This static relay has a built-in heatsink for limited derating while limiting occupied space in panel It also has a visual indicator showing the status of its input Its rated current is 25 A, is controlled with a 90 to 140 V AC circuit, has a rated load voltage of 48 to 600 V AC output. It mounts on symetrical DIN rails and comes with a secure mounting latch
Brand: Schneider Electric
Add to Quote CatalogueRange Of Product | Harmony Solid State Relays |
---|---|
Output Switching Mode | zero voltage switching |
Product Or Component Type | solid state relay up to 30 A |
Phase | 3 phase |
Number Of Channels | 3 |
Device Short Name | SSM3 |
Cos Phi | 0.5-0.5 (with maximum load) |
[Uc] Control Circuit Voltage | 90...140 V AC |
Output Voltage | 48...600 V AC |
Maximum Horse Power Rating |
|
Tightening Torque |
|
Insulation Resistance | 1000 MOhm |
Mounting Support | symmetrical DIN rail |
Maximum I²T For Fusing |
|
Maximum Voltage Drop | <1.35 V on-state |
Connections - Terminals |
|
Surge Current |
|
Response Time |
|
Load Current | 0.1-25 A |
Net Weight | 0.74 kg |
Maximum Leakage Current | 0.25 mA off-state |
Absolute Maximum Voltage | 1100 V |
Dv/Dt | 500 V/µs off-state at maximum voltage |
Local Signalling | for input status LED (green) |
Solid State Output Type | zero voltage switching |
Capacitance Unbalance | 8 pF for input/output |
Line Rated Current | 25 A |
Switching Voltage |
|
Input Current Limits | 15-19 mA |
Overvoltage Category | III |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1508007EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | X |
Circularity Profile | ENVEOLI1508007EN |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Product Certifications |
|
Ambient Air Temperature For Operation | -20-80 °C |
Standards |
|
Pollution Degree | 2 |
Dielectric Strength |
|
Marking |
|
Ip Degree Of Protection | IP20 |
Ambient Air Temperature For Storage | -40-100 °C |