CAD32T7 – TeSys Deca control relay – 3 NO   2 NC –
CAD32T7
TeSys Deca control relay - 3 NO + 2 NC - <= 690 V - 480 V AC standard coil

TeSys D control relay, 5 contacts (3NO + 2NC), 10A/690V, for control of electromagnetic loads AC-15/DC-13. It provides a 480V 50/60Hz AC control circuit, connection by screw clamp terminals. For high operating rates until 180 cycles/min and ambient temperature -40/+60°C, it procures high reliability and durability. Compact (45mm width), for clipping on 35mm DIN rail or fixing by screw. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium product (RoHS/REACh).

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Contactor Application control circuit
Product Or Component Type control relay
Product Name TeSys CAD
Range
  • TeSys
  • TeSys Deca
Device Short Name CAD
Warranty 18 months
Non-Overlap Time
  • 1.5 ms on energisation between NC and NO contact
  • 1.5 ms on de-energisation between NC and NO contact
Minimum Switching Current 5 mA
Mechanical Robustness
  • shocks control relay open10 Gn for 11 ms IEC 60068-2-27
  • shocks control relay closed15 Gn for 11 ms IEC 60068-2-27
  • vibrations control relay open2 Gn, 5...300 Hz IEC 60068-2-6
  • vibrations control relay closed4 Gn, 5...300 Hz IEC 60068-2-6
[Ue] Rated Operational Voltage <= 690 V AC 25...400 Hz
Height 77 mm
[Ith] Conventional Free Air Thermal Current 10 A 60 °C
Control Circuit Voltage Limits
  • 0.3...0.6 Uc -40-70 °C drop-out AC 50/60 Hz
  • 0.8...1.1 Uc -40-60 °C operational AC 50 Hz
  • 0.85...1.1 Uc -40-60 °C operational AC 60 Hz
  • 1...1.1 Uc 60-70 °C operational AC 50/60 Hz
Mounting Support
  • plate
  • rail
Control Circuit Type AC 50/60 Hz
[Uc] Control Circuit Voltage 480 V AC 50/60 Hz
Insulation Resistance > 10 MOhm
Irms Rated Making Capacity
  • 140 A AC IEC 60947-5-1
  • 250 A DC IEC 60947-5-1
Associated Fuse Rating 10 A gG IEC 60947-5-1
Net Weight 0.58 kg
[Uimp] Rated Impulse Withstand Voltage 6 kV IEC 60947
Inrush Power In Va 70-70 VA 50 Hz 20 °C)
Connections - Terminals
  • screw clamp terminals 1 1-4 mm²flexible without cable end
  • screw clamp terminals 2 1-4 mm²flexible without cable end
  • screw clamp terminals 1 1-4 mm²flexible with cable end
  • screw clamp terminals 2 1-2.5 mm²flexible with cable end
  • screw clamp terminals 1 1-4 mm²solid without cable end
  • screw clamp terminals 2 1-4 mm²solid without cable end
Pole Contact Composition 3 NO + 2 NC
Utilisation Category
  • DC-13
  • AC-15
  • AC-14
Minimum Switching Voltage 17 V
Maximum Operating Rate 180 cyc/mn
Tightening Torque
  • 1.2 N.m screw clamp terminals Philips No 2
  • 1.2 N.m screw clamp terminals flat Ø 6 mm
  • 1.2 N.m screw clamp terminals pozidriv No 2
Mechanical Durability 30 Mcycles
Hold-In Power Consumption In Va 8-8 VA 50 Hz 20 °C)
Operating Time
  • 12...22 ms coil energisation and NO closing
  • 4...12 ms coil de-energisation and NO opening
  • 4...19 ms coil energisation and NC opening
  • 6...17 ms coil de-energisation and NC closing
Width 45 mm
Depth 84 mm
[Ui] Rated Insulation Voltage
  • 600 V UL
  • 600 V CSA
  • 690 V IEC 60947-5-1
[Icw] Rated Short-Time Withstand Current
  • 100 A - 1 s
  • 120 A - 500 ms
  • 140 A - 100 ms
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1501004
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile ENVEOLI1501004
Eu Rohs Directive Compliant
Product Certifications
  • CB Scheme
  • CCC
  • UL
  • CSA
  • EAC
  • CE
  • UKCA
Ambient Air Temperature For Operation
  • -40-60 °C
  • 60-70 °C with derating
Standards
  • EN/IEC 60947-5-1
  • GB/T 14048.5
  • UL 60947-5-1
  • CSA C22.2 No 60947-5-1
  • JIS C8201-5-1
Ambient Air Temperature For Storage -60-80 °C
Protective Treatment TH IEC 60068
Ip Degree Of Protection IP2