Circuit breaker, ComPact NSX100R, 200kA/415VAC, MicroLogic 6.2E trip unit 100A, 3 poles 3d

This Compact NSX100R is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 200kA rms at 415VAC 50/60Hz and 45kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 100A rating electronic Micrologic 6.2 E trip unit, with an adjustable ground-fault protection (with OFF position). Micrologic 6.2 E trip unit provides adjustable long time, short time and instantaneous protection. Micrologic 6.2 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX100R is part of Schneider Electric EcoStruxure Power architecture.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Network Frequency 50/60 Hz
Line Rated Current 100 A 40 °C
Trip Unit Name MicroLogic 6.2 E
Range Of Product ComPact NSX100...250
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz
Trip Unit Protection Functions LSIG
Network Type AC
Protected Poles Description 3t
Product Or Component Type circuit breaker
Product Name ComPact NSX
Range ComPact
Control Type toggle
Utilisation Category category A
Mounting Mode fixed
Breaking Capacity
  • 200 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2
  • 200 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2
  • 200 kA Icu 440 V AC 50/60 Hz IEC 60947-2
  • 80 kA Icu 500 V AC 50/60 Hz IEC 60947-2
  • 65 kA Icu 525 V AC 50/60 Hz IEC 60947-2
  • 45 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation yes EN/IEC 60947-2
Poles Description 3P
Breaking Capacity Code R 200 kA 415 V AC
Device Application distribution
Device Short Name NSX100R
Trip Unit Technology electronic
Warranty 18 months
[Tg] Ground-Fault Time Delay Adjustment Range
  • 0-0.4 s I²t=off
  • 0.1-0.4 s I²t=on
[Ics] Rated Service Breaking Capacity
  • 200 kA 220/240 V AC 50/60 Hz IEC 60947-2
  • 200 kA 380/415 V AC 50/60 Hz IEC 60947-2
  • 200 kA 440 V AC 50/60 Hz IEC 60947-2
  • 80 kA 500 V AC 50/60 Hz IEC 60947-2
  • 65 kA 525 V AC 50/60 Hz IEC 60947-2
  • 45 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height 161 mm
[Ig] Ground-Fault Pick-Up Adjustment Range
  • 0.4...1 x In In = 40 A
  • 0.2...1 x In In > 40 A
  • Ig enable on/off
Thermal Memory 20 minutes before and after tripping
Earth-Leakage Protection without
Ground-Fault Time Delay Adjustment Type -Tg adjustable
Mounting Support backplate
Ground-Fault Pick-Up Adjustment Type adjustable 9 settings
Instantaneous Pick-Up Adjustment Range 1.5...15 x In
Type Of Measurement energy meter
Downside Connection front
Number Of Slots 5
Communication Of Data
  • maintenance indicators
  • energy metering
  • time-stamped histories and event tables
  • demand current and power
  • maximeters/minimeters
  • instantaneous and demand values
  • protection and alarm settings
  • power quality
Protection Type
  • L : for overload protection (long time)
  • S : for short time short-circuit protection
  • I : for instantaneous short-circuit protection
  • G : for ground fault protection
Long Time Delay Adjustment Type adjustable
Instantaneous Pick-Up Adjustment Type Ii adjustable
Zone Selective Interlocking Zsi with
Net Weight 2.05 kg
[Tr] Long-Time Delay Adjustment Range
  • 15-400 s 1.5 x Ir
  • 0.35-11 s 7.2 x Ir
  • 0.5-16 s 6 x Ir
Electrical Durability
  • 10000 cycles 690 V In
  • 20000 cycles 690 V In/2
  • 30000 cycles 440 V In
  • 50000 cycles 440 V In/2
Short-Time Delay Adjustment Type adjustable 5 settings
Long Time Pick-Up Adjustment Type Ir adjustable 9 settings
Long Time Pick-Up Adjustment Range 40...100 A
Upside Connection front
[Tsd] Short-Time Delay Adjustment Range 0-0.4 s
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz
Trip Unit Rating 100-100 A 40 °C
Local Signalling
  • for ready to operate flashing LED (green)
  • for overload LED 105 % Ir (red)
  • for overload LED 90 % Ir (orange)
Mechanical Durability 50000 cycles
[Isd] Short-Time Pick-Up Adjustment Range 1.5...15 x In
Connection Pitch 35 mm
[Uimp] Rated Impulse Withstand Voltage 8 kV
Width 105 mm
Display Type LCD display
Depth 86 mm
Short-Time Pick-Up Adjustment Type Isd adjustable
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP120606EN
California Proposition 65 WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI120604EN
Eu Rohs Directive Compliant
Product Certifications
  • Marine
  • CCC
  • EAC
Ik Degree Of Protection IK07 IEC 62262
Ambient Air Temperature For Operation -25-70 °C
Standards EN/IEC 60947
Ip Degree Of Protection IP40 conforming to IEC 60529
Electrical Shock Protection Class class II
Pollution Degree 3 IEC 60664-1
Ambient Air Temperature For Storage -40-85 °C
Relative Humidity 0-95 %
Operating Altitude
  • 0...6561.68 ft (0...2000 m) without derating
  • 2000 m...5000 m with derating
Overvoltage Category class II