Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
LC1F150X7 – contactor, TeSys F, 3P(3NO), AC-3,
LC1F150X7
contactor, TeSys F, 3P(3NO), AC-3, <=440V 150A, coil 600V AC
Specifications
[Uc] Control Circuit Voltage 600 V AC 40...400 Hz
Range Of Product TeSys F
[Ue] Rated Operational Voltage <= 690 V AC 50/60 Hz
Contactor Application
  • resistive load
  • motor control
Product Or Component Type contactor
Range TeSys
Utilisation Category
  • AC-3
  • AC-1
  • AC-4
[Ie] Rated Operational Current
  • 250 A 40 °C) <= 440 V AC-1
  • 150 A 55 °C) <= 440 V AC-3
Poles Description 3P
Device Short Name LC1F
Product Certifications
  • BV
  • RINA
  • LROS (Lloyds register of shipping)
  • RMRoS
  • ABS
  • CCC
  • CB
  • UL
  • DNV
Power Dissipation Per Pole
  • 22 W AC-1
  • 8 W AC-3
Average Impedance 0.35 mOhm - Ith 250 A 50 Hz
[Ith] Conventional Free Air Thermal Current 250 A 40 °C
Control Circuit Voltage Limits
  • operational 0.85...1.1 Uc 40...400 Hz 55 °C)
  • drop-out 0.2...0.55 Uc 40...400 Hz 55 °C)
Standards
  • EN 60947-4-1
  • EN 60947-1
  • IEC 60947-4-1
  • JIS C8201-4-1
  • IEC 60947-1
Mounting Support plate
Control Circuit Type AC 40...400 Hz
Rated Breaking Capacity 1200 A IEC 60947-4-1
Associated Fuse Rating
  • 160 A aM <= 440 V
  • 250 A gG <= 440 V
[Uimp] Rated Impulse Withstand Voltage 8 kV
Inrush Power In Va 690-855 VA, 40...400 Hz 0.9 20 °C)
Connections - Terminals
  • control circuit screw clamp terminals 1 1-4 mm²flexible without cable end
  • control circuit screw clamp terminals 2 1-4 mm²flexible without cable end
  • control circuit screw clamp terminals 1 1-4 mm²flexible with cable end
  • control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end
  • control circuit screw clamp terminals 1 1-4 mm²solid without cable end
  • control circuit screw clamp terminals 2 1-4 mm²solid without cable end
  • power circuit bar 2 25 x 3 mm
  • power circuit lugs-ring terminals 1 120-120 mm²
  • power circuit connector 1 120-120 mm²
  • power circuit bolted connection
Pole Contact Composition 3 NO
Operating Time
  • 35 ms closing at Uc)
  • 130 ms opening at Uc)
Maximum Operating Rate 1200 cyc/h 55 °C
Mechanical Durability 10 Mcycles
Tightening Torque
  • control circuit 1.2 N.m
  • power circuit 18 N.m
Compatibility Code LC1F
Hold-In Power Consumption In Va 6.6-8.1 VA, 40...400 Hz 0.9 20 °C)
Overvoltage Category III
Motor Power Kw
  • 75 kW 380...400 V AC 50/60 Hz AC-3)
  • 80 kW 415 V AC 50/60 Hz AC-3)
  • 80 kW 440 V AC 50/60 Hz AC-3)
  • 90 kW 500 V AC 50/60 Hz AC-3)
  • 100 kW 660...690 V AC 50/60 Hz AC-3)
  • 40 kW 220...230 V AC 50/60 Hz AC-3)
  • 22 kW 400 V AC 50/60 Hz AC-4)
[Ui] Rated Insulation Voltage
  • 1000 V IEC 60947-4-1
  • 1500 V VDE 0110 group C
[Icw] Rated Short-Time Withstand Current
  • 1200 A 40 °C - 10 s
  • 700 A 40 °C - 30 s
  • 600 A 40 °C - 1 min
  • 450 A 40 °C - 3 min
  • 350 A 40 °C - 10 min
Heat Dissipation 5.9-7.2 W
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP111201EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI111214EN_V1
Eu Rohs Directive Compliant
Ambient Air Temperature For Operation -40-60 °C
Height 170 mm
Net Weight 3.43 kg
Ambient Air Temperature For Storage -60-80 °C
Protective Treatment TH
Ip Degree Of Protection
  • IP2X front face with shrouds IEC 60529
  • IP2X front face with shrouds VDE 0106
Operating Altitude 9842.52 ft (3000 m) without derating
Width 163.5 mm
Depth 171 mm
Permissible Ambient Air Temperature Around The Device 60-70 °C at Uc
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews