This Harmony RM35-BA control relay allows monitoring of pump control. This modular pump control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market medium form-factors with 35mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 3-pole DIN device. It also offers a selectable memory function, integral LED for indicating control status, sealable cover, with simple and precise settings with screw trimmers. It provides automatic shutdown management and fault information to user for a quick fault identification and troubleshooting. Multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Minimum Switching Current 10 mA 5 V DC
Maximum Switching Current 5 A AC/DC
Range Of Product Harmony Control Relays
Measurement Range 1...10 A AC
Switching Capacity In Va 1250 VA
Product Or Component Type pump control relay
Utilisation Category
  • AC-12 IEC 60947-5-1
  • AC-13 IEC 60947-5-1
  • AC-14 IEC 60947-5-1
  • AC-15 IEC 60947-5-1
  • DC-12 IEC 60947-5-1
  • DC-13 IEC 60947-5-1
Relay Name RM35BA
Relay Type pump control relays
Product Specific Application for 3-phase and single-phase pump
Time Delay Type
  • adjustable 1...60 s, +/- 10 % Ti on energisation
  • fixed 0.3 s reset on terminal Y2
  • adjustable 0.1...10 s, +/- 10 % Tt on crossing the threshold
Relay Monitored Parameters
  • overcurrent and undercurrent control
  • phase sequence on 3-phase supply
  • phase failure on 3-phase supply
Maximum Power Consumption In Va 5 VA AC
Warranty 18 months
Maximum Measuring Cycle 140 ms as true rms value
Hysteresis 5-5 % threshold
Insulation Resistance
  • > 500 MOhm 500 V DC between supply and relay output 60255-5
  • > 500 MOhm 500 V DC between measurement and relay output 60664-1
  • > 1 MOhm 500 V DC between supply and measurement 60255-5
  • > 500 MOhm 500 V DC between supply and relay output 60664-1
  • > 500 MOhm 500 V DC between measurement and relay output 60255-5
  • > 1 MOhm 500 V DC between supply and measurement 60664-1
[Us] Rated Supply Voltage
  • 208...480 V AC 3 phase
  • 230 V AC 1 phase
Operating Rate <= 360 operations/hour full load
Status Led
  • 1 LED Green power ON
  • 1 LED Yellow fault
  • 1 LED Yellow relay ON
Output Contacts 1 C/O
Reset Time 2000 ms
Marking
  • CE : EMC 89/336/EEC
  • CE : 73/23/EEC
Response Time < 300 ms (in the event of a fault)
Input Current
  • 11 A permanent at 25 °C E1-L2 terminals
  • 50 A non repetitive < 1 s at 25 °C E1-L2 terminals
Maximum Switching Voltage 250 V AC/DC
Connections - Terminals
  • screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
[Ui] Rated Insulation Voltage 400 V IEC 60664-1
Overvoltage Category III IEC 60664-1
Supply Voltage Limits 183-528 V AC
Mounting Support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Nominal Output Current 5 A
Mechanical Durability 30000000 cycles
Housing Material self-extinguishing plastic
Resistance Across Terminals 0.01 Ohm E1-L2 terminals
Operating Position any position
Control Circuit Voltage Limits 15 % + 10 % Un
Measurement Accuracy +/- 10 % of the full scale value
Measurement Error
  • 1 % by volt over the whole range
  • +/- 0.05 %/°C
Width 35 mm
Tightening Torque 0.6-1 N.m IEC 60947-1
Electrical Durability 100000 cycles
[Us] Rated Supply Voltage
  • 208...480 V AC 3 phase
  • 230 V AC single phase
Run-Up Delay At Power-Up 0.5 s
Supply Frequency 50/60 Hz +/- 10 %
Repeat Accuracy
  • +/- 1 % input and measurement circuit
  • +/- 1 % time delay
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1504008EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI1504008EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • C-tick
  • CSA
  • GOST
  • UL
  • GL
Ambient Air Temperature For Operation -20-50 °C
Standards EN/IEC 60255-6
Immunity To Microbreaks 500 ms
Electromagnetic Compatibility
  • emission standard for industrial environments EN/IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3
  • immunity for industrial environments NF EN/IEC 61000-6-2
Shock Resistance 15 gn 11 ms IEC 60255-21-1
Vibration Resistance
  • 0.35 mm 5-57.6 Hz)IEC 60068-2-6/IEC 60255-21-1
  • 1 gn 57.6-150 Hz)IEC 60068-2-6/IEC 60255-21-1
Ip Degree Of Protection
  • IP20 IEC 60529 terminals)
  • IP30 IEC 60529 casing)
Pollution Degree 3 IEC 60664-1
Ambient Air Temperature For Storage -40-70 °C
Relative Humidity 95-95 % 55-55 °C IEC 60068-2-30
Dielectric Strength 2 kV AC 50 Hz shock wave 4 kV)
Documents