This Compact NSX400HB2 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for motor protection applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 100kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds an electronic Micrologic 2.3 M trip unit, with 320A rating. Micrologic 2.3 M trip unit provides adjustable long time and short time protections, and fixed instantaneous protection. This 3 poles version (140mm x 255mm x 110mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX400HB2 is part of Schneider Electric EcoStruxure Power architecture.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Network Frequency 50/60 Hz
Line Rated Current 320 A 65 °C
Trip Unit Name MicroLogic 2.3 M
Range Of Product ComPact NSX400...630
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz
Trip Unit Protection Functions LSoI
Network Type AC
Protected Poles Description 3t
Product Or Component Type circuit breaker
Product Name ComPact NSX
Range ComPact
Control Type toggle
Utilisation Category category A
Mounting Mode fixed
Breaking Capacity
  • 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2
  • 100 kA Icu 525 V AC 50/60 Hz IEC 60947-2
  • 100 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation yes EN/IEC 60947-2
Poles Description 3P
Breaking Capacity Code HB2 100 kA 690 V AC
Device Application motor
Device Short Name NSX400HB2
Trip Unit Technology electronic
Warranty 18 months
[Ics] Rated Service Breaking Capacity
  • 100 kA 500 V AC 50/60 Hz IEC 60947-2
  • 100 kA 525 V AC 50/60 Hz IEC 60947-2
  • 100 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height 255 mm
Thermal Memory 20 minutes before and after tripping
Earth-Leakage Protection without
Mounting Support backplate
Complementary Motor Protection phase unbalance
Instantaneous Pick-Up Adjustment Range 4800 A
Downside Connection front
Number Of Slots 6
Protection Type
  • L : for overload protection (long time)
  • So : for short time short-circuit protection with fixed delay
  • I : for instantaneous short-circuit protection
Long Time Delay Adjustment Type fixed
Instantaneous Pick-Up Adjustment Type Ii fixed
Zone Selective Interlocking Zsi without
Net Weight 6.05 kg
[Tr] Long-Time Delay Adjustment Range
  • 10-10 s 7.2 x Ir 10
  • 120-120 s 1.5 x Ir 5
  • 20-20 s 7.2 x Ir 20
  • 240-240 s 1.5 x Ir 10
  • 26-26 s 6 x Ir 20
  • 480-480 s 1.5 x Ir 20
  • 5-5 s 7.2 x Ir 5
  • 13.5-13.5 s 6 x Ir 10
  • 6.5-6.5 s 6 x Ir 5
Electrical Durability
  • 3000 cycles 690 V In
  • 6000 cycles 690 V In/2
  • 6000 cycles 440 V In
  • 12000 cycles 440 V In/2
Short-Time Delay Adjustment Type fixed
Long Time Pick-Up Adjustment Type Ir adjustable 9 settings
Long Time Pick-Up Adjustment Range 160...320 A
Upside Connection front
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz
Trip Unit Rating 320-320 A 65 °C
Local Signalling
  • for ready to operate flashing LED (green)
  • for temperature over set point LED 95 % Ith (red)
Mechanical Durability 15000 cycles
Motor Tripping Class
  • 5
  • 20
  • 10
[Isd] Short-Time Pick-Up Adjustment Range 5...13 x Ir
Connection Pitch 45 mm
[Uimp] Rated Impulse Withstand Voltage 8 kV
Width 140 mm
Depth 110 mm
Short-Time Pick-Up Adjustment Type Isd adjustable 9 settings
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP120606EN
California Proposition 65 WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI120604EN
Eu Rohs Directive Compliant
Product Certifications
  • CCC
  • EAC
  • Marine
Ik Degree Of Protection IK07 IEC 62262
Ambient Air Temperature For Operation -25-70 °C
Standards EN/IEC 60947
Ip Degree Of Protection IP40 conforming to IEC 60529
Electrical Shock Protection Class class II
Pollution Degree 3 IEC 60664-1
Ambient Air Temperature For Storage -50-85 °C
Relative Humidity 0-95 %
Operating Altitude
  • 0...6561.68 ft (0...2000 m) without derating
  • 2000 m...5000 m with derating
Overvoltage Category class II