TeSys GV manual self protected combination starters meet the requirements of UL 508 Type F, see UL File E164871. Manual motor starter consists of a GV2P14 motor starter protector and a LC1D09G7 IEC contactor assembled together into one device. The GV2P14 high performance manual starter with a rotary handle offers a high withstand rating and visible trip indication. The GV2P14 provides trip on overload, short circuit, undervoltage, or shunt trip. It has a 6.0 to 10.0 A thermal setting. The LC1D09B7 IEC contactor is rated 9 amperes and has a 24 VAC 50/60 Hz coil.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Product Certifications
  • RINA
  • DNV
  • GOST
  • LROS (Lloyds register of shipping)
  • UL
  • GL
  • BV
  • CCC
  • CSA
[Uc] Control Circuit Voltage 120 V AC 50/60 Hz
[Ue] Rated Operational Voltage
  • power circuit <= 690 V AC 25...400 Hz
  • power circuit <= 300 V DC
Power Dissipation Per Pole
  • 1.56 W AC-1
  • 0.2 W AC-3
Average Impedance 2.5 mOhm - Ith 25 A 50 Hz power circuit
Auxiliary Contact Composition 1 NO + 1 NC
[Ith] Conventional Free Air Thermal Current
  • 25 A 60 °C power circuit
  • 10 A 60 °C signalling circuit
Phase Failure Sensitivity yes IEC 60947-4-1
Mounting Support
  • rail
  • plate
Control Circuit Type AC 50/60 Hz
Standards
  • CSA C22.2 No 14
  • EN 60947-4-1
  • EN 60947-5-1
  • IEC 60947-4-1
  • IEC 60947-5-1
  • UL 508
Safety Reliability Level
  • B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
  • B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Contactor Application
  • resistive load
  • motor control
Rated Breaking Capacity 250 A 440 V power circuit IEC 60947
Product Or Component Type motor starter
Irms Rated Making Capacity
  • 250 A 440 V power circuit IEC 60947
  • 140 A AC signalling circuit IEC 60947-5-1
  • 250 A DC signalling circuit IEC 60947-5-1
Associated Fuse Rating
  • 10 A gG signalling circuit IEC 60947-5-1
  • 25 A gG <= 690 V type 1 power circuit
  • 20 A gG <= 690 V type 2 power circuit
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
Connections - Terminals
  • power circuit screw clamp terminals 1 1-4 mm²flexible without cable end
  • power circuit screw clamp terminals 2 1-4 mm²flexible without cable end
  • power circuit screw clamp terminals 1 1-4 mm²flexible with cable end
  • power circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end
  • power circuit screw clamp terminals 1 1-4 mm²solid without cable end
  • power circuit screw clamp terminals 2 1-4 mm²solid without cable end
  • control circuit screw clamp terminals 1 1-4 mm²flexible without cable end
  • control circuit screw clamp terminals 2 1-4 mm²flexible without cable end
  • control circuit screw clamp terminals 1 1-4 mm²flexible with cable end
  • control circuit screw clamp terminals 2 1-2.5 mm²flexible with cable end
  • control circuit screw clamp terminals 1 1-4 mm²solid without cable end
  • control circuit screw clamp terminals 2 1-4 mm²solid without cable end
Range TeSys
Pole Contact Composition 3 NO
Utilisation Category
  • AC-3
  • AC-1
  • AC-4
[Ie] Rated Operational Current
  • 9 A 60 °C) <= 440 V AC AC-3 power circuit
  • 25 A 60 °C) <= 440 V AC AC-1 power circuit
