Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
RM35JA32MR – Harmony, Modular 1-phase current control relay, 5 A, 2 CO, 0.15…15 A, 24…240 V AC/DC
RM35JA32MR
Harmony, Modular 1-phase current control relay, 5 A, 2 CO, 0.15…15 A, 24…240 V AC/DC

This Harmony RM35-JA relay allows monitoring of current control in single phase networks. This modular multi function single phase current control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a diagnostic button, sealable cover, simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Minimum Switching Current 10 mA 5 V DC
Maximum Switching Current 8 A AC
Range Of Product Harmony Control Relays
Measurement Range
  • 0.15...1.5 A E1-M terminals
  • 0.5...5 A E2-M terminals
  • 1.5...15 A E3-M terminals
  • 150 mA...15 A current AC/DC 50/60 Hz
Switching Capacity In Va 2000 VA
Product Or Component Type current control relay
Utilisation Category
  • AC-15 IEC 60947-5-1
  • DC-13 IEC 60947-5-1
  • AC-1 IEC 60947-4-1
  • DC-1 IEC 60947-4-1
Relay Name RM35JA
Contacts Type And Composition 2 C/O
Relay Type current control relay
Time Delay Type adjustable 0.1...30 s, +/- 10 % of the full scale value on crossing the threshold Tt
Relay Monitored Parameters
  • overcurrent or undercurrent in window mode
  • overcurrent or undercurrent detection
Maximum Power Consumption In Va 3.5 VA
[Us] Rated Supply Voltage 24...240 V AC/DC 50/60 Hz +/- 10 %
Safety Reliability Data
  • MTTFd = 296.8 years
  • B10d = 270000
Maximum Measuring Cycle 100 ms measurement cycle as true rms value
Switching Threshold Drift
  • <= 0.05 % per degree centigrade depending permissible ambient air temperature
  • <= 1 % within the supply voltage range
Control Circuit Voltage Limits 15 % + 10 % Un
Hysteresis
  • 5-50 % adjustable threshold setting
  • 3-3 % fixed full scale for window mode
Insulation Resistance > 100 MOhm 500 V DC IEC 60255-27
Measurement Error
  • < 1 % over the whole range with voltage variation
  • 0.05 %/°C with temperature variation
Internal Input Resistance
  • 0.015 Ohm
  • 0.005 Ohm
  • 0.05 Ohm
Output Contacts 2 C/O
Contacts Material cadmium free
Response Time <= 500 ms (on crossing the threshold)
Net Weight 0.12 kg
Threshold Setting 10...100 %
Maximum Switching Voltage 250 V AC
Reset Time 1500 ms at maximum voltage
Connections - Terminals
  • screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
  • screw terminals, 1 x 0.5...1 x 3.3 mm² AWG 20...AWG 12) solid without cable end
  • screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 14) flexible with cable end
Overvoltage Category
  • III IEC 60664-1
  • III UL 508
Insulation between supply and measurement
Time Delay Drift
  • <= 0.05 % per degree centigrade depending permissible ambient air temperature
  • <= 1 % within the supply voltage range
Setting Accuracy Of Time Delay 10 P
Supply Voltage Limits 20.4-264 V AC/DC
Mounting Support 35 mm DIN rail conforming to EN/IEC 60715
Nominal Output Current 8 A
Local Signalling
  • for relay ON LED (yellow)
  • for power ON LED (green)
Mechanical Durability 10000000 cycles
Housing Material self-extinguishing plastic
Resistance Across Terminals
  • 0.005 Ohm E3-M terminals
  • 0.015 Ohm E2-M terminals
  • 0.05 Ohm E1-M terminals
Width 35 mm
Tightening Torque 0.6-1 N.m IEC 60947-1
Maximum Power Consumption In W 1.5 W DC
Electrical Durability 100000 cycles
Run-Up Delay At Power-Up 0.3 s
Repeat Accuracy
  • +/- 0.5 % input and measurement circuit
  • +/- 2 % time delay
Setting Accuracy Of The Switching Threshold +/- 10 % of the full scale
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1504008EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI1504008EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • CE
  • GL
  • CCC
  • EAC
  • RCM
  • UL
  • CSA
Standards EN/IEC 60255-1
Immunity To Microbreaks 50 ms
Dielectric Test Voltage 2.5 kV AC 50 Hz, 1 min IEC 60255-27
Electromagnetic Compatibility
  • immunity for residential, commercial and light-industrial environments EN/IEC 61000-6-1
  • immunity for industrial environments EN/IEC 61000-6-2
  • emission standard for industrial environments EN/IEC 61000-6-4
  • electrostatic discharge 6 kV contact discharge)level 3 IEC 61000-4-2
  • electrostatic discharge 8 kV air discharge)level 3 IEC 61000-4-2
  • radiated radio-frequency electromagnetic field immunity test 10 V/mlevel 3 IEC 61000-4-3
  • electrical fast transient/burst immunity test 4 kV direct)level 4 IEC 61000-4-4
  • electrical fast transient/burst immunity test 2 kV capacitive coupling)level 4 IEC 61000-4-4
  • surge immunity test 4 kV common mode)level 4 IEC 61000-4-5
  • surge immunity test 2 kV differential mode)level 4 IEC 61000-4-5
  • conducted and radiated emissionsclass B group 1 CISPR 11
  • conducted and radiated emissionsclass B CISPR 22
  • emission standard for residential, commercial and light-industrial environments except radiated emission) EN/IEC 61000-6-3
Shock Resistance
  • 15 gn 11 ms) not in operation IEC 60068-2-27
  • 5 gn 11 ms) in operation IEC 60068-2-27
Ambient Air Temperature For Operation
  • -20-50 °C 60 Hz
  • -20-60 °C 50 Hz
Vibration Resistance
  • 0.075 mm 10-58.1 Hz) not in operation IEC 60068-2-6
  • 1 gn 10-58.1 Hz) not in operation IEC 60068-2-6
  • 0.035 mm 58.1-150 Hz) in operation IEC 60068-2-6
  • 0.5 gn 58.1-150 Hz) in operation IEC 60068-2-6
Environmental Characteristic 3K3 C
Ip Degree Of Protection
  • IP20 IEC 60529 terminals)
  • IP50 IEC 60529 front panel)
  • IP30 IEC 60529 housing)
Pollution Degree
  • 3 IEC 60664-1
  • 3 UL 508
Ambient Air Temperature For Storage -40-70 °C
Relative Humidity 93-97 % 25-55 °C IEC 60068-2-30