VW3A3202 – extended I/O card, Altivar
VW3A3202
extended I/O card, Altivar

This extended I/O card enables your drive to meet the needs of more complex or extensive applications. It comprises four logic inputs, two analog inputs, one input for PTC probe and one frequency control input. It also comprises three logic outputs and two analog outputs. It is compatible with Altivar 61 and Altivar 71.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Discrete Input Logic
  • negative LI11...LI14), >= 16 V, <= 10 V
  • positive LI11...LI14), <= 5 V, >= 11 V
  • positive RP), < 1.2 V, >= 3.5 V
Analogue Output Type
  • AO2 software-configurable current 0...20 mA 500 Ohm 4-6 ms 10 bits
  • AO2 software-configurable voltage +/- 10 V DC 470 Ohm 4-6 ms 10 bits
  • AO3 software-configurable current 0...20 mA 500 Ohm 4-6 ms 10 bits
  • AO3 software-configurable voltage +/- 10 V DC 470 Ohm 4-6 ms 10 bits
Discrete Output Type
  • LO3, LO4) assignable logic 4-6 ms level 1 PLC
  • R4A, R4B, R4C) configurable relay logic
Product Or Component Type extended I/O card
Analogue Input Number 2
Discrete Output Number 5
Discrete Input Type
  • RP) frequency control 4-6 ms
  • LI11...LI14) programmable level 1 PLC 3.5 kOhm 4-6 ms
Analogue Output Number 2
Discrete Output Logic
  • LO3, LO4) negative
  • LO3, LO4) positive
Discrete Input Number 6
Range Compatibility
  • Altivar 61Q
  • Altivar Lift
  • Altivar 71Q
  • Altivar 71
  • Altivar 61
Analogue Input Type
  • AI3-/Al3+ differential current programmable 0...20 mA 250 Ohm 4-6 ms 11 bits + sign
  • AI4 software-configurable current 0...20 mA 250 Ohm 4-6 ms 11 bits
  • AI4 software-configurable voltage 0...10 V DC, 24 V max 30000 Ohm 4-6 ms 11 bits
Supply
  • internal supply for reference potentiometer, 10.5 V DC 10-11 V) , <0.01 A 1-10 kOhm overload and short-circuit protection
  • internal supply, 24 V DC 21-27 V) , <0.2 A overload and short-circuit protection
Warranty 18 months
Electrical Durability 100000 cycles configurable relay logic
Discrete Input Voltage 24 V DC <= 30 V)programmable
Maximum Switching Current
  • configurable relay logic 5 A 250 V AC resistive, cos phi = 1
  • configurable relay logic 5 A 30 V DC resistive, cos phi = 1
  • configurable relay logic 1.5 A 250 V AC inductive, cos phi = 0.4 7 ms
  • configurable relay logic 1.5 A 30 V DC inductive, cos phi = 0.4 7 ms
Discrete Output Voltage 24 V DC <= 30 V) assignable logic
Net Weight 0.3 kg
Maximum Output Current 0.2 A, assignable logic
Minimum Switching Current 3 mA 24 V DC configurable relay logic
Ptc Probe Input
  • TH2+, TH2- trip resistance 3 kOhm
  • TH2+, TH2- reset resistance 1.8 Ohm
  • TH2+, TH2- short circuit protection < 0.05 Ohm
  • TH2+, TH2- for 6 PTC probe <= 1.5 Ohm
Electrical Connection terminal, 1.5 mm² / AWG 16, 0.25 N.m
Discrete Input Frequency 0...30 kHz frequency control
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP2010015EN
Sustainable Offer Status Green Premium product
Pvc Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation X
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)