Maximum Operating Rate 3600 cyc/h 60 °C
Suitability For Isolation yes IEC 60947-1
Tightening Torque
  • power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm
  • power circuit 1.7 N.m screw clamp terminals Philips No 2
  • control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm
  • control circuit 1.7 N.m screw clamp terminals Philips No 2
Trip Unit Rating 6-10 A
Electrical Durability
  • 0.6 Mcycles 25 A AC-1 <= 440 V
  • 2 Mcycles 9 A AC-3 <= 440 V
Mechanical Durability 15 Mcycles
Poles Description 3P
Operating Time
  • 12...22 ms closing
  • 4...19 ms opening
Overvoltage Category III
Motor Power Kw
  • 2.2 kW 220...230 V AC 50/60 Hz AC-3)
  • 4 kW 380...400 V AC 50/60 Hz AC-3)
  • 4 kW 415...440 V AC 50/60 Hz AC-3)
  • 5.5 kW 500 V AC 50/60 Hz AC-3)
  • 5.5 kW 660...690 V AC 50/60 Hz AC-3)
  • 2.2 kW 400 V AC 50/60 Hz AC-4)
Maximum Horse Power Rating
  • 1 hp 230/240 V at AC 50/60 Hz for 1 phase
  • 2 hp 200/208 V at AC 50/60 Hz for 3 phase
  • 2 hp 230/240 V at AC 50/60 Hz for 3 phase
  • 5 hp 460/480 V at AC 50/60 Hz for 3 phase
  • 7.5 hp 575/600 V at AC 50/60 Hz for 3 phase
  • 0.33 hp 115 V at AC 50/60 Hz for 1 phase
[Ui] Rated Insulation Voltage
  • power circuit 690 V IEC 60947-4-1
  • power circuit 600 V CSA
  • power circuit 600 V UL
  • signalling circuit 690 V IEC 60947-1
  • signalling circuit 600 V CSA
  • signalling circuit 600 V UL
Trip Unit Technology thermal-magnetic
[Icw] Rated Short-Time Withstand Current
  • 105 A 40 °C - 10 s power circuit
  • 210 A 40 °C - 1 s power circuit
  • 30 A 40 °C - 10 min power circuit
  • 61 A 40 °C - 1 min power circuit
  • 100 A - 1 s signalling circuit
  • 120 A - 500 ms signalling circuit
  • 140 A - 100 ms signalling circuit
Protective Cover with
Non-Overlap Time
  • 1.5 ms on de-energisation between NC and NO contact
  • 1.5 ms on energisation between NC and NO contact
Minimum Switching Current 5 mA signalling circuit
Line Rated Current 10 A
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz IEC 60947-2
Connections - Terminals
  • screw clamp terminals 2 1-6 mm² solid
  • screw clamp terminals 2 1.5-6 mm² flexible without cable end
  • screw clamp terminals 2 1-4 mm² flexible with cable end
Control Circuit Voltage Limits
  • drop-out 0.3...0.6 Uc AC 50/60 Hz 60 °C)
  • operational 0.8...1.1 Uc AC 50 Hz 60 °C)
  • operational 0.85...1.1 Uc AC 60 Hz 60 °C)
Rated Duty continuous IEC 60947-4-1
Contact Compatibility M2
Magnetic Tripping Current 138-138 A
[Ith] Conventional Free Air Thermal Current 10 A IEC 60947-4-1
Motor Power Kw
  • 3-3 kW 400/415 V AC 50/60 Hz
  • 5.5-5.5 kW 690 V AC 50/60 Hz
  • 5-5 kW 500 V AC 50/60 Hz
Insulation Resistance > 10 MOhm signalling circuit
Maximum Operating Rate 25 cyc/h
Operating Position any position
Power Range
  • 0-0.5 kW 100-120 V 3 phase
  • 0.55-1 kW 100-120 V 3 phase
  • 0-0.5 kW 200-240 V 3 phase
  • 0.55-1 kW 200-240 V 3 phase
  • 1.1-2 kW 200-240 V 3 phase
  • 0-0.5 kW 380-440 V 3 phase
  • 0.55-1 kW 380-440 V 3 phase
  • 1.1-2 kW 380-440 V 3 phase
  • 2.2-3 kW 380-440 V 3 phase
  • 4-6 kW 380-440 V 3 phase
  • 0-0.5 kW 480-500 V 3 phase
  • 0.55-1 kW 480-500 V 3 phase
  • 1.1-2 kW 480-500 V 3 phase
  • 2.2-3 kW 480-500 V 3 phase
