Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
XACS414 – Contact block, Harmony XAC, single contact, spring return, front mounting, 40mm horizontal/30mmVertical fixing centres, 2NC
XACS414
Contact block, Harmony XAC, single contact, spring return, front mounting, 40mm horizontal, 30mm vertical fixing centres, 2NC

This spring return contact block is a separate component for double insulated, XACB pendant control station. It is designed for front mounting and features 2 NC contacts.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Mounting Of Block front mounting
Range Of Product Harmony XAC
Contact Block Type single
Product Or Component Type contact block
Component Name XACS
Contacts Type And Composition 2 NC
Contact Operation slow-break
Mechanical Interlocking without mechanical interlock
Type Of Operator spring return
Electrical Circuit Type control circuit
Product Compatibility
  • ZA2B... head
  • XACA
Warranty 18 months
Terminal Identifier
  • (13-14)NO
  • (11-12)NC
Terminals Description Iso N°1
  • (21-22)NC
  • (11-12)NC
Maximum Resistance Across Terminals 25 MOhm
Horizontal Fixing Centres 40 mm
[Ithe] Conventional Enclosed Thermal Current 10 A
Short-Circuit Protection 10 A fuse protection cartridge gG
Net Weight 0.07 kg
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-1
Vertical Fixing Centres 30 mm
Connections - Terminals
  • screw clamp terminals, 1 x 2.5 mm² with or without cable end
  • screw clamp terminals, 2 x 1.5 mm² with or without cable end
[Ui] Rated Insulation Voltage 500 V 3)IEC 60947-1
Rated Operational Power In Va
  • 140 VA AC-15 1000000 cycles 60 cyc/mn 24 V 50/60 Hz 0.5 inductive
  • 385 VA AC-15 1000000 cycles 60 cyc/mn 48 V 50/60 Hz 0.5 inductive
  • 455 VA AC-15 1000000 cycles 60 cyc/mn 230 V 50/60 Hz 0.5 inductive
  • 525 VA AC-15 1000000 cycles 60 cyc/mn 127 V 50/60 Hz 0.5 inductive
Mechanical Durability 1000000 cycles
Contact Code Designation
  • A300 AC-15, Ue = 240 V, Ie = 3 A IEC 60947-5-1 appendix A
  • Q300 DC-13, Ue = 250 V, Ie = 0.27 A IEC 60947-5-1 appendix A
Rated Operational Power In W
  • 42 W DC-13 1000000 cycles 60 cyc/mn 120 V 0.5 inductive IEC 60947-5-1 appendix C
  • 45 W DC-13 1000000 cycles 60 cyc/mn 48 V 0.5 inductive IEC 60947-5-1 appendix C
  • 60 W DC-13 1000000 cycles 60 cyc/mn 24 V 0.5 inductive IEC 60947-5-1 appendix C
Rohs Exemption Information Yes
Mercury Free Yes
Toxic Heavy Metal Free Yes
Reach Regulation Free of Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc Yes
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Ambient Air Temperature For Operation -25-70 °C
Standards
  • CSA C22.2 No 14
  • IEC 60947-5-1
  • EN 60947-5-1
Shock Resistance 100 gn IEC 60068-2-27
Vibration Resistance 15 gn 10-500 Hz)IEC 60068-2-6
Ambient Air Temperature For Storage -40-70 °C
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews