Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
LV433702 – Circuit breaker, ComPact NSX630R, 200kA/415VAC, MicroLogic 1.3M trip unit 500A, 3 poles 3d
LV433702
Circuit breaker, ComPact NSX630R, 200kA/415VAC, MicroLogic 1.3M trip unit 500A, 3 poles 3d

This Compact NSX630R is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for motor protection applications. The breaking capacity (Icu) is 200kA rms at 415VAC 50/60Hz and 45kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 1.3 M trip unit, with 500A rating. Micrologic 1.3 M trip unit provides an adjustable short time protection and a fixed instantaneous protection. This 3 poles version (140mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX630R is part of Schneider Electric EcoStruxure Power architecture.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Network Frequency 50/60 Hz
Line Rated Current 500 A 65 °C
Trip Unit Name MicroLogic 1.3 M
Range Of Product ComPact NSX400...630
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz
Trip Unit Protection Functions I
Network Type AC
Protected Poles Description 3t
Product Or Component Type circuit breaker
Product Name ComPact NSX
Range ComPact
Control Type toggle
Utilisation Category category A
Mounting Mode fixed
Breaking Capacity
  • 200 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2
  • 200 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2
  • 200 kA Icu 440 V AC 50/60 Hz IEC 60947-2
  • 80 kA Icu 500 V AC 50/60 Hz IEC 60947-2
  • 65 kA Icu 525 V AC 50/60 Hz IEC 60947-2
  • 45 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation yes EN/IEC 60947-2
Poles Description 3P
Breaking Capacity Code R 200 kA 415 V AC
Device Application motor
Device Short Name NSX630R
Trip Unit Technology electronic
Warranty 18 months
[Ics] Rated Service Breaking Capacity
  • 200 kA 220/240 V AC 50/60 Hz IEC 60947-2
  • 200 kA 380/415 V AC 50/60 Hz IEC 60947-2
  • 200 kA 440 V AC 50/60 Hz IEC 60947-2
  • 80 kA 500 V AC 50/60 Hz IEC 60947-2
  • 65 kA 525 V AC 50/60 Hz IEC 60947-2
  • 45 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height 255 mm
Earth-Leakage Protection without
Mounting Support backplate
Instantaneous Pick-Up Adjustment Range 6500 A
Downside Connection front
Number Of Slots 6
Protection Type I : for short-circuit protection (magnetic)
Instantaneous Pick-Up Adjustment Type Ii fixed
Zone Selective Interlocking Zsi without
Net Weight 6.2 kg
Electrical Durability
  • 2000 cycles 690 V In
  • 6000 cycles 690 V In/2
  • 4000 cycles 440 V In
  • 8000 cycles 440 V In/2
Short-Time Delay Adjustment Type fixed
Upside Connection front
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz
Trip Unit Rating 500-500 A 65 °C
Local Signalling for ready to operate flashing LED (green)
Mechanical Durability 15000 cycles
[Isd] Short-Time Pick-Up Adjustment Range
  • 6500 A
  • 5000 A
  • 3000 A
  • 3500 A
  • 5500 A
  • 4500 A
  • 4000 A
  • 2500 A
  • 6000 A
Connection Pitch 45 mm
[Uimp] Rated Impulse Withstand Voltage 8 kV
Width 140 mm
Depth 110 mm
Short-Time Pick-Up Adjustment Type Isd adjustable 9 settings
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP120606EN
California Proposition 65 WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI120604EN
Eu Rohs Directive Compliant
Product Certifications
  • Marine
  • CCC
  • EAC
Ik Degree Of Protection IK07 IEC 62262
Ambient Air Temperature For Operation -25-70 °C
Standards EN/IEC 60947
Ip Degree Of Protection IP40 conforming to IEC 60529
Electrical Shock Protection Class class II
Pollution Degree 3 IEC 60664-1
Ambient Air Temperature For Storage -50-85 °C
Relative Humidity 0-95 %
Operating Altitude
  • 0...6561.68 ft (0...2000 m) without derating
  • 2000 m...5000 m with derating
Overvoltage Category class II
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews