Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
K30H014UP – Cam changeover switch, Harmony K, front mounting, plastic, 4 poles, 30°, 32A, 64x64mm, marked 1/2
K30H014UP
Cam changeover switch, Harmony K, front mounting, plastic, 4 poles, 30°, 32A, 64x64mm, marked 1/2

This Harmony K30 complete cam switch/selector switch has 4 poles (4P). It also has a rating of 32A, a screw clamp mounting mode and a metallic color with black marking. It has "1 - 2" marking to indicate the position of the switch. This metal head complete cam switch/selector switch is designed to meet most industrial and process control application thanks to a compact size, an easy integration with 16mm and 22mm diameter units and has several selection functions. It has a 60 degree between its switching positions.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Range Of Product Harmony K
Fixing Mode 4 holes
Presentation Of Legend with metallic, 1 - 2 black
Ip Degree Of Protection
  • IP40 IEC 529
  • IP40 NF C 20-010
Product Or Component Type complete cam switch
[Ith] Conventional Free Air Thermal Current 32 A
Cam Switch Function changeover switch
Component Name K30
Type Of Operator Black handle
Mounting Location front
Switching Positions
  • right: 30°
  • left: 330°
Cam Switch Head Type with front plate 64 x 64 mm
Poles Description 4P
Rotary Handle Padlocking without
Return without
Off Position without Off position
Warranty 18 months
Short-Circuit Protection 50 A cartridge fuse gG
Net Weight 0.485 kg
[Uimp] Rated Impulse Withstand Voltage
  • 6 kV EN 947-1
  • 6 kV IEC 947-1
Cad Overall Height 64 mm
Switching Angle 30 °
Electrical Connection
  • captive screw clamp terminals flexible 2 x 4 mm²
  • captive screw clamp terminals solid 2 x 6 mm²
Short-Circuit Current 5000 A
[Ui] Rated Insulation Voltage
  • 690 V 3)EN 60947-1
  • 690 V 3)IEC 60947-1
Positive Opening with
Tightening Torque 1.2 N.m
Contact Operation slow-break
Mechanical Durability 300000 cycles
Switching Capacity In Ma
  • 11000 mA DC 120 V 2 inductive 50 ms)
  • 11000 mA DC 180 V 3 inductive 50 ms)
  • 11000 mA DC 60 V 1 inductive 50 ms)
  • 1200 mA DC 220 V 1 resistive 1 ms)
  • 1200 mA DC 440 V 2 resistive 1 ms)
  • 1200 mA DC 660 V 3 resistive 1 ms)
  • 16000 mA DC 140 V 3 inductive 50 ms)
  • 16000 mA DC 48 V 1 inductive 50 ms)
  • 16000 mA DC 95 V 2 inductive 50 ms)
  • 23000 mA DC 120 V 2 resistive 1 ms)
  • 23000 mA DC 180 V 3 resistive 1 ms)
  • 23000 mA DC 60 V 1 resistive 1 ms)
  • 25000 mA DC 30 V 1 inductive 50 ms)
  • 25000 mA DC 60 V 2 inductive 50 ms)
  • 25000 mA DC 90 V 3 inductive 50 ms)
  • 3200 mA DC 110 V 1 inductive 50 ms)
  • 3200 mA DC 220 V 2 inductive 50 ms)
  • 3200 mA DC 330 V 3 inductive 50 ms)
  • 32000 mA DC 140 V 3 resistive 1 ms)
  • 32000 mA DC 24 V 1 inductive 50 ms)
  • 32000 mA DC 24 V 1 resistive 1 ms)
  • 32000 mA DC 48 V 1 resistive 1 ms)
  • 32000 mA DC 48 V 2 inductive 50 ms)
  • 32000 mA DC 48 V 2 resistive 1 ms)
  • 32000 mA DC 70 V 3 inductive 50 ms)
  • 32000 mA DC 70 V 3 resistive 1 ms)
  • 32000 mA DC 95 V 2 resistive 1 ms)
  • 400 mA DC 440 V 1 resistive 1 ms)
  • 400 mA DC 660 V 2 resistive 1 ms)
  • 6500 mA DC 110 V 1 resistive 1 ms)
  • 6500 mA DC 220 V 2 resistive 1 ms)
  • 6500 mA DC 330 V 3 resistive 1 ms)
Cad Overall Width 64 mm
Cad Overall Depth 119 mm
Rohs Exemption Information Yes
Mercury Free Yes
Toxic Heavy Metal Free Yes
Reach Regulation Free of Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Nickel compounds, which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc Yes
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Ambient Air Temperature For Operation -25-55 °C
Product Certifications
  • cULus 120 V 2 hp 1 phase
  • cULus 240 V 5 hp 1 phase
  • cULus 240 V 5 hp 3 phase
  • cULus 480 V 20 hp 3 phase
Standards EN/IEC 60947-3
Ambient Air Temperature For Storage -40-70 °C
Overvoltage Category
  • class II IEC 60536
  • class II NF C 20-030
Protective Treatment TC
Documents
Royal Wholesale Electric

5.0

Powered by