Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
SR3XT43BD – Analogue I/O extension module, Zelio Logic, 4 I/O, 24 V DC
SR3XT43BD
analogue IO extension module, Zelio Logic SR2 SR3, 4 IO, 24V DC

This Schneider Electric Zelio Logic SR3 Analog I/O Extension Module Smart Relays uses a supply voltage of 24 volts direct current, has 4 inputs / outputs contact with screw-clamp terminals. This Analog I/O Extension Module Smart Relays provides Zelio Logic relays with additional inputs and outputs. It has a compact form-factor, allowing installation on DIN rail. Simple ladder programming, adapted for non-specialists. Discovery package, coming with Zelio Soft programming software, the simplest way to learn and use this relay. Built-in EEPROM flash memory for data backup up to 10 years, easy-to-recover after a power shortage or incident. More I/O than SR2 model, for larger applications. This product meets EN/IEC 61000-4-12, EN/IEC 61000-4-5, EN/IEC 61000-4-3, EN/IEC 61000-4-4 level 3, EN/IEC 61000-4-6 level 3, EN/IEC 61000-4-2 level 3, EN/IEC 60068-2-6 Fc, EN/IEC 61000-4-11 and EN/IEC 60068-2-27 Ea standards. Simple to select, install and program, Zelio Logic is suitable for all your applications. Flexible, it offers you the choice of 2 ranges, compact or modular, extendable and 2 programming languages (FBD or LADDER). Easy to use, Zelio Logic provides a real alternative to solutions based on cabled logic or specific cards.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Range Of Product Zelio Logic
Product Or Component Type analogue I/O extension module
Warranty 18 months
Lsb Value
  • 0.15 °C, - 25...125 °C analogue input circuit
  • 20 µA, 0...20 mA analogue input circuit
  • 9.8 mV, 0...10 V analogue input circuit
  • 9.8 mV, 0...10 V analogue output
Input Impedance
  • 18 kOhm 0...10 V analogue input circuit
  • 247 Ohm 0...20 mA analogue input circuit
Maximum Load Current 10 mA analogue output
Analogue Input Range
  • 0...10 V
  • 0...20 mA
  • -25...125 °C
Conversion Error
  • +/- 1 % of the full scale value 0...10 V 25 °C)analogue output
  • +/- 1 % of the full scale value 0...10 V 55 °C)analogue output
  • +/- 1 % 0...10 V 25 °C)analogue input circuit
  • +/- 1 % 0...10 V 55 °C)analogue input circuit
  • +/- 1 % 0...20 mA 25 °C)analogue input circuit
  • +/- 1 % 0...20 mA 55 °C)analogue input circuit
  • +/- 1.5 °C - 25...125 °C 25 °C)analogue input circuit
  • +/- 1.5 °C - 25...125 °C 55 °C)analogue input circuit
Analogue Input Type common mode
Analogue Output Range 0...10 V
Net Weight 0.11 kg
Conversion Time
  • smart relay cycle time analogue input circuit
  • smart relay cycle time analogue output
Analogue Output Resolution 10 bits on the output range
Connections - Terminals
  • screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) semi-solid
  • screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) solid
  • screw terminals, 2 x 0.25...2 x 1.5 mm² AWG 23...AWG 16) solid
  • screw terminals, 1 x 0.25...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
  • screw terminals, 2 x 0.25...2 x 0.75 mm² AWG 24...AWG 18) flexible with cable end
Analogue Input Number 2
Analogue Output Number 2
Short-Circuit Protection with analogue output
Operating Distance
  • 10 m with screened cable analogue input circuit
  • 10 m with screened cable analogue output
Reverse Polarity Protection analogue input circuit with
Tightening Torque 0.5 N.m
Temperature Probe Type Pt 100, 3-wire IEC 751
Analogue Input Resolution 10 bits on the input range
[Imp] Maximum Permanent Current 30 mA analogue input circuit
Maximum Permissible Voltage 30 V analogue input circuit
Load Type resistive analogue output
Repeat Accuracy
  • < +/- 0.3 °C - 25...125 °C 25 °C analogue input circuit
  • <= +/- 1 % 0...10 V 25 °C analogue input circuit
  • <= +/- 1 % 0...10 V 55 °C analogue output
  • <= +/- 1 % 0...20 mA 25 °C analogue input circuit
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP2011013EN
Sustainable Offer Status Green Premium product
Pvc Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI2011013EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • GOST
  • UL
  • C-tick
  • CSA
Standards
  • EN/IEC 61000-4-12
  • EN/IEC 61000-4-5
  • EN/IEC 61000-4-3
  • EN/IEC 61000-4-4 level 3
  • EN/IEC 61000-4-6 level 3
  • EN/IEC 61000-4-2 level 3
  • EN/IEC 60068-2-6 Fc
  • EN/IEC 61000-4-11
  • EN/IEC 60068-2-27 Ea
Disturbance Radiated/Conducted class B EN 55022-11 group 1
Ambient Air Temperature For Operation
  • -20-40 °C IEC 60068-2-1 and IEC 60068-2-2
  • -20-55 °C IEC 60068-2-1 and IEC 60068-2-2
Environmental Characteristic
  • EMC directive EN/IEC 61000-6-2
  • EMC directive EN/IEC 61000-6-3
  • EMC directive EN/IEC 61000-6-4
  • EMC directive EN/IEC 61131-2 zone B
  • low voltage directive EN/IEC 61131-2
Ip Degree Of Protection
  • IP20 IEC 60529 terminal block)
  • IP40 IEC 60529 front panel)
Pollution Degree 2 EN/IEC 61131-2
Ambient Air Temperature For Storage -40-70 °C
Relative Humidity 95-95 % without condensation or dripping water
Maximum Altitude Transport 3048 m
Operating Altitude 6561.68 ft (2000 m)
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews