This multi-circuit power meter is part of the PowerLogic EM4000 Series. This compact multi-circuit energy meter enables reliable metering of building electrical loads with a low installation cost-per-point. It combine revenue-accurate electricity sub-metering with advanced communications technology. It is ideal for departmental metering applications and M&V within office, condominiums, malls and other multi-user environments. This version monitor up to 24 tenants with a single device, combined with 0.333 volt split or solid core current transducer. Designed for 277 (phase neutral) or 480 volts (phase phase) networks, working at 60 Hz. Measurement accuracy is plus or minus 0.5 %, compliant with ANSI C12.1 and C12.20 Class 0.5 ; IEC 62053-22 Class 0.5S. The printed board is installed in a Type 1 black enclosure, with an integrated backlit LCD display, 2 lines, on the door. Mechanical dimensions are 335 mm in width, 305 mm in height and 55 mm in depth ; for 4 kg.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Network Frequency 60 Hz
Power Quality Analysis compliance monitoring
Type Of Measurement
  • current per phase, rms
  • negative active energy
  • voltage per phase, rms
  • negative reactive energy
  • apparent energy
  • pulse count
  • active and reactive power
  • apparent power
  • positive active energy
  • positive reactive energy
Power Monitoring basic instrumentation
Product Or Component Type multi-circuit energy meter
Product Name PowerLogic EM4000
Range PowerLogic
Energy Management
  • sub billing and cost allocation
  • billing analysis
[Us] Rated Supply Voltage 120 V AC 60 Hz
Device Application sub billing
Device Short Name EM4033
Communication Port Support
  • RJ45 ETHERNET
  • RS485
Measurement Voltage
  • 80-480 V without PTs
  • 480-999000 V with external PTs
Sampling Rate 256 samples/cycle
Communication Port Protocol
  • BACnet IP
  • FTP
  • HTTP
  • Modbus TCP/IP
  • SNTP
Communication Of Data
  • voltage
  • positive active energy
  • positive reactive energy
  • negative reactive energy
  • apparent energy
  • negative active energy
Number Of Inputs 2 pulse
Messages Display Capacity 2 lines of 16 characters
Measurement Accuracy +/- 0.5 % of the measuring range
Analogue Input Type
  • 24 solid core CT 0.333 V single pole
  • 12 solid core CT 0.333 V single phase
  • 8 solid core CT 0.333 V three phase
  • 24 split core CT 0.333 V single pole
  • 12 split core CT 0.333 V single phase
  • 8 split core CT 0.333 V three phase
Display Type Backlit LCD
Environmental Disclosure ENVPEP111007EN
California Proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI111006EN
Eu Rohs Directive Not compliant
Ambient Air Temperature For Operation -40-70 °C
Height 33.5 cm
Standards
  • ANSI/TIA-968-A : 2002
  • EN 55022
  • FCC Part 15 class B
  • IEC 6100-4-5
  • ICES-003
  • CSA C22.2 No 61010-1-4
  • CSA C22.2 No 61010-1
Device Mounting wall mounted
Product Certifications UL
Enclosure Type NEMA type 1
Net Weight 4 kg
Type Of Installation
  • indoor installation
  • enclosed outdoor
Pollution Degree 2
Mounting Mode wall mount
Ambient Air Temperature For Storage -40-70 °C
Relative Humidity 90-90 % 40-40 °C
Width 30.5 cm
Depth 5.5 cm
Operating Altitude <= 9842.52 ft (3000 m)