VCCF4 is a 3-pole TeSys Vario switch-disconnector from Schneider Electric. Rated 80A 690V, it is used for main and emergency stop switching in motor applications up to 30kW@400V AC-23. Composed of a V4 switch body, extension shaft, red padlockable handle, and a yellow 60x60mm front plate. For enclosure back mounting, with a 4 screw fixing handle, it ensures IP65 to the mounting. Available worldwide, multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHs/Reach). Possible distance between back of enclosure and door 300-320mm. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).
Brand: Schneider Electric
Add to Quote CatalogueProduct Or Component Type | emergency stop switch disconnector |
---|---|
Product Name | TeSys VARIO |
Range | TeSys |
Device Short Name | VCCF |
Warranty | 18 months |
Rotary Handle Padlocking | 1 to 3 padlocks 4-8 mm |
Rotary Handle Mounting Style | extended |
[Ue] Rated Operational Voltage | 690 V AC 50/60 Hz |
Height | 83 mm |
Intermittent Duty Class | 30 |
[Ith] Conventional Free Air Thermal Current | 80 A |
Network Type |
|
Handle Front Plate Colour | yellow |
Fixing Mode |
|
[Ithe] Conventional Enclosed Thermal Current | 63 A |
Handle Colour | red |
Marking | 0 - 1 |
Base Dimension | 60 x 60 mm |
Net Weight | 0.68 kg |
Performance Level | high performance |
[Uimp] Rated Impulse Withstand Voltage | 8 kV |
Making Capacity |
|
Control Type | rotary handle |
Connections - Terminals |
|
Contacts Type And Composition | 3 NO |
[Icm] Rated Short-Circuit Making Capacity | 2.1 kA 400 V at Ipeak |
Electrical Durability |
|
Suitability For Isolation | yes |
[Ie] Rated Operational Current | 57 A AC-23 Ue: 400 V |
Mounting Support |
|
Mechanical Durability | 30000 cycles |
Poles Description | 3P |
Width | 60 mm |
Tightening Torque | power circuit 4-4 N.m screw clamp terminals |
Device Composition |
|
Breaking Capacity |
|
Rated Operational Power In W |
|
Rated Conditional Short-Circuit Current |
|
[Icw] Rated Short-Time Withstand Current | 960 A 400 V 1 s |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP110227EN |
Sustainable Offer Status | Green Premium product |
Pvc Free | Yes |
Toxic Heavy Metal Free | Yes |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | Product out of China RoHS scope. Substance declaration for your information. |
Eu Rohs Directive | Compliant |
Product Certifications |
|
Ambient Air Temperature For Operation | -20-50 °C |
Standards | IEC 60947-3 |
Ip Degree Of Protection |
|
Protective Treatment | TC |
Compatibility Code | main switch disconnector |
Mechanical Robustness |
|
Fire Resistance | 960 °C IEC 60695-2-1 |