Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
LP1K0610ED – Contactor, TeSys K, 3P, AC-3, lt or eq to 440V, 6A, 1 NO aux, 48VDC coil
LP1K0610ED
Contactor, TeSys K, 3P, AC-3, lt or eq to 440V, 6A, 1 NO aux, 48VDC coil

LP1K0610ED is a compact 3-pole TeSys K contactor from Schneider Electric for motor applications. Rated 9A AC-3 4kW@400V, it includes a 48 V DC coil and 1NO auxiliary contact allowing easy integration to all control systems. LP1K0610ED is a 3-pole TeSys K contactor from Schneider Electric for simple motor applications rated up to 2.2kW@400V. Very compact, DIN-rail compatible, with connections by screw clamp terminals, it can be easily integrated into all control systems thanks to its 48V DC coil and 1NO built-in auxiliary contact. Available worldwide, it complies with multi-standards (IEC, UL, CSA, CCC, EAC, Marine) and is certified Green Premium (RoHs/Reach). Very compact, 45mm wide, for DIN-rail and panel mounting. Ready for connection to all control systems thanks to a 48V DC control voltage and 1NO built-in auxiliary contact. Optimized for simple power applications. Can be completed with auxiliary contact blocks (LA1K, LA2K) and thermal relays (LR2K).

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Contactor Application motor control
Product Or Component Type contactor
Range TeSys
Device Short Name LP1K
Warranty 18 months
Minimum Switching Current 5 mA signalling circuit
[Uc] Control Circuit Voltage 48 V DC
[Ue] Rated Operational Voltage
  • power circuit <= 690 V AC <= 400 Hz
  • signalling circuit <= 690 V AC <= 400 Hz
Height 58 mm
Average Impedance 3 mOhm - Ith 20 A 50 Hz power circuit
Auxiliary Contact Composition 1 NO
Control Circuit Voltage Limits
  • operational 0.8...1.15 Uc 50 °C)
  • drop-out >= 0.10 Uc 50 °C)
[Ith] Conventional Free Air Thermal Current
  • 20 A 60 °C power circuit
  • 10 A 50 °C signalling circuit
Mounting Support
  • rail
  • plate
Control Circuit Type DC standard
Safety Reliability Level
  • B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Hold-In Power Consumption In W 3-3 W 20 °C
Insulation Resistance > 10 MOhm signalling circuit
Rated Breaking Capacity
  • 110 A 220...230 V IEC 60947
  • 110 A 380...400 V IEC 60947
  • 110 A 415 V IEC 60947
  • 110 A 440 V IEC 60947
  • 80 A 500 V IEC 60947
  • 70 A 660...690 V IEC 60947
Irms Rated Making Capacity
  • 110 A AC power circuit IEC 60947
  • 110 A AC signalling circuit IEC 60947
Motor Power Kw
  • 1.5 kW 220...230 V AC 50/60 Hz AC-3
  • 2.2 kW 380...415 V AC 50/60 Hz AC-3
  • 3 kW 440/690 V AC 50/60 Hz AC-3
  • 1.5 kW 220...230 V AC 50/60 Hz AC-3e
  • 2.2 kW 380...415 V AC 50/60 Hz AC-3e
  • 3 kW 440/690 V AC 50/60 Hz AC-3e
  • 1.5 kW 220...230 V AC 50/60 Hz AC-4
  • 2.2 kW 380...415 V AC 50/60 Hz AC-4
  • 3 kW 440/690 V AC 50/60 Hz AC-4
Associated Fuse Rating
  • 25 A gG <= 440 V power circuit
  • 25 A aM power circuit
  • 10 A gG signalling circuit IEC 60947
  • 10 A gG signalling circuit VDE 0660
Net Weight 0.225 kg
[Uimp] Rated Impulse Withstand Voltage 8 kV
Connections - Terminals
  • screw clamp terminals 1 1.5-4 mm²solid
  • screw clamp terminals 1 0.75-4 mm²flexible without cable end
  • screw clamp terminals 1 0.34-2.5 mm²flexible with cable end
  • screw clamp terminals 2 1.5-4 mm²solid
  • screw clamp terminals 2 0.75-4 mm²flexible without cable end
  • screw clamp terminals 2 0.34-1.5 mm²flexible with cable end
  • power circuit screw clamp terminals 2 1.5-1.5 mm²flexible with cable end
Pole Contact Composition 3 NO
Utilisation Category
  • AC-3
  • AC-3e
  • AC-4
[Ie] Rated Operational Current
  • 6 A 60 °C) <= 440 V AC AC-3 power circuit
  • 6 A 60 °C) <= 440 V AC AC-3e power circuit
Minimum Switching Voltage 17 V signalling circuit
Maximum Operating Rate 3600 cyc/h
Electrical Durability
  • 1.3 Mcycles 6 A AC-3 <= 440 V
  • 1.3 Mcycles 6 A AC-3e <= 440 V
  • 0.05 Mcycles 36 A AC-4 <= 440 V
Mechanical Durability 10 Mcycles
Inrush Power In W 3-3 W 20 °C)
Auxiliary Contacts Type instantaneous 1 NO
Poles Description 3P
Operating Time
  • 30...40 ms coil energisation and NO closing
  • 10 ms coil de-energisation and NO opening
Width 45 mm
Tightening Torque
  • 0.8-1.3 N.m screw clamp terminals Philips No 2
  • 0.8-1.3 N.m screw clamp terminals flat Ø 6 mm
  • 0.8-1.3 N.m screw clamp terminals pozidriv No 2
Overvoltage Category III
Depth 57 mm
[Ui] Rated Insulation Voltage
  • power circuit 600 V UL 508
  • power circuit 690 V IEC 60947-4-1
  • signalling circuit 690 V IEC 60947-4-1
  • signalling circuit 690 V IEC 60947-5-1
  • signalling circuit 600 V UL 508
  • power circuit 600 V CSA C22.2 No 14
  • signalling circuit 600 V CSA C22.2 No 14
[Icw] Rated Short-Time Withstand Current
  • 90 A 50 °C - 1 s power circuit
  • 85 A 50 °C - 5 s power circuit
  • 80 A 50 °C - 10 s power circuit
  • 60 A 50 °C - 30 s power circuit
  • 45 A 50 °C - 1 min power circuit
  • 40 A 50 °C - 3 min power circuit
  • 20 A 50 °C - >= 15 min power circuit
  • 80 A - 1 s signalling circuit
  • 90 A - 500 ms signalling circuit
  • 110 A - 100 ms signalling circuit
Heat Dissipation 1.3-1.3 W
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1503003EN
Sustainable Offer Status Green Premium product
Toxic Heavy Metal Free Yes
Reach Regulation Free of Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc Yes
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile ENVEOLI1503003EN
Eu Rohs Directive Compliant
Product Certifications
  • CB Scheme
  • CCC
  • UL
  • CSA
  • EAC
  • CE
  • UKCA
Ambient Air Temperature For Operation -25-50 °C
Standards
  • EN/IEC 60947-4-1
  • EN/IEC 60947-5-1
  • UL 60947-4-1
  • UL 60947-5-1
  • CSA C22.2 No 60947-4-1
  • CSA C22.2 No 60947-5-1
  • GB/T 14048.4
Flame Retardance
  • V1 conforming to UL 94
  • requirement 2 conforming to NF F 16-101
  • requirement 2 conforming to NF F 16-102
Ambient Air Temperature For Storage -50-80 °C
Ip Degree Of Protection IP2X
Operating Altitude 6561.68 ft (2000 m) without derating
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews