This multi-circuit power meter is part of the PowerLogic EM4900 Series. This device is a multi-circuit power meters that make it easy to add many revenue-grade metering points. Without having to purchase, mount, wire and commission individual energy meters. This version measures current, voltage, power and energy consumption of up to 14 3-phase circuits with one board configuration. It offers Modbus RTU communications. Measurement accuracy is plus or minus 1 % with LVCT0xxxx0S split core, or plus or minus 0.5 % with LVCT2xxxx0S split core. The printed board can be installed in a panel. Mechanical dimensions of the base board are 226 mm in width, 146 mm in height and 71 mm in depth.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Network Frequency
  • 50 Hz
  • 60 Hz
Type Of Measurement
  • current per phase, rms
  • current average
  • phase angle
  • active power total
  • active power per phase
  • apparent power total
  • apparent power per phase
  • power factor average
  • power factor per phase
  • active energy
Power Monitoring basic instrumentation
Product Or Component Type multi-circuit energy meter
Product Name PowerLogic EM4900
Range PowerLogic
Energy Management
  • sub billing and cost allocation
  • billing analysis
[Us] Rated Supply Voltage 100...277 V AC 50/60 Hz
Device Application sub billing
Device Short Name EM4914
Metering Type
  • demand power P
  • demand current I1, I2, I3, peak demand current IM1, IM2, IM3
Communication Port Support RS485 screw block terminal
Measurement Voltage
  • 150-480 V AC 50/60 Hz between phases
  • 90-277 V AC 50/60 Hz between phase and neutral
Sampling Rate 256 samples/cycle
Communication Port Protocol Modbus RTU 9600, 19200, 38400 bps even/odd or none - 2 or 4 wires
Communication Service updating firmware
Communication Of Data
  • high current alarm
  • low current alarm
  • total energy
  • high-high current alarm
  • under voltage alarm
  • over voltage alarm
  • low-low current alarm
Measurement Accuracy
  • power +/- 0.5 % of the measuring range
  • energy +/- 0.5 % of the measuring range
  • current +/- 0.5 % of the measuring range
  • voltage +/- 0.5 % of the measuring range
Refresh Time
  • 2 s Modbus)
  • 14 s BACnet)
  • 20 s SNMP)
Data Recording
  • maximum of demand active power
  • maximum of instantaneous current
  • maximum of demand current
Analogue Input Type
  • 42 solid core CT 0.333 V single pole
  • 21 solid core CT 0.333 V single phase
  • 14 solid core CT 0.333 V three phase
  • 42 split core CT 0.333 V single pole
  • 21 split core CT 0.333 V single phase
  • 14 split core CT 0.333 V three phase
Rohs Exemption Information Yes
Mercury Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Eu Rohs Directive Compliant
Ambient Air Temperature For Operation 0-60 °C
Standards
  • IEC 61010
  • UL 508
Net Weight 1.5 kg
Pollution Degree 2
Mounting Mode wall mount
Ambient Air Temperature For Storage -40-70 °C
Width 288 mm
Depth 146 mm
Installation Category III