LC1F1400 – contactor body withou coil, TeSys F, 3P(3NO), AC-1,
LC1F1400
contactor body withou coil, TeSys F, 3P(3NO), AC-1, <=1000V AC 1400A, with coil LX1/ LX9, 110…500V AC 40/400Hz, LX4, 110...440V DC
Specifications
[Ue] Rated Operational Voltage
  • <= 1000 V AC 50/60 Hz
  • <= 460 V DC
Contactor Application resistive load
Product Or Component Type contactor
Product Name TeSys F
Range TeSys
Pole Contact Composition 3 NO
[Ie] Rated Operational Current 1400 A 40 °C) <= 440 V AC AC-1
Utilisation Category AC-1
Poles Description 3P
Device Short Name LC1F
Warranty 18 months
Product Certifications
  • CSA
  • EAC
  • CB Scheme
  • CCC
  • UL
  • UKCA
Power Dissipation Per Pole 150 W AC-1
Average Impedance 0.1 mOhm - Ith 1400 A 50 Hz
Control Circuit Voltage Limits
  • operational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil
  • drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil
  • operational: 0.85...1.1 Uc DC with LX4 coil
  • drop-out: 0.2...0.35 Uc DC with LX4 coil
[Ith] Conventional Free Air Thermal Current 1400 A 40 °C
Standards
  • EN 60947-4-1
  • IEC 60947-1
  • JIS C8201-4-1
  • IEC 60947-4-1
  • EN 60947-1
  • UL 60947-4-1
  • CSA C22.2 No 60947-4-1
[Uc] Control Circuit Voltage
  • 100...500 V AC 40...400 Hz with LX1/LX9 coil
  • 110...440 V DC with LX4 coil
Mounting Support plate
Rated Breaking Capacity 2100 A IEC 60947-4-1
Irms Rated Making Capacity 2100 A AC IEC 60947-4-1
Associated Fuse Rating 1600 A gG <= 440 V IEC 60947-4-1
[Uimp] Rated Impulse Withstand Voltage 8 kV
Inrush Power In Va
  • 1600-2400 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
  • 2000-2200 VA (at 20 °C)with LX4 coil
Connections - Terminals
  • power circuit bar 2
  • power circuit bolted connection
  • control circuit screw clamp terminals 1 1-4 mm²flexible without cable end
  • control circuit screw clamp terminals 2 1-4 mm²flexible with cable end
  • control circuit screw clamp terminals 1 1-4 mm²flexible with cable end
  • control circuit screw clamp terminals 2 1-2.5 mm²solid without cable end
  • control circuit screw clamp terminals 1 1-4 mm²
Maximum Operating Rate 600 cyc/h 55 °C
Operating Time
  • 40...50 ms closing with LX1/LX9 coil
  • 100...170 ms opening with LX1/LX9 coil
  • 50...60 ms closing with LX4 coil
  • 40...50 ms opening with LX4 coil
Tightening Torque
  • power circuit 58 N.m
  • control circuit 1.2 N.m
Mechanical Durability 0.5 Mcycles
Hold-In Power Consumption In Va
  • 29-37 VA, 40...400 Hz cos phi 0.9 (at 20 °C)with LX1/LX9 coil
  • 8-10 VA (at 20 °C)with LX4 coil
Overvoltage Category III
[Ui] Rated Insulation Voltage
  • 1000 V IEC 60947-4-1
  • 1500 V VDE 0110 group C
  • 1000 V UL 60947-4-1
[Icw] Rated Short-Time Withstand Current
  • 8000 A 40 °C - 10 s
  • 6000 A 40 °C - 30 s
  • 4500 A 40 °C - 1 min
  • 4000 A 40 °C - 3 min
  • 2600 A 40 °C - 10 min
Heat Dissipation 18-18 W
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP110206EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI1102006EN
Eu Rohs Directive Compliant
Mechanical Robustness
  • vibrations contactor open2 Gn, 5...300 Hz
  • vibrations contactor closed4 Gn, 5...300 Hz
  • shocks contactor open6 Gn for 1/2 sine wave (11 ms)
  • shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Ambient Air Temperature For Operation -5-40 °C
Height 332 mm
Net Weight 29 kg
Ambient Air Temperature For Storage -60-80 °C
Protective Treatment TH
Operating Altitude 9842.52 ft (3000 m) without derating
Width 438 mm
Depth 238.6 mm
Permissible Ambient Air Temperature Around The Device -40-60 °C
Documents