TeSys U multifunction control unit to be inserted in advanced power bases LUB120, LUB320, LUB380 to form a TeSys U starter controller, for 1-phase motor applications up to 0.09kW@400V and 3-phase up to 0.25kW@400V. It provides full protection to motors with a rated current Ir 0.35-1.4A (Ir adjustable), overload class selectable 5-30, short circuit at 13 x Irmax, overcurrent at 14.2 x Ir, phase loss, insulation fault (protection of equipment only). Equipped with a LCD display and a 4-button keyboard for the setting of protection and alarm parameters, and display of electrical values and events. RS485 Modbus communication RJ45 port available for remote control and integration with SoMove/MachineExpert. To be used with a 24V DC voltage for the control of the starter (through the control terminals A1/A2 located in the power base), it must be supplied with an external 24V DC power supply. Certified when used in conjunction with a LUB power base (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
[Uc] Control Circuit Voltage 24 V DC
[Ue] Rated Operational Voltage 690 V AC
Range Of Product TeSys Ultra
Thermal Protection Adjustment Range 0.35-1.4 A
Product Or Component Type multifunction control unit
Product Name TeSys Ultra
Thermal Overload Class
  • class 5…30 50-60 Hz -25-55 °C IEC 60947-6-2
  • class 5…30 50-60 Hz -25-55 °C UL 508
Motor Power Kw
  • 0.25 kW 400...440 V AC 50/60 Hz 3 phase
  • 0.09 kW 400...440 V AC 50/60 Hz 1 phase
Range TeSys
Utilisation Category
  • AC-43
  • AC-44
  • AC-41
Function Available
  • protection against phase failure and phase imbalance
  • protection function alarm
  • protection against overload and short-circuit
  • log function
  • earth fault protection
  • monitoring function, indication of main motor parameters
  • differentiation of thermal overload and magnetic fault
  • overload, no-load running
  • manual or automatic reset
Tripping Threshold 14.2 x Ir +/- 20 %
Product Compatibility
  • power base LUB12
  • power base LUB32
  • power base LUB38
  • power base LUB120
  • power base LUB320
  • power base LUB380
  • reversing contactor breaker LU2B12BL
  • reversing contactor breaker LU2B32BL
  • reversing contactor breaker LU2B38BL
Product Specific Application most sophisticated control and protection requirements, with display
Network Frequency 40...60 Hz
Device Application
  • motor control
  • motor protection
Load Type
  • 3-phase motor self-cooled factory setting
  • 3-phase motor self-cooled, force cooled settable
  • single-phase motor self-cooled, force cooled settable
Device Short Name LUCM
Warranty 18 months
Product Certifications
  • CE
  • UL
  • CSA
  • CCC
  • EAC
  • ASEFA
  • ATEX
  • Marine
Height 66 mm
Reset
  • automatic reset setting range
  • manual factory setting
  • manual setting range
  • remote reset setting range
Physical Interface RS485 multidrop RJ45 front panel Modbus RTU 19200 bit/s
Net Weight 0.175 kg
Fixing Mode plug-in front face)
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-6-2
Standards
  • EN 60947-6-2
  • IEC 60947-6-2
  • UL 60947-4-1, with phase barrier
  • CSA C22.2 No 60947-4-1, with phase barrier
Time Before Reset
  • 1-1000 s manual or automatic reset settable
  • 120-120 s manual factory setting
Information Displayed
  • average current factory setting)
  • average current settable)
  • cause of last 5 faults settable)
  • current in phase settable)
  • earth leakage current settable)
  • phase imbalance settable)
  • thermal state of motor settable)
Typical Current Consumption
  • 150 mA 24 V DC I maximum while closing with LUB12
  • 200 mA 24 V DC I maximum while closing with LUB32
  • 200 mA 24 V DC I maximum while closing with LUB38
  • 70 mA 24 V DC I rms sealed with LUB12
  • 75 mA 24 V DC I rms sealed with LUB32
  • 75 mA 24 V DC I rms sealed with LUB38
[Ui] Rated Insulation Voltage
  • 690 V IEC 60947-6-2
  • 600 V UL 60947-4-1
  • 600 V CSA C22.2 No 60947-4-1
Messages Display Capacity
  • 2 lines of 12 characters LCD - English +/- 5 % 1 % of Ir
  • 2 lines of 12 characters LCD - French +/- 5 % 1 % of Ir
  • 2 lines of 12 characters LCD - German +/- 5 % 1 % of Ir
  • 2 lines of 12 characters LCD - Italian +/- 5 % 1 % of Ir
  • 2 lines of 12 characters LCD - Spanish +/- 5 % 1 % of Ir
Return Time <= 200 ms
Compatibility Code LUCM
User Language
  • English factory setting
  • English, French, German, Italian, Spanish settable
Control Circuit Voltage Limits
  • 20...28 V DC 24 V in operation
  • 14.5 V DC 24 V drop-out
Operating Time
  • 35 ms opening with LUB12 control circuit
  • 35 ms opening with LUB32 control circuit
  • 35 ms opening with LUB38 control circuit
  • 75 ms closing with LUB12 control circuit
  • 65 ms closing with LUB32 control circuit
  • 65 ms closing with LUB38 control circuit
Width 45 mm
Safe Separation Of Circuit
  • 400 V SELV between the control and auxiliary circuits IEC 60947-1
  • 400 V SELV between the control or auxiliary circuit and the main circuit IEC 60947-1
Depth 60 mm
Heat Dissipation
  • 1.7-1.7 W control circuit with LUB12
  • 1.8-1.8 W control circuit with LUB32
  • 1.8-1.8 W control circuit with LUB38
  • 0.8-0.8 W external auxiliary circuit
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP080204EN
Sustainable Offer Status Green Premium product
Pvc Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI100414
Eu Rohs Directive Compliant
Halogen Content Performance Halogen free plastic parts product
Ambient Air Temperature For Operation -25-60 °C
Resistance To Radiated Fields 10 V/m 3 IEC 61000-4-3
Non-Dissipating Shock Wave
  • 1 kV serial mode IEC 60947-6-2
  • 2 kV common mode IEC 60947-6-2
Shock Resistance
  • 10 gn power poles open IEC 60068-2-27
  • 15 gn power poles closed IEC 60068-2-27
Vibration Resistance
  • 2 gn 5-300 Hz power poles open IEC 60068-2-6
  • 4 gn 5-300 Hz power poles closed IEC 60068-2-6
Immunity To Microbreaks 3 ms
Immunity To Voltage Dips 70 % / 500 ms IEC 61000-4-11
Ip Degree Of Protection
  • IP20 front panel and wired terminals IEC 60947-1
  • IP20 other faces IEC 60947-1
  • IP40 front panel outside connection zone IEC 60947-1
Ambient Air Temperature For Storage -40-85 °C
Protective Treatment TH IEC 60068
Resistance To Electrostatic Discharge
  • 8 kV 3 in open air IEC 61000-4-2
  • 8 kV 4 on contact IEC 61000-4-2
Operating Altitude 6561.68 ft (2000 m)
Fire Resistance
  • 960 °C parts supporting live components IEC 60695-2-12
  • 650 °C IEC 60695-2-12
Immunity To Radioelectric Fields 10 V IEC 61000-4-6
Resistance To Fast Transients
  • 2 kV 3 serial link IEC 61000-4-4
  • 4 kV 4 all circuits except for serial link IEC 61000-4-4
Documents