PowerLogic ION7400 utility feeder power meters combine capabilities not typically available in compact meters. They offers a hight flexibility and usability, along with accurate 3-phase energy and power measurements with data logging. Use Power Monitoring Expert software for data analysis or share operation data with SCADA systems through multiple communication channels and protocols. Certified by third party labs for energy accuracy (IEC 62052-11, IEC 62052-22, IEC 62052-24) and power quality (IEC 62586-2, IEC 61000-4-30 Class S). Cybersecurity features include secure protocols (HTTPS, SFTP), security event logging, Syslog protocol. Ability to enable/disable communication ports, and 16 user configurable accounts. With 512 MB of memory to support 50 data logs, 50+ user-definable alarms, waveform captures, 1/2 cycle RMS logging, custom web pages, min/max logs, energy trends, and Time of Use. The ability to timestamp events to +/-1 ms utilizing time synchronization method that include PTP (IEEE1588), NTP, IRIG-B, GPS ASCII (RS485) and network time set function. 3 digital inputs and one digital output. I/O option modules include 2 relays and 6 digital inputs or 2 analog outputs and 4 analog inputs. Wide control power range of 20-60 VDC. Operating environment of -25 to +70C; Humidity rating of 5% to 95%; Altitude up to 3000 m. DIN rail mounting (no display).

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Product Or Component Type power meter
Product Name PowerLogic ION7400
Range PowerLogic
Device Short Name ION7413
Communication Network Type IPv6 (internet protocol)
Network Frequency
  • 50 Hz
  • 60 Hz
Communication Port Support
  • ETHERNET
  • screw terminal block RS485
  • mini B USB USB
Power Quality Analysis
  • EN 50160 2010 compliance report
  • IEEE 519 2014 compliance report
  • IEC 61000-4-30 class S power quality measurement
  • up to the 63rd harmonic
  • harmonic distortion
  • waveform capture
  • voltage sag and swell detection
  • programmablity (logic and math functions)
  • IEC 62586 power quality monitoring
  • IEC 61000-4-15 flicker
  • disturbance direction detection
Height 90.5 mm
Measurement Voltage
  • 57-400 V AC 42...69 Hz between phase and neutral
  • 100-690 V AC 42...69 Hz between phases
Sampling Rate 256 samples/cycle
Standards
  • IEC 61326-1
  • IEC 62053-22
  • IEC 62053-24
  • IEC 62052-11
  • IEC 61557-12
  • IEEE 1588
  • IEC 62586
Memory Capacity 512 MB
Number Of Outputs 1 pulse
Product Certifications
  • CE
  • cULus
  • N998
Type Of Measurement
  • current
  • voltage
  • frequency
  • active and reactive power total
  • apparent power total
  • power factor total
  • active and reactive power per phase, rms
  • apparent power per phase, rms
  • power factor per phase, rms
  • active and reactive energy
  • apparent energy
Communication Port Protocol
  • Modbus RTU 115 kbauds - 2-wire
  • ION 115 kbauds - 2-wire
  • DNP3
  • IEC 61850
  • Modbus TCP/IP
  • Ethernet Modbus TCP/IP daisy chain 10/100 Mbit/s
  • RSTP 801.1d 2004
  • DLMS
Power Consumption In W 17 W
Frequency Measurement Range 42-69 Hz
Communication Service
  • NTP time synchronization
  • SMTP e-mail notification
  • RSTP support
  • DHCP
  • SNMP
  • PTP time synchronization
Number Of Inputs
  • 3 digital 30 V AC
  • 3 digital 60 V DC
Net Weight 528 g
Type Of Installation indoor installation
Depth 90.8 mm
Measurement Current 50-10000 mA
Information Displayed
  • voltage
  • current
  • frequency
  • power
  • energy consumption
  • harmonic distortion
[Us] Rated Supply Voltage 20...60 V DC +/- 10 %
Mounting Mode clip-on
Measurement Accuracy
  • current +/- 0.1 %
  • voltage +/- 0.1 %
  • active energy +/- 0.2 %
Mounting Support DIN rail
Poles Description
  • 1P + N
  • 3P
  • 3P + N
Data Recording
  • sequence of event recording
  • trending/forecasting
  • harmonics logs
  • time stamping
  • GPS synchronisation
  • waveform logs
  • min/max of instantaneous values
  • sag and swell logs
  • data logs
  • event logs
  • alarm logs
Line Rated Current
  • 10 A
  • 1 A
  • 5 A
Cybersecurity
  • enable/disable communication ports
  • robust security logs
  • port hardening
  • password protection
  • Syslog protocol support
Isolation Voltage
  • III400-690 V conforming to IEC 61010-1:ed. 3
  • III400-690 V conforming to EN 61010-1:ed. 3
  • III347-600 V conforming to UL 61010-1:ed. 3
  • III347-600 V conforming to CSA C22.2 No 61010-1:ed. 3
Analogue Input Type
  • voltage 5 MOhm)
  • current 0.3 mOhm)
Web Services
  • customizable home page
  • file upload/download via FTP
  • file upload/download via SFTP
  • web server
  • alarm notification by e-mail
  • viewing of captured waveform (FTP)
  • viewing of captured waveform (web)
  • HTTPS server
Width 90.5 mm
Display Type Without Display
Device Application
  • WAGES metering
  • power monitoring
  • data aggregation
  • revenue billing
Accuracy Class
  • class 0.2S active energy IEC 62053-22
  • class 0.2 active energy ANSI C12.20
  • class 0.2 active power IEC 61557-12
  • class 0.5S reactive energy IEC 62053-24
  • class 0.5 power factor IEC 61557-12
  • class 0.2 voltage IEC 61557-12
  • class 0.2 current IEC 61557-12
  • class 0.2 frequency IEC 61557-12
  • class 0.2 active energy IEC 61557-12
Installation Category III
Environmental Disclosure ENVPEP1512006EN
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI1512006EN
Eu Rohs Directive Compliant
Ambient Air Temperature For Operation -25-70 °C
Electromagnetic Compatibility
  • electrostatic discharge IEC 61000-4-2
  • radiated radio-frequency electromagnetic field immunity test IEC 61000-4-3
  • electrical fast transient/burst immunity test IEC 61000-4-4
  • surge immunity test IEC 61000-4-5
  • conducted RF disturbances IEC 61000-4-6
  • magnetic field at power frequency IEC 61000-4-8
  • voltage dips and interruptions immunity test IEC 61000-4-11
  • immunity to impulse waves IEC 61000-4-12
  • conducted and radiated emissions EN 55022
  • conducted and radiated emissions EN 55011
  • conducted and radiated emissions FCC part 15
  • conducted and radiated emissions ICES-003
  • conducted RF disturbances 2...150 Hz) CLC/TR 50579
  • surge withstand IEEE C37.90.1
Ambient Air Temperature For Storage -40-85 °C
Relative Humidity 5-95 %
Ip Degree Of Protection IP30 IEC 60529
Operating Altitude 9842.52 ft (3000 m)