Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
RM17TU00 – Harmony, Modular multifunction 3-phase supply control relay, 5 A, 1 CO, 208…480 V AC
RM17TU00
Harmony, Modular multifunction 3-phase supply control relay, 5 A, 1 CO, 208...480 V AC

This Harmony RM17-TU relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase supply control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. The product monitors its own power supply, when the power supply is abnormal, the output relay de-energizes. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Range Of Product Harmony Control Relays
Measurement Range 208...480 V voltage AC
Switching Capacity In Va 1250 VA
Product Or Component Type 3-phase control relay
Relay Name RM17TU
Contacts Type And Composition 1 C/O
Relay Type multifunction control relay
Product Specific Application for 3-phase supply
Time Delay Type adjustable 0.1...10 s, +/- 10 % of the full scale value
Relay Monitored Parameters
  • undervoltage detection
  • phase sequence
  • phase failure detection
[Uc] Control Circuit Voltage 208...480 V
Warranty 18 months
Voltage Range 208...480 V phase to phase
Safety Reliability Data
  • MTTFd = 502.2 years
  • B10d = 470000
Minimum Switching Current 10 mA 5 V DC
Maximum Measuring Cycle 150 ms measurement cycle as true rms value
Control Circuit Voltage Limits 12 % + 10 % Un
Maximum Switching Current
  • 5 A AC
  • 5 A DC
Hysteresis 2-2 %
Insulation Resistance
  • > 500 MOhm 500 V DC IEC 60255-5
  • > 500 MOhm 500 V DC IEC 60664-1
Measurement Error
  • < 0.05 %/°C with temperature variation
  • < 1 % over the whole range with voltage variation
Operating Rate <= 360 operations/hour full load
Phase Failure Sensitivity 0.7 Un
Power Consumption In Va 0-22 VA 400 V AC 50 Hz
Output Contacts 1 C/O
Adjustment Of Asymmetry Threshold 5...15 % of Un selected
Marking CE
Response Time < 200 ms (in the event of a fault)
Operating Position any position without derating
Utilisation Category
  • AC-12 IEC 60947-5-1
  • AC-13 IEC 60947-5-1
  • AC-14 IEC 60947-5-1
  • AC-15 IEC 60947-5-1
  • DC-12 IEC 60947-5-1
  • DC-13 IEC 60947-5-1
Net Weight 0.13 kg
Maximum Switching Voltage
  • 250 V AC
  • 250 V DC
Measurement Voltage Limits 183-528 V AC
Reset Time 1500 ms time delay
Connections - Terminals
  • screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end
  • screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end
  • screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end
  • screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
[Ui] Rated Insulation Voltage 400 V IEC 60664-1
Overvoltage Category III IEC 60664-1
Supply Voltage Limits 183-528 V AC
Mounting Support 35 mm symmetrical DIN rail conforming to EN/IEC 60715
Nominal Output Current 5 A
Local Signalling
  • for power ON LED (green)
  • for relay ON LED (yellow)
Mechanical Durability 30000000 cycles
Housing Material self-extinguishing plastic
Control Circuit Frequency 50...60 Hz +/- 10 %
Threshold Adjustment Voltage
  • -2...-12 % in the range 208 V AC
  • -2...-17 % in the range 220 V AC
  • 2...20 % of Un selected
  • +2...+10 % in the range 480 V AC
Width 17.5 mm
Tightening Torque 0.6-1 N.m IEC 60947-1
Electrical Durability 100000 cycles
Run-Up Delay At Power-Up 650 ms
Supply Frequency 50/60 Hz +/- 10 %
Repeat Accuracy
  • 0.5 % input and measurement circuit
  • 3 % time delay
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1504008EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation X
Circularity Profile ENVEOLI1504008EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • GL
  • GOST
  • UL
  • C-tick
  • CSA
Standards EN/IEC 60255-1
Non-Dissipating Shock Wave
  • 4 kV IEC 60255-5
  • 4 kV IEC 60664-1
  • 4 kV IEC 61000-4-5
Dielectric Test Voltage
  • 2 kV AC 50 Hz, 1 min IEC 60255-5
  • 2 kV AC 50 Hz, 1 min IEC 60664-1
Electromagnetic Compatibility
  • emission standard for industrial environments EN/IEC 61000-6-4
  • emission standard for residential, commercial and light-industrial environments EN/IEC 61000-6-3
  • immunity for industrial environments EN/IEC 61000-6-2
Shock Resistance 15 gn 11 ms IEC 60255-21-1
Ambient Air Temperature For Operation -20-50 °C
Vibration Resistance
  • 0.35 mm 5-57.6 Hz)IEC 60068-2-6
  • 1 gn 57.6-150 Hz)IEC 60255-21-1
Ip Degree Of Protection
  • IP20 IEC 60529 terminals)
  • IP30 IEC 60529 casing)
Pollution Degree 3 IEC 60664-1
Directives
  • 73/23/EEC - low voltage directive
  • 89/336/EEC - electromagnetic compatibility
Ambient Air Temperature For Storage -40-70 °C
Relative Humidity 95-95 % 55-55 °C IEC 60068-2-30
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews