This Compact NSX160H is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 70kA rms at 415VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 80A rating thermal-magnetic trip unit (TMD). TMD trip unit provides an adjustable thermal overload protection and a fixed magnetic protection. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX160H is part of Schneider Electric EcoStruxure Power architecture.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Network Frequency 50/60 Hz
Line Rated Current 80 A 40 °C
Trip Unit Name TM-D
Range Of Product ComPact NSX100...250
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz
Trip Unit Protection Functions LI
Network Type AC
Protected Poles Description 3t
Product Or Component Type circuit breaker
Product Name ComPact NSX
Range ComPact
Control Type toggle
Utilisation Category category A
Mounting Mode fixed
Breaking Capacity
  • 10 kA 600 V AC 50/60 Hz UL 508
  • 85 kA 240 V AC 50/60 Hz UL 508
  • 65 kA 480 V AC 50/60 Hz UL 508
  • 10 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
  • 100 kA Icu 220/240 V AC 50/60 Hz IEC 60947-2
  • 35 kA Icu 525 V AC 50/60 Hz IEC 60947-2
  • 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2
  • 65 kA Icu 440 V AC 50/60 Hz IEC 60947-2
  • 70 kA Icu 380/415 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation yes EN/IEC 60947-2
Poles Description 3P
Breaking Capacity Code H 70 kA 415 V AC
Device Application distribution
Device Short Name NSXm 160H
Trip Unit Technology thermal-magnetic
Warranty 18 months
[Ics] Rated Service Breaking Capacity
  • 10 kA 660/690 V AC 50/60 Hz IEC 60947-2
  • 100 kA 220/240 V AC 50/60 Hz IEC 60947-2
  • 35 kA 525 V AC 50/60 Hz IEC 60947-2
  • 50 kA 500 V AC 50/60 Hz IEC 60947-2
  • 65 kA 440 V AC 50/60 Hz IEC 60947-2
  • 70 kA 380/415 V AC 50/60 Hz IEC 60947-2
Height 161 mm
Earth-Leakage Protection without
Mounting Support backplate
Downside Connection front
Number Of Slots 5
Protection Type
  • L : for overload protection (thermal)
  • I : for short-circuit protection (magnetic)
Long Time Delay Adjustment Type fixed
Net Weight 2.2 kg
[Tr] Long-Time Delay Adjustment Range
  • 120-400 s 1.5 x In
  • 15-15 s 6 x Ir
Electrical Durability
  • 7500 cycles 690 V In
  • 15000 cycles 690 V In/2
  • 20000 cycles 440 V In
  • 40000 cycles 440 V In/2
Short-Time Delay Adjustment Type fixed
Long Time Pick-Up Adjustment Type Ir adjustable
Long Time Pick-Up Adjustment Range 0.7...1 x In
Upside Connection front
[Ui] Rated Insulation Voltage 800 V AC 50/60 Hz
Trip Unit Rating 80-80 A 40 °C
Mechanical Durability 40000 cycles
[Isd] Short-Time Pick-Up Adjustment Range 640 A
Connection Pitch 35 mm
[Uimp] Rated Impulse Withstand Voltage 8 kV
Width 105 mm
Depth 86 mm
Short-Time Pick-Up Adjustment Type Isd fixed
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP120606EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI120604EN
Eu Rohs Directive Compliant
Product Certifications
  • CCC
  • EAC
  • Marine
Ik Degree Of Protection IK07 IEC 62262
Ambient Air Temperature For Operation -25-70 °C
Standards EN/IEC 60947
Ip Degree Of Protection IP40 conforming to IEC 60529
Electrical Shock Protection Class class II
Pollution Degree 3 IEC 60664-1
Ambient Air Temperature For Storage -50-85 °C
Relative Humidity 0-95 %
Operating Altitude
  • 0...6561.68 ft (0...2000 m) without derating
  • 2000 m...5000 m with derating
Overvoltage Category class II
Documents