These TeSys VLS disconnect switches are for integration into control systems in applications like material handling, HVAC, pumping, solar energy, mining and many more. This family of disconnect switches has switches ranging from 16A to 125A. The 16A, 25A, 32A, 40A and 63A disconnect switches are UL508 motor disconnect switches rated. The 30A, 63A, 80A, 100A and 125A disconnect switches are UL98 non fusible disconnect switch rated. This fourth pole adder can be added to a VLS3P016R1, VLS3P025R1, VLS3P032R1 or VLS3P040R1 DIN rail mount switch. This fourth pole adder for DIN rail mounted devices can be mounted on the right or left hand side. This early make adder pole has one normally open contact The operational voltage of this fourth pole adder module is 600 Vac 50/60 Hz. This fourth pole adder module has a 40 A current rating. The screw clamp terminals will accept 18 AWG to 6 AWG wire. Fourth pole adder is 3.07 inches tall, 0.47 inches wide and 1.72 inches deep. It weighs 0.09 lbs. This fourth pole adder block is cULus Listed and meets IEC 60947-3 requirements.
Brand: Schneider Electric
Add to Quote CatalogueNetwork Frequency | 50/60 Hz |
---|---|
Network Type | AC |
Range Compatibility | TeSys (TeSys VARIO LS) VLS3P |
Product Or Component Type | additional pole |
Performance Level | high performance |
Range | TeSys |
Contacts Type And Composition | 1 NO |
Suitability For Isolation | yes |
Contact Operation | early make |
Poles Description | 1P |
Device Short Name | VLS1P |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz |
Height | 78 mm |
Intermittent Duty Class | class 120 - 60 % |
[Ith] Conventional Free Air Thermal Current | 40 A 55 °C |
Mounting Support | DIN rail |
[Ithe] Conventional Enclosed Thermal Current | 40 A |
Net Weight | 0.04 kg |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Making Capacity |
|
Mounting Location |
|
Connections - Terminals |
|
[Icm] Rated Short-Circuit Making Capacity | 1128 A 690 V |
Electrical Durability | 100000 cycles AC-21A |
[Ie] Rated Operational Current |
|
Mechanical Durability | 100000 cycles |
Color | Gray |
Width | 12 mm |
Tightening Torque | power circuit 1.8-2 N.m screw clamp terminals |
Depth | 43.6 mm |
Breaking Capacity |
|
Rated Operational Power In W |
|
Rated Conditional Short-Circuit Current | 50 kA 400 V 40 A gG |
[Icw] Rated Short-Time Withstand Current | 800 A 690 V 1 s |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Free of Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Reach Free Of Svhc | Yes |
China Rohs Regulation | Pro-active China RoHS declaration (out of China RoHS legal scope) |
Eu Rohs Directive | Compliant |
Product Certifications |
|
Ambient Air Temperature For Operation | -25-55 °C |
Standards |
|
Ip Degree Of Protection | IP20 conforming to IEC 60529 |
Mechanical Robustness |
|
Fire Resistance | 960 °C IEC 60695-2-11 |
Powered by