  • 4-6 kW 480-500 V 3 phase
  • 0-0.5 kW 525-690 V 3 phase
  • 0.55-1 kW 525-690 V 3 phase
  • 1.1-2 kW 525-690 V 3 phase
  • 2.2-3 kW 525-690 V 3 phase
  • 4-6 kW 525-690 V 3 phase
Utilisation Category
  • AC-3 IEC 60947-4-1
  • category A IEC 60947-2
Inrush Power In Va
  • 70-70 VA 60 Hz 0.75 20 °C)
  • 70-70 VA 50 Hz 0.75 20 °C)
Fixing Mode
  • 35 mm symmetrical DIN rail clipped auto-sensing)
  • panel screwed with 2 x M4 screws)
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947-2
[Ics] Rated Service Short-Circuit Breaking Capacity
  • 100 % 690 V AC 50/60 Hz IEC 60947-2
  • 100 % 500 V AC 50/60 Hz IEC 60947-2
  • 100 % 230/240 V AC 50/60 Hz IEC 60947-2
  • 100 % 440 V AC 50/60 Hz IEC 60947-2
  • 100 % 400/415 V AC 50/60 Hz IEC 60947-2
Control Type rotary knob
Coil Technology without built-in suppressor module
Power Dissipation Per Pole 2.5 W
Electrical Durability 100000 cycles AC-3 440 V
Motor Starter Type direct on-line contactor
Minimum Switching Voltage 17 V signalling circuit
Breaking Capacity
  • 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2
  • 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2
  • 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2
  • 50 kA Icu 500 V AC 50/60 Hz IEC 60947-2
  • 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2
Mechanical Durability 100000 cycles
Signalling Circuit Frequency 25...400 Hz
[Ui] Rated Insulation Voltage 690 V AC 50/60 Hz IEC 60947-2
Tightening Torque 1.7 N.m screw clamp terminals
Direct Connector without
Auxiliary Contacts Type
  • mechanically linked 1 NO + 1 NC IEC 60947-5-1
  • mirror contact 1 NC IEC 60947-4-1
Hold-In Power Consumption In Va
  • 7.5-7.5 VA 60 Hz 0.3 20 °C)
  • 7-7 VA 50 Hz 0.3 20 °C)
Network Frequency 50/60 Hz IEC 60947-4-1
Heat Dissipation 2-3 W 50/60 Hz
Rohs Exemption Information Yes
Mercury Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Eu Rohs Directive Compliant
Ik Degree Of Protection IK04
Mechanical Robustness
  • vibrations contactor open2 Gn, 5...300 Hz
  • vibrations contactor closed4 Gn, 5...300 Hz
  • shocks contactor open10 Gn for 11 ms
  • shocks contactor closed15 Gn for 11 ms
Ambient Air Temperature For Operation -20-60 °C
Ambient Air Temperature For Operation -5-60 °C
Height 77 mm
Standards
  • IEC 60947-2
  • UL 508
  • VDE 0113
  • NF C 79-130
  • NF C 63-650
  • IEC 60947-1
  • CSA C22.2
  • NF C 63-120
  • IEC 60947-4-1
  • VDE 0660
  • EN 60204
Climatic Withstand IACS E10
Pollution Degree 3
Product Certifications
  • UL
  • CSA
  • BV
  • DNV
  • ATEX
  • EAC
  • LROS (Lloyds register of shipping)
  • UL 508 type E
  • CCC
  • GL
  • RINA
  • TSE
  • EZU
Net Weight 0.32 kg
Depth 97 mm
Flame Retardance V1 conforming to UL 94
Ambient Air Temperature For Storage -60-80 °C
Ambient Air Temperature For Storage -40-80 °C
Width 45 mm
Height 89 mm
Protective Treatment TH
Ip Degree Of Protection IP20 IEC 60529
Ip Degree Of Protection IP20 front face IEC 60529
Operating Altitude 6561.68 ft (2000 m)
Operating Altitude 9842.52 ft (3000 m) without derating
Fire Resistance 850 °C IEC 60695-2-1
Depth 86 mm
Permissible Ambient Air Temperature Around The Device -40-70 °C at Uc
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews