This multi-circuit power meter is part of the PowerLogic EM4900 Series. This device is a multi-circuit power meters that make it easy to add many revenue-grade metering points. Without having to purchase, mount, wire and commission individual energy meters. This version measures current, voltage, power and energy consumption of up to 4 3-phase circuits with one board configuration. It also offers Ethernet and serial communications. Measurement accuracy is plus or minus 1 % with LVCT0xxxx0S split core, or plus or minus 0.5 % with LVCT2xxxx0S split core. The printed board is installed in a sturdy metal enclosure. Mechanical dimensions of the main unit are 253 mm in width, 353 mm in height and 71 mm in depth.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Network Frequency
  • 60 Hz
  • 50 Hz
Energy Management
  • sub billing and cost allocation
  • billing analysis
[Us] Rated Supply Voltage 100...277 V AC 50/60 Hz
Type Of Measurement
  • current per phase, rms
  • current average
  • phase angle
  • active power total
  • active power per phase
  • apparent power total
  • apparent power per phase
  • power factor average
  • power factor per phase
  • active energy
Power Monitoring basic instrumentation
Product Or Component Type multi-circuit energy meter
Product Name PowerLogic EM4900E
Device Application sub billing
Device Short Name EM4904
Metering Type
  • demand power P
  • demand current I1, I2, I3, peak demand current IM1, IM2, IM3
Range PowerLogic
Communication Port Support
  • spring connector RS485
  • RJ45
Measurement Accuracy
  • power +/- 0.5 % of the measuring range
  • energy +/- 0.5 % of the measuring range
  • current +/- 0.5 % of the measuring range
  • voltage +/- 0.5 % of the measuring range
Measurement Voltage
  • 150-480 V AC 50/60 Hz between phases
  • 90-277 V AC 50/60 Hz between phase and neutral
Sampling Rate 256 samples/cycle
Refresh Time
  • 2 s Modbus)
  • 14 s BACnet)
  • 20 s SNMP)
Communication Port Protocol
  • Modbus RTU 9600, 19200, 38400 bps even/odd or none - 2 wires
  • Modbus TCP 9600, 19200, 38400 bps even/odd or none - 2 wires
  • SNMP
  • BACnet IP 10, 100 Mbits
  • BACnet MS/TP
Communication Service updating firmware
Data Recording
  • maximum of demand active power
  • maximum of instantaneous current
  • maximum of demand current
Analogue Input Type
  • 12 solid core CT 0.333 V single pole
  • 6 solid core CT 0.333 V single phase
  • 4 solid core CT 0.333 V three phase
  • 12 split core CT 0.333 V single pole
  • 6 split core CT 0.333 V single phase
  • 4 split core CT 0.333 V three phase
Web Services web server
Communication Of Data
  • high-high current alarm
  • under voltage alarm
  • high current alarm
  • low current alarm
  • total energy
  • over voltage alarm
  • low-low current alarm
Rohs Exemption Information Yes
Mercury Free Yes
Eu Rohs Directive Compliant
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Ambient Air Temperature For Operation 0-60 °C
Height 70 mm
Pollution Degree 2
Mounting Mode wall mount
Ambient Air Temperature For Storage -40-70 °C
Standards
  • UL 508
  • IEC 61010
Width 253 mm
Depth 307 mm
Net Weight 1.5 kg
Installation Category III