Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
M9D11610 – Residual current breaker with overcur. prot. (RCBO), Multi9 N40 Vigi, 1P N, 10A, C curve, 6000A/6kA, AC type, 30mA
M9D11610
Residual current breaker with overcur. prot. (RCBO), Multi9 N40 Vigi, 1P+N, 10A, C curve, 6000A/6kA, AC type, 30mA

This Multi9 N40 Vigi is a modular residual current breaker with overcurrent protection (RCBO). It is a 1P+N circuit breaker with 1 protected pole, 10A In rated current and C tripping curve. The earth leakage protection class is AC type with a sensitivity of 30mA. The earth-leakage protection time delay is instantaneous. The Icu rated short circuit breaking capacity is up to 6kA according EN/IEC 60947-2 standard. The Icn rated short circuit breaking capacity is up to 6000 A according EN/IEC 61009-1 standard. This product protects against short circuit, cable overload, electrical shock by indirect contact and fire hazards. A green strip on the toggle guarantees opening of all the poles in safety conditions. This product is compliant with EN/IEC 61009-1 and EN/IEC 60947-2 standards. It has an electrical endurance going up to 20000 cycles and a mechanical endurance going up to 20000 cycles. The Ue operational voltage is 240VAC. The Ui rated insulation voltage is 400VAC. The Uimp rated impulse withstand voltage is 4kV. The frequency is 50Hz. It is DIN rail mountable. The width in 9mm pitches is 4. The product color is light grey (RAL7035). The dimensions are (W) 36mm x (H) 81mm x (D) 70mm. The weight is 125g. It has an IP20 degree of protection. It becomes IP40 once in modular enclosure according to IEC/EN 60529 standard. The operating temperature is from -5°C to 60°C. The storage temperature is from -30°C to 70°C.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Line Rated Current 10 A 50 °C EN/IEC 60947-2
Curve Code C
Number Of Protected Poles 1
Network Type AC
Earth-Leakage Protection Class type AC
Earth-Leakage Sensitivity 30 mA
Product Or Component Type residual current breaker with overcurrent protection (RCBO)
Product Name Multi9 N40 Vigi
Utilisation Category category A EN/IEC 60947-2
Range Multi9
Earth-Leakage Protection Time Delay instantaneous
Breaking Capacity
  • 6 kA Icu 240 V AC 50 Hz EN/IEC 60947-2
  • 6000 A Icn 240 V AC 50 Hz EN/IEC 61009-1
Suitability For Isolation yes EN/IEC 60947-2
Poles Description 1P + N
Neutral Position left
Device Application distribution
Device Short Name N40 Vigi
Trip Unit Technology thermal-magnetic
Network Frequency 50 Hz
[Ics] Rated Service Breaking Capacity 4.5 kA 75 % EN/IEC 60947-2 - 240 V AC 50 Hz
Height 81 mm
Contact Position Indicator yes
Earth-Leakage Protection integrated
Mounting Support DIN rail
9 Mm Pitches 4
Limitation Class 3 EN/IEC 61009-1
Surge Current 250 A
Net Weight 0.125 kg
Wire Stripping Length 13 mm top or bottom
Control Type toggle
Connections - Terminals
  • tunnel type terminal top or bottom) 0.75-16 mm² - rigid
  • tunnel type terminal top or bottom) 0.33-10 mm² - flexible
  • tunnel type terminal top or bottom) 0.33-10 mm² - flexible with ferrule
Residual Current Tripping Technology voltage independent
[Ui] Rated Insulation Voltage 400 V AC 50 Hz EN/IEC 60947-2
Mounting Mode clip-on
Electrical Durability 20000 cycles
Rated Breaking And Making Capacity Idm 4500 A 240 V AC 50 Hz EN/IEC 61009-1
Mechanical Durability 20000 cycles
Local Signalling
  • fault indication
  • ON/OFF indication
[Uimp] Rated Impulse Withstand Voltage 4 kVEN/IEC 60947-2
Connection Pitch 9 mm between phase and neutral
Color Gray
Width 36 mm
Provision For Padlocking padlockable
Depth 70 mm
Tightening Torque 2-2 N.m top or bottom
Magnetic Tripping Limit 8.5 x In +/- 20 % AC
[Ue] Rated Operational Voltage 240 V AC 50 Hz
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP111021EN
Reach Regulation Reference contains Substances of Very High Concern above the threshold
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Eu Rohs Directive Compliant
Halogen Content Performance Halogen free plastic parts product
Ambient Air Temperature For Operation -5-60 °C
Tropicalisation 2 IEC 60068-1
Standards
  • EN/IEC 61009-1
  • EN/IEC 60947-2
Electromagnetic Compatibility 8/20 µs impulse withstand, 250 A
Ip Degree Of Protection
  • IP20 conforming to IEC 60529
  • IP40 (modular enclosure) conforming to IEC 60529
Pollution Degree 3 EN/IEC 60947-2
Ambient Air Temperature For Storage -30-70 °C
Relative Humidity 95-95 % 55-55 °C
Overvoltage Category IV
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews