
Depth 104 mm
Tightening Torque 0.8-1.2 N.m EN 60947-1
Shape Of Screw Head
  • cross Philips no 1
  • cross pozidriv No 1
  • slotted flat Ø 4 mm
  • slotted flat Ø 5.5 mm
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP2201004EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI2201004EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • CSA
  • LROS (Lloyds register of shipping)
  • DNV
  • BV
  • UL Listed
  • GL
Ik Degree Of Protection IK03 IEC 50102
Ambient Air Temperature For Operation -40-70 °C
Standards
  • EN/IEC 60947-1
  • EN/IEC 60947-5-5
  • JIS C8201-5-1
  • EN/IEC 60947-5-4
  • IEC 60364-5-53
  • EN/IEC 60204-1
  • UL 508
  • EN/IEC 60947-5-1
  • CSA C22.2 No 14
  • EN/ISO 13850
  • JIS C8201-1
Shock Resistance
  • 30 gn 18 ms) half sine wave acceleration IEC 60068-2-27
  • 50 gn 11 ms) half sine wave acceleration IEC 60068-2-27
Vibration Resistance 5 gn 2-500 Hz)IEC 60068-2-6
Ip Degree Of Protection
  • IP66 IEC 60529
  • IP67
  • IP69
  • IP69K
Ambient Air Temperature For Storage -40-70 °C
Nema Degree Of Protection
  • NEMA 13
  • NEMA 4X
Electrical Shock Protection Class class I IEC 60536
Protective Treatment TH
Documents