Specifications
Terminal Block Type passthrough
Accessory / Separate Part Category connection accessory
Product Or Component Type terminal block
Product Name TR
Length 58.8 mm
Range Linergy
Mounting Mode clip-on
Terminal Block Level 1
Nominal Cross Section 1.5 mm²
Quantity Per Set set of 50
Color Gray
Device Short Name TRH
Dielectric Loss
  • 0.01 at 1 MHz IEC 60250
  • 0.01 at 1 MHz VDE 0303-T4
Height 42.8 mm
Number Of Terminals 2
Cable Cross Section
  • upstream 0.14-4 mm², solid
  • downstream 0.2-1.5 mm², flexible with cable end
  • upstream 0.2-1.5 mm², flexible without cable end
Connection Position top
Number Of Measurement Input 2
Tool Type
  • connection screwdriver
  • disconnection screwdriver
  • without tool
Net Weight 9.7 g
Flame Retardance V0 0.8 mm UL 94
Connections - Terminals
  • 1 x screw terminal upstream M3)
  • 1 x IDC downstream M3)
Wire Stripping Length 9 mm
Resistivity
  • 10000 MΩ.m IEC 60093
  • 10000 MΩ.m VDE 0303-T30
Dielectric Constant 3.7 at 1 MHz
Material
  • polyamide 6/6 insulating case
  • copper alloy connector and screw
  • copper alloy commoning link
  • chromium-nickel steel spring
Surface Resistance
  • 1000 GΩ IEC 60093
  • 1000 GΩ VDE 0303-T30
Width 5.2 mm
Range Compatibility
  • Prisma G
  • Prisma P
  • Prisma PH
  • Prisma Pack
  • Spacial
  • Kaedra
  • Pragma
  • TeSys
Tightening Torque 0.5-0.6 N.m
Product Compatibility Spacial enclosures
Line Rated Current
  • 17-17 A EN/IEC 60947-7-1
  • 10-10 A cURus
  • 10-10 A CSA
  • 16.5-16.5 A ATEX Exe II Ex II 2 GD
Creep Resistance
  • 500 CTI (> 400 kB) IEC 60093
  • 500 CTI (> 400 kB) VDE 0303-T30
[Ue] Rated Operational Voltage
  • 800 V EN/IEC 60947-7-1
  • 600 V cURus
  • 600 V CSA
  • 550 V ATEX Exe II Ex II 2 GD
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1304013EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Nickel (Metallic), which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Halogen Content Performance Halogen free plastic parts product
Product Certifications
  • cURus
  • IEC-Ex
  • CSA
  • EAC
  • ATEX
Ambient Air Temperature For Operation
  • -40-130 °C IEC 60216-1
  • -40-130 °C VDE 0304-T21
Dielectric Strength 1000 V IEC 60243-1