This Harmony RE22 modular single function timer can be set between 1 seconds and 300 hours. It provides function K and it is mountable on DIN rail. This modular single function timing relay is ideal for providing timing control in automation systems such as automatic door opening, alarm, lighting in toilets and car park barriers. It has one of market slimmest form-factors with 22.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 2-pole DIN device. It also offers a sealable cover, simple and precise settings with rotary trimmers. Selectable timing range offers a one stop solution for your power management system. Single function timer for a simple integration in hard-wired logic schematics, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0
Brand: Schneider Electric
Add to Quote CatalogueDiscrete Output Type | relay |
---|---|
Range Of Product | Harmony Timer Relays |
Product Or Component Type | single function relay |
Nominal Output Current | 5 A |
Device Short Name | RE22 |
Power Consumption In W | 2 W 240 V DC |
Safety Reliability Data |
|
Contacts Type And Composition | 2 C/O timed contact, cadmium free |
Setting Accuracy Of Time Delay | +/- 10 % of full scale 25 °C IEC 61812-1 |
Creepage Distance | 4 kV/3 IEC 60664-1 |
Maximum Delay Response | 350 ms |
Control Type |
|
Insulation Resistance | 100 MOhm 500 V DC IEC 60664-1 |
Immunity To Microbreaks | 10 ms |
Power Consumption In Va | 3-3 VA 240 V AC |
Switching Capacity In Va | 1250 VA |
Maximum Switching Current | 5 A |
Voltage Range | 0.85...1.1 Us |
Net Weight | 0.1 kg |
Mounting Position | any position |
Voltage Drift | +/- 0.2 %/V |
Reset Time | 100 ms on de-energisation |
Maximum Switching Voltage | 250 V AC |
Connections - Terminals |
|
[Us] Rated Supply Voltage | 24...240 V AC/DC 50/60 Hz |
Temperature Drift | +/- 0.05 %/°C |
Time Delay Range |
|
Minimum Switching Current | 10 mA 5 V DC |
Overvoltage Category | III IEC 60664-1 |
Input Voltage | <= 2.4 V |
Mounting Support | 35 mm DIN rail conforming to EN/IEC 60715 |
Electrical Durability |
|
Mechanical Durability | 10000000 cycles |
Housing Material | self-extinguishing |
Status Led |
|
[Uimp] Rated Impulse Withstand Voltage | 5 kV 1.2-50 µs IEC 60664-1 |
Width | 22.5 mm |
Time Delay Type | delay on de-energization |
Tightening Torque | 0.6-1 N.m IEC 60947-1 |
Supply Frequency | 50...60 Hz +/- 5 % |
Repeat Accuracy | +/- 0.5 % IEC 61812-1 |
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP1401008EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
China Rohs Regulation | X |
Circularity Profile | ENVEOLI1401008EN |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Product Certifications |
|
Ambient Air Temperature For Operation | -20-60 °C |
Standards |
|
Electromagnetic Compatibility |
|
Dielectric Strength | 2.5 kV 1 mA/1 minute 50 Hz between relay output and power supply basic insulation IEC 61812-1 |
Shock Resistance |
|
Vibration Resistance | 20 m/s² 10-150 Hz)IEC 60068-2-6 |
Pollution Degree | 3 IEC 60664-1 |
Directives |
|
Ambient Air Temperature For Storage | -40-70 °C |
Relative Humidity | 95-95 % 25-55 °C |
Ip Degree Of Protection |
|
Powered by
Based on 2 User Reviews
1619 Boyd St, Santa Ana, CA 92705
(714) 835-6211
(714) 972-2366