Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
XACS101 – Contact block, Harmony XAC, single contact, spring return, base mounting, 1NO
XACS101
Contact block, Harmony XAC, single contact, spring return, base mounting, 1NO

This Harmony XACS101 is a spring return contact block - 1NO - base mounting. It is part of the range Harmony XAC pendant control stations for diameter 22mm plastic signaling units.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Mounting Of Block base mounting
Contacts Type And Composition 1 NO
Range Of Product Harmony XAC
Contact Operation slow-break
Type Of Operator spring return
Contact Block Type single
Electrical Circuit Type control circuit
Product Or Component Type contact block
Component Name XACS
Product Compatibility XACA
Warranty 18 months
Connections - Terminals
  • screw clamp terminals, 1 x 0.5...1 x 2.5 mm² without cable end
  • screw clamp terminals, 1 x 0.5...2 x 1.5 mm² with cable end
Terminals Description Iso N°1 (13-14)NO
[Ui] Rated Insulation Voltage 600 V 3)IEC 60947-1
Maximum Resistance Across Terminals 25 MOhm
Mechanical Durability 1000000 cycles
[Ithe] Conventional Enclosed Thermal Current 10 A
Operating Force 10 N
Short-Circuit Protection 10 A fuse protection cartridge gG
Contact Code Designation
  • A600 AC-15, Ue = 240 V, Ie = 3 A IEC 60947-5-1 appendix A
  • A600 AC-15, Ue = 600 V, Ie = 1.2 A IEC 60947-5-1 appendix A
  • Q600 DC-13, Ue = 250 V, Ie = 0.27 A IEC 60947-5-1 appendix A
  • Q600 DC-13, Ue = 600 V, Ie = 0.1 A IEC 60947-5-1 appendix A
Rated Operational Power In W
  • 40 W DC-13 1000000 cycles 60 cyc/mn 120 V 0.5 inductive IEC 60947-5-1 appendix C
  • 48 W DC-13 1000000 cycles 60 cyc/mn 48 V 0.5 inductive IEC 60947-5-1 appendix C
  • 65 W DC-13 1000000 cycles 60 cyc/mn 24 V 0.5 inductive IEC 60947-5-1 appendix C
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-1
China Rohs Regulation X
Rohs Exemption Information Yes
Mercury Free Yes
Toxic Heavy Metal Free Yes
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Reach Regulation Free of Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc Yes
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Ambient Air Temperature For Operation -25-70 °C
Ambient Air Temperature For Storage -40-70 °C
Overvoltage Category class II IEC 61140
Standards
  • UL 508
  • EN/IEC 60947-5-1
  • CSA C22.2 No 14
Shock Resistance 100 gn IEC 60068-2-27
Vibration Resistance 15 gn 10-500 Hz)IEC 60068-2-6
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews