Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
LC2D50G7 – Reversing contactor, TeSys Deca, 3P(3NO), AC-3, IEC,
LC2D50G7
Reversing contactor, TeSys Deca, 3P(3NO), AC-3, IEC, <=440V, 50A, 120V AC 60Hz coil
Specifications
Control Circuit Type AC
[Uc] Control Circuit Voltage 120 V AC 60 Hz
Range Of Product TeSys Deca
Contactor Application motor control
Product Or Component Type reversing contactor
Connections - Terminals
  • control circuit 1 1-4 mm²flexible with cable end
  • power circuit 2 1-25 mm²flexible with cable end
  • power circuit 2 1-25 mm²flexible without cable end
  • power circuit 2 1-25 mm²solid without cable end
  • power circuit 2 1-35 mm²flexible with cable end
  • power circuit 2 1-35 mm²flexible without cable end
  • power circuit 2 1-35 mm²solid without cable end
  • control circuit 1 1-4 mm²flexible without cable end
  • control circuit 1 1-4 mm²solid without cable end
  • control circuit 2 1-2.5 mm²flexible with cable end
  • control circuit 2 1-4 mm²flexible without cable end
  • control circuit 2 1-4 mm²solid without cable end
  • power circuit 1 1-35 mm²flexible with cable end
  • power circuit 1 1-35 mm²flexible without cable end
  • power circuit 1 1-35 mm²solid without cable end
Pole Contact Composition 3 NO
Utilisation Category
  • AC-2
  • AC-3
  • AC-4
[Ie] Rated Operational Current power circuit 50 A AC AC-3 60 °C)
Poles Description 3P
Motor Power Kw
  • 15 kW 220...240 V AC 50/60 Hz
  • 22 kW 380...400 V AC 50/60 Hz
  • 25 kW 415 V AC 50/60 Hz
  • 30 kW 440 V AC 50/60 Hz
  • 30 kW 500 V AC 50/60 Hz
  • 33 kW 660...690 V AC 50/60 Hz
Device Short Name LC2D
Coil Type standard
Warranty 18 months
Non-Overlap Time
  • 1.5 ms on de-energisation between NC and NO contacts
  • 1.5 ms on energisation between NC and NO contacts
Interlocking Type mechanical
Minimum Switching Current 5 mA control circuit
[Ue] Rated Operational Voltage power circuit <= 1000 V AC 25...400 Hz
Height 132 mm
Power Dissipation Per Pole 3.7 W AC-3 - Ith 80 A
Average Impedance Ith 80 A 50 Hz power circuit
Auxiliary Contact Composition 1 NO + 1 NC
Control Circuit Voltage Limits
  • drop-out 0.3...0.6 Uc 50/60 Hz 60 °C)
  • operational 0.8...1.1 Uc 50 Hz 60 °C)
  • operational 0.85...1.1 Uc 60 Hz 60 °C)
[Ith] Conventional Free Air Thermal Current
  • 10 A 60 °C control circuit
  • 80 A 60 °C power circuit
Mounting Support
  • plate
  • rail
Safety Reliability Level
  • B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Insulation Resistance > 10 MOhm control circuit
Rated Breaking Capacity 900 A 440 V power circuit IEC 60947
Irms Rated Making Capacity
  • 140 A AC control circuit IEC 60947-5-1
  • 900 A 440 V power circuit IEC 60947
Associated Fuse Rating
  • 10 A gG control circuit IEC 60947-5-1
  • 100 A gG <= 690 V type 1 power circuit
  • 100 A gG <= 690 V type 2 power circuit
Net Weight 2.4 kg
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
Inrush Power In Va
  • 200-200 VA 0.75 20 °C)
  • 220-220 VA 0.75 20 °C)
Coil Technology without built-in bidirectional peak limiting diode suppressor
Flame Retardance V1 conforming to UL 94
Minimum Switching Voltage 17 V control circuit
Maximum Operating Rate 3600 cyc/h 60 °C
Tightening Torque
  • control circuit 1.7 N.m 1-2.5 mm² flat Ø 6 mm
  • control circuit 1.7 N.m 1-2.5 mm² Philips No 2
  • control circuit 1.7 N.m 1-4 mm² flat Ø 6 mm
  • control circuit 1.7 N.m 1-4 mm² Philips No 2
  • power circuit 5 N.m 1-25 mm² hexagonal
  • power circuit 8 N.m 1-35 mm² hexagonal
Assembly Style ready assembled
Mechanical Durability 6000000 cycles
Auxiliary Contacts Type
  • mechanically linked 1 NO + 1 NC IEC 60947-5-1
  • mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va
  • 20-20 VA 50 Hz 0.3 20 °C)
  • 22-22 VA 60 Hz 0.3 20 °C)
  • 26-26 VA 50 Hz 0.3 20 °C)
  • 26-26 VA 60 Hz 0.3 20 °C)
Operating Time
  • 12...26 ms closing
  • 4...19 ms opening
Width 165 mm
Overvoltage Category III
Depth 142 mm
[Ui] Rated Insulation Voltage
  • control circuit 600 V CSA
  • control circuit 600 V UL
  • power circuit 600 V CSA
  • power circuit 600 V UL
  • control circuit 690 V IEC 60947-1
  • power circuit 690 V IEC 60947-1
Protective Cover with
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1503009EN
Sustainable Offer Status Green Premium product
Pvc Free Yes
Toxic Heavy Metal Free Yes
Reach Regulation Free of Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc Yes
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile ENVEOLI1503009EN
Eu Rohs Directive Compliant
Product Certifications
  • GL
  • UL
  • RINA
  • GOST
  • CSA
  • LROS (Lloyds register of shipping)
  • CCC
  • DNV
  • BV
  • UKCA
Ambient Air Temperature For Operation -5-60 °C
Standards
  • IEC 60947-4-1
  • CSA C22.2 No 14
  • UL 508
  • IEC 60947-5-1
  • EN 60947-4-1
  • EN 60947-5-1
Shock Resistance
  • 10 gn contactor closed
  • 8 gn contactor opened
Vibration Resistance
  • 2 gn 5-300 Hz contactor opened
  • 3 gn 5-300 Hz contactor closed
Ambient Air Temperature For Storage -60-80 °C
Protective Treatment TH 3)IEC 60068
Ip Degree Of Protection
  • IP2X IEC 60529
  • IP2X VDE 0106
Operating Altitude 9842.52 ft (3000 m) without derating
Fire Resistance 850 °C IEC 60695-2-1
Permissible Ambient Air Temperature Around The Device -40-70 °C at Uc
Heat Dissipation 6-10 W 50/60 Hz control circuit