Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
METSEEM3560 – PowerLogic EM3500 DIN rail meter – BACnet – current transformer
METSEEM3560
PowerLogic EM3500 DIN rail meter - BACnet - current transformer

The EM3500 series offer a three-phases DIN rail-mounted energy meters fitted for accurate cost allocation and sub-metering. EM35xx models are designed for use with Low Votage Current Transducers 1/3Volt or 1Volt output. Current input from 5A to 32000A, according to the LVCT configuration in the HMI, ANSI C12.20 0.2% accuracy, IEC 62053-22 class 0.2S. The data logging capability protects data in the event of a power failure. Native BACnet and phase alarms are all provided to suit a wide variety of applications. Additional pulse input provide an easy way to incorporate simple WAGES sensors using a BACnet system. Suitable for a 230V AC network, with a supply voltage range of 90V AC to 300V AC at 50Hz or 60Hz. Compliant with UL508, CSA 22.2 number 14-05 and EN 61010-1. Product dimensions are as follows: width 107 mm, depth 59 mm, height 91 mm.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Product Or Component Type energy meter
Product Name PowerLogic EM3500
Range PowerLogic
Device Short Name EM3560
Metering Type
  • current I1, I2, I3, Iavg
  • voltage U21, U32, U13, V1, V2, V3
  • peak demand power PM, QM, SM
  • demand power P, Q, S
Network Frequency
  • 60 Hz
  • 50 Hz
Communication Port Support screw terminal block RS485
[Ue] Rated Operational Voltage
  • 90...347 V AC 50/60 Hz between phase and neutral UL
  • 156...600 V AC 50/60 Hz between phases UL
  • 90...300 V AC 50/60 Hz between phase and neutral CE
  • 125...300 V DC
Standards
  • UL 508
  • CSA C22.2 No 14-05
  • IEC 61010-1
Number Of Outputs 1 alarm output
Mounting Support DIN rail
Power Consumption In Va
  • 5-5 VA 347 V AC between phase and neutral)
  • 5-5 VA 600 V AC between phases)
Product Certifications
  • CE IEC 61010
  • cULus UL 508
Type Of Measurement
  • active and reactive power total
  • active and reactive power per phase
  • apparent power total
  • apparent power per phase
  • power factor total
  • power factor per phase
  • peak demand power
  • current
  • voltage
  • frequency
Communication Port Protocol BACnet MS/TP 9600 bauds...115200 bauds (automatic detection) - 2-wire
Communication Service
  • total cumulated energy
  • total cumulated active energy
Ride-Through Time 100 ms 120 V AC
Display Digits 5
Number Of Inputs 1 pulse
Tamperproof Of Settings protected by access code
Measurement Current 5-32000 A
Information Displayed
  • status and alert
  • communication with system
  • input/output status
  • error
  • Tx activity
  • Rx activity
  • instant power per usage
Function Available
  • fixed or rolling block
  • external synchronisation to communication
Mounting Mode
  • clip-on
  • by screws
Local Signalling
  • Red LED threshold reached
  • Green flashing LED output signal
Power Consumption In W 3 W 300-300 V
Measurement Accuracy
  • power +/- 0.2 %
  • energy +/- 0.2 %
Technology Type electronic
Buffer Size 32-bit 3
Poles Description 3P + N
Data Recording energy consumption logs
Analogue Input Type split core current transducer 0.333 V or 1 V
Display Type Backlit LCD
Device Application
  • partial meter
  • sub billing
Accuracy Class
  • class 0.2S power IEC 62053-22
  • class 0.2S energy IEC 62053-22
  • class 0.2S power ANSI C12.20
  • class 0.2S energy ANSI C12.20
Rated Voltage 90-347 V
Rohs Exemption Information Yes
Mercury Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Eu Rohs Directive Compliant
Ambient Air Temperature For Operation -30-70 °C
Height 91 mm
9 Mm Pitches 12
Color dark grey
Ambient Air Temperature For Storage -40-85 °C
Relative Humidity 0-95 %
Width 107 mm
Depth 59 mm
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews