Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
RMPT30BD – Converter for Universal Pt100 probes, Harmony Analog, temperature transmitter, 0…100 degree COr 32…212 degree F
RMPT30BD
Converter for Universal Pt100 probes, Harmony Analog, temperature transmitter, 0...100 degree COr 32...212 degree F

This temperature transmitter is part of the range of Harmony Analog interfaces. It is designed to convert signal of Pt100 probe into standard electrical signal which is compatible with automation platforms, controllers. Its supply voltage is 24V DC, non isolated. It also allows the connection distance between a sensor and the measurement acquisition device to be increased. The cables used to connect the converters to process equipment (PLCs) are standard cables, which are more cost effective than extension cables or compensation cables suitable for low level signals for Pt100 probes or thermocouples. Conforming to IEC standards, UL and CSA certified, this converter is suitable for universal use. 0 0 0 0 0 0 0 0 0 0 0

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Range Of Product Harmony Analog
Analogue Output Type
  • current 0...20 mA <= 500 Ohm
  • current 4...20 mA <= 500 Ohm
  • voltage 0...10 V >= 100 kOhm
Product Or Component Type converter for Universal Pt100 probes
Analogue Input Type temperature probe 0...100 °C/32..212 °F Pt 100 2, 3 or 4 wires
Warranty 18 months
[Us] Rated Supply Voltage 24 V DC non isolated +/- 20 %
Current Consumption
  • <= 40 mA voltage output
  • <= 60 mA current output
Safety Reliability Data
  • MTTFd = 32.9 years
  • B10d = 30437
Measurement Error
  • +/- 0.5 % of full scale 3 or 4 wires)20 °C
  • +/- 1 % of full scale 2 wires)20 °C
  • +/- 10 % of full scale20 °C electromagnetic interference of 10 V/m)
Clamping Connection Capacity
  • 1 x 2.5 mm²
  • 2 x 1.5 mm²
[Ui] Rated Insulation Voltage 2000 V
Marking CE
Analogue Output Voltage
  • -15...-11 V no input or input wire broken
  • 11...15 V no input or input wire broken
Net Weight 0.12 kg
Fixing Mode
  • clip-on 35 mm symmetrical DIN rail)
  • fixed mounting plate)
Surge Withstand 0.5 kV 1.2/50 µs IEC 61000-4-5
Maximum Wiring Resistance 0.2 Ohm 2 wires
Local Signalling for power ON LED (green)
Temperature Coefficient 150 ppm/°C
Protection Type
  • reverse polarity protection on power supply
  • short-circuit protection on output
  • overvoltage protection on output (+/- 30 V)
  • reverse polarity protection on output
Tightening Torque 0.6-1.1 N.m
Analogue Output Current
  • -30-0 mA no input or input wire broken
  • 22-30 mA no input or input wire broken
Repeat Accuracy
  • +/- 0.2 % full scale 20 °C
  • +/- 0.6 % full scale 60 °C
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1607005EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI1607005EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • GL
  • UL
  • CSA
Standards
  • DIN 43760
  • EN/IEC 60751
  • EN/IEC 60947-1
  • EN/IEC 60584-1
Ambient Air Temperature For Operation
  • 0-50 °C mounting side by side
  • 0-60 °C 2 cm spacing
Electromagnetic Compatibility
  • electrostatic discharge 6 kV contact discharge)level 3 IEC 61000-4-2
  • electrostatic discharge 8 kV air discharge)level 3 IEC 61000-4-2
Shock Resistance 50 gn 11 ms IEC 60068-2-27
Vibration Resistance 5 gn 10-100 Hz)IEC 60068-2-6
Ip Degree Of Protection
  • IP20 terminal block)
  • IP50 housing)
Disturbance Radiated/Conducted
  • CISPR 22 group 1 - class B
  • CISPR 11
Pollution Degree 2 IEC 60664-1
Ambient Air Temperature For Storage -40-85 °C
Fire Resistance
  • 850 °C IEC 60695-2-1
  • 850 °C UL
Resistance To Fast Transients
  • 1 kV IEC 61000-4-4 on input-output)
  • 2 kV IEC 61000-4-4 on power supply)
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews