Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
RM35UB3N30 – Modular 3 phaseVoltage control relay, Harmony, 5A, 2CO, 120…277V AC
RM35UB3N30
Modular 3 phaseVoltage control relay, Harmony, 5A, 2CO, 120…277V AC

This Harmony RM35-UB allows monitoring of voltage control in 3-phase networks. This modular multi function 3-phase voltage control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Minimum Switching Current 10 mA 5 V DC
Maximum Switching Current 5 A AC/DC
Range Of Product Harmony Control Relays
Measurement Range 114...329 V voltage AC 50/60 Hz
Power Consumption In Va 0-3.9 VA AC
Switching Capacity In Va 1250 VA
Product Or Component Type voltage control relay
Utilisation Category
  • AC-12 IEC 60947-5-1
  • AC-13 IEC 60947-5-1
  • AC-14 IEC 60947-5-1
  • AC-15 IEC 60947-5-1
  • DC-12 IEC 60947-5-1
  • DC-13 IEC 60947-5-1
  • DC-14 IEC 60947-5-1
Relay Name RM35UB3
Contacts Type And Composition 2 C/O
Relay Type voltage control relay
Product Specific Application for 3-phase supply
Time Delay Type adjustable 0.3...30 s, 0 + 10 % on crossing the threshold
Relay Monitored Parameters
  • absence of neutral
  • overvoltage and undervoltage between phases
  • overvoltage and undervoltage between neutral
Warranty 18 months
[Us] Rated Supply Voltage 120...277 V AC 50/60 Hz +/- 10 %
Safety Reliability Data
  • B10d = 470000
  • MTTFd = 502.2 years
Maximum Measuring Cycle 150 ms measurement cycle as true rms value
Hysteresis 2-2 %
Insulation Resistance
  • > 500 MOhm 500 V DC IEC 60255-5
  • > 500 MOhm 500 V DC IEC 60664-1
Measurement Error
  • < 1 % over the whole range with voltage variation
  • 0.05 %/°C with temperature variation
Operating Rate <= 360 operations/hour full load
Output Contacts 1 C/O + 1 C/O, 1 per threshold
Response Time < 200 ms (in the event of a fault)
Operating Position any position without derating
Net Weight 0.08 kg
Maximum Switching Voltage 250 V AC/DC
Reset Time 1500 ms time delay
Run-Up Delay At Power-Up 650 ms
Connections - Terminals
  • screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
Functionality overvoltage and undervoltage detection
[Ui] Rated Insulation Voltage 400 V IEC 60664-1
Overvoltage Category III IEC 60664-1
Quality Labels CE
Supply Voltage Limits 114-329 V AC
Mounting Support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Nominal Output Current 5 A
Local Signalling
  • for power ON LED (green)
  • for relay ON LED (yellow)
Mechanical Durability 30000000 cycles
Voltage Detection Threshold 114 V
Compatibility Code RM3
Housing Material self-extinguishing plastic
Control Circuit Frequency 50...60 Hz +/- 15 %
Measurement Accuracy +/- 10 % of the full scale value
Width 35 mm
Tightening Torque 0.6-1 N.m IEC 60947-1
Electrical Durability 10000 cycles
Repeat Accuracy
  • +/- 0.5 % input and measurement circuit
  • +/- 1 % time delay
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1504008EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation X
Circularity Profile ENVEOLI1504008EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • UL
  • C-tick
  • GL
  • CSA
  • GOST
Standards EN/IEC 60255-1
Non-Dissipating Shock Wave 4 kV
Dielectric Test Voltage 2 kV AC 50 Hz, 1 min
Electromagnetic Compatibility
  • emission standard for industrial environments EN/IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3
  • immunity for industrial environments NF EN/IEC 61000-6-2
Shock Resistance 5 gn IEC 60068-2-27
Ambient Air Temperature For Operation -20-50 °C
Vibration Resistance
  • 0.35 mm 5-57.6 Hz)IEC 60068-2-6
  • 1 gn 57.6-150 Hz)IEC 60255-21-1
Ip Degree Of Protection
  • IP20 IEC 60529 terminals)
  • IP30 IEC 60529 casing)
Pollution Degree 3 IEC 60664-1
Directives
  • 73/23/EEC - low voltage directive
  • 89/336/EEC - electromagnetic compatibility
Ambient Air Temperature For Storage -40-70 °C
Relative Humidity 95-95 % 55-55 °C IEC 60068-2-30
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews