Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
METSEPM5110 – power meter PowerLogic PM5110, modbus, up to 15th Harmonic, 1DO 33 alarms
METSEPM5110
power meter PowerLogic PM5110, modbus, up to 15th Harmonic, 1DO 33 alarms

This device is a flush-mount energy meter with a 96mm by 96mm backlit LCD display. The meter provides Class 0.5S accuracy per IEC 62053-22 standard and 64 samples per cycle. The meter will measure Energy, Active and Reactive Power, Voltage, Current, Frequency, Power Factor and up to 15th Harmonic. The meter will function in a 50Hz or 60Hz network and accepts supply voltage ranging from 100 to 415 VAC and 125 to 250 VDC. Line rated current for this meter is 1A or 5A input and will support Single Phase and Neutral, Three Phase, or Three Phase and Neutral configurations. The range of measurement voltage between Phases is 35 to 690 VAC at 47 to 63 Hz. Measurement range between Phase and Neutral is 20 to 400VAC at 47 to 63 Hz. Communication protocol is Modbus RTU and ASCII 2 wires with RS485 port support. The meter also has one digital pulse output and 33 configurable alarms. Product dimensions are as follows: width 3.78 inches (96 millimetres), depth 2.83 inches (72 millimetres), height 3.78 inches (96 millimetres) and product weight 13.4 onces (380 g).

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Product Or Component Type power meter
Product Name PowerLogic PM5000
Range PowerLogic
Device Short Name PM5110
Network Frequency
  • 50 Hz
  • 60 Hz
Communication Port Support RS485
Power Quality Analysis up to the 15th harmonic
Height 96 mm
Measurement Voltage
  • 35-760 V AC 45...65 Hz between phases
  • 20-440 V AC 45...65 Hz between phase and neutral
Sampling Rate 64 samples/cycle
Standards
  • UL 61010-1
  • EN 50470-3
  • EN 50470-1
  • IEC 62053-22
  • IEC 60529
  • IEC 62053-24
  • IEC 61557-12
Number Of Outputs 1 digital
Product Certifications
  • CE IEC 61010-1
  • cULus UL 61010-1
Type Of Measurement
  • current
  • voltage
  • frequency
  • power factor
  • energy
  • active and reactive power
Communication Port Protocol
  • Modbus RTU and ASCII 9.6, 19.2 and 38.4 kbauds even/odd or none - 2 wires 2500 V
  • JBUS
Frequency Measurement Range 45-65 Hz
Ride-Through Time
  • 80 ms 120 V AC typical
  • 100 ms 230 V AC typical
  • 100 ms 415 V AC typical
  • 50 ms 125 V DC typical
Display Resolution 128 x 128 pixels
Number Of Inputs 0
Net Weight 380 g
Depth 72 mm
Measurement Current 50-8500 mA
Connections - Terminals
  • voltage circuit screw terminal block4
  • control circuit screw terminal block2
  • current transformer screw terminal block6
  • input/output circuit screw terminal block6
  • RS485 link screw terminal block4
[Us] Rated Supply Voltage
  • 90...450 V AC 45...65 Hz
  • 100...300 V DC
Mounting Mode flush-mounted
Measurement Accuracy
  • active energy +/- 0.5 %
  • reactive energy +/- 2 %
  • active power +/- 0.5 %
  • apparent power +/- 0.5 %
  • frequency +/- 0.05 %
  • power factor +/- 0.5
  • current +/- 0.5 %
  • voltage +/- 0.5 %
  • apparent energy +/- 0.5 %
  • reactive power +/- 2 %
Mounting Support framework
Poles Description
  • 1P + N
  • 3P + N
  • 3P
Data Recording
  • time stamping
  • min/max of instantaneous values
Line Rated Current
  • 1 A
  • 5 A
Analogue Input Type
  • voltage 5 MOhm)
  • current <= 0.3 mOhm)
Width 96 mm
Display Type monochrome graphic LCD
Device Application power monitoring
Accuracy Class class 0.5S active energy IEC 62053-22
Maximum Power Consumption In Va 11 VA 415 V
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1305025
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI1305025
Eu Rohs Directive Compliant
Ambient Air Temperature For Operation
  • -25-70 °C meter
  • -20-70 °C display
  • -25--20 °C with reduced performance) display
Electromagnetic Compatibility
  • voltage dips and interruptions immunity testclass A IEC 61000-4-11
  • limits for harmonic current emissionsclass A IEC 61000-3-2
  • electrostatic dischargelevel 4 IEC 61000-4-2
  • conducted RF disturbanceslevel 3 IEC 61000-4-6
  • magnetic field at power frequencylevel 4 IEC 61000-4-8
  • immunity to conducted disturbances 150 kHz...80 MHz IEC 61000-4-6
  • electrical fast transient/burst immunity test IEC 61000-4-4
  • radiated radio-frequency electromagnetic field immunity test IEC 61000-4-3
  • voltage dips and interruptions immunity test IEC 61000-4-11
  • conducted and radiated emissionsclass B EN 55022
  • surge immunity test IEC 61000-4-5
Pollution Degree 2
Ambient Air Temperature For Storage -40-85 °C
Relative Humidity 5-95 % 50-50 °C non-condensing
Ip Degree Of Protection
  • display IP54 IEC 60529
  • rear IP30 IEC 60529
Operating Altitude 6561.68 ft (2000 m) CAT III