Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
LV429140 – trip unit MicroLogic 6.2 E for ComPact NSX 100/160/250 circuit breakers, electronic, rating 100A, 4 poles 4d
LV429140
trip unit MicroLogic 6.2 E for ComPact NSX 100/160/250 circuit breakers, electronic, rating 100A, 4 poles 4d

This Micrologic 6.2 E (Energy) is a 4 poles 4d electronic trip unit used on Compact NSX 100/160/250 circuit breakers. This 100A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. It has an additional and adjustable ground fault protection. Micrologic 6.2 E indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 6.2 E is equipped with a display module that gives energy measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Network Frequency 50/60 Hz
Trip Unit Name MicroLogic 6.2 E
Range Of Product ComPact NSX100...250
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz
Trip Unit Protection Functions LSIG
Network Type AC
Protected Poles Description
  • 3t + OSN
  • 4t
  • 3t + N/2
  • 3t
Product Or Component Type trip unit
Protection Type
  • L : for overload protection (long time)
  • S : for short time short-circuit protection
  • I : for instantaneous short-circuit protection
  • G : for ground fault protection
Range ComPact
Poles Description 4P
Neutral Position left
Range Compatibility
  • ComPact NSX100
  • ComPact NSX160
  • ComPact NSX250
Device Application distribution
Trip Unit Technology electronic
Warranty 18 months
[Tg] Ground-Fault Time Delay Adjustment Range
  • 0-0.4 s I²t=off
  • 0.1-0.4 s I²t=on
[Ig] Ground-Fault Pick-Up Adjustment Range
  • 0.4...1 x In In = 40 A
  • 0.2...1 x In In > 40 A
  • Ig enable on/off
Thermal Memory 20 minutes before and after tripping
Earth-Leakage Protection without
Ground-Fault Time Delay Adjustment Type -Tg adjustable
Ground-Fault Pick-Up Adjustment Type adjustable
Type Of Measurement energy meter
Communication Of Data
  • power quality
  • demand current and power
  • instantaneous and demand values
  • maximeters/minimeters
  • protection and alarm settings
  • time-stamped histories and event tables
  • energy metering
  • maintenance indicators
Long Time Delay Adjustment Type adjustable
Instantaneous Pick-Up Adjustment Type Ii adjustable
Zone Selective Interlocking Zsi with
Electrical Data Recording maintenance indicators
[Tr] Long-Time Delay Adjustment Range
  • 15-400 s 1.5 x Ir
  • 0.35-11 s 7.2 x Ir
  • 0.5-16 s 6 x Ir
Short-Time Delay Adjustment Type adjustable
Instantaneous Pick-Up Adjustment Range
  • 1.5...12 x In Compact NSX250
  • 1.5...15 x In Compact NSX100
  • 1.5...15 x In Compact NSX160
Neutral Protection Setting
  • 0.5 x Ir 3t + N/2)
  • 1 x Ir 4t)
  • 1.6 x Ir 3t + OSN)
  • no protection 3t)
Long Time Pick-Up Adjustment Type Ir adjustable 9 settings
Long Time Pick-Up Adjustment Range 40...100 A
[Tsd] Short-Time Delay Adjustment Range
  • 0-0.4 s I²t=off
  • 0.1-0.4 s I²t=on
[Isd] Short-Time Pick-Up Adjustment Range 1.5...10 x Ir
Display Type LCD display
Short-Time Pick-Up Adjustment Type Isd adjustable 9 settings
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP120606EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI120604EN
Eu Rohs Directive Compliant
Product Certifications
  • EAC
  • Marine
  • CCC
Ambient Air Temperature For Operation -25-70 °C
Standards
  • EN/IEC 60947-2
  • UL 508
Ambient Air Temperature For Storage -40-85 °C
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews