Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
SSM3A325F7 – Solid state modular relay, Harmony, 25A, DIN rail mount, zero voltage switching, input 90…140V AC, output 48…600V AC
SSM3A325F7
single-phase relay, Harmony solid state modular relay, 25A, DIN rail mount, zeroVoltage switching, input 90…140V AC, output 48…600V AC

This static relay has a built-in heatsink for limited derating while limiting occupied space in panel It also has a visual indicator showing the status of its input Its rated current is 25 A, is controlled with a 90 to 140 V AC circuit, has a rated load voltage of 48 to 600 V AC output. It mounts on symetrical DIN rails and comes with a secure mounting latch

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Range Of Product Harmony Solid State Relays
Output Switching Mode zero voltage switching
Product Or Component Type solid state relay up to 30 A
Phase 3 phase
Number Of Channels 3
Device Short Name SSM3
Cos Phi 0.5-0.5 (with maximum load)
[Uc] Control Circuit Voltage 90...140 V AC
Output Voltage 48...600 V AC
Maximum Horse Power Rating
  • 1 hp 40 °C 240 V AC
  • 2 hp 40 °C 380 V AC
  • 3 hp 40 °C 480 V AC
Tightening Torque
  • 0.6...0.7 N.m for input
  • 1.36...1.7 N.m for output
Insulation Resistance 1000 MOhm
Mounting Support symmetrical DIN rail
Maximum I²T For Fusing
  • 410 A².s for 10 ms at 50 Hz
  • 374 A².s for 8.3 ms at 60 Hz
Maximum Voltage Drop <1.35 V on-state
Connections - Terminals
  • screw terminals 0.2...1.3 mm², AWG 24...AWG 16) input
  • screw terminals 1.3...5.3 mm², AWG 16...AWG 10) output
Surge Current
  • 286 A 20 ms 50 Hz
  • 300 A 16.6 ms 60 Hz
Response Time
  • 30 ms (turn-off)
  • 20 ms (turn-on)
Load Current 0.1-25 A
Net Weight 0.74 kg
Maximum Leakage Current 0.25 mA off-state
Absolute Maximum Voltage 1100 V
Dv/Dt 500 V/µs off-state at maximum voltage
Local Signalling for input status LED (green)
Solid State Output Type zero voltage switching
Capacitance Unbalance 8 pF for input/output
Line Rated Current 25 A
Switching Voltage
  • 90 V turn-on
  • 10 V turn-off
Input Current Limits 15-19 mA
Overvoltage Category III
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1508007EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation X
Circularity Profile ENVEOLI1508007EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • UL
  • EAC
  • CSA
Ambient Air Temperature For Operation -20-80 °C
Standards
  • IEC 60950-1
  • UL 508
  • CSA C22.2 No 14
Pollution Degree 2
Dielectric Strength
  • 4 kV AC for input/output
  • 4 kV AC for input or output to case
Marking
  • CSA
  • UL
  • CE
  • EAC
Ip Degree Of Protection IP20
Ambient Air Temperature For Storage -40-100 °C
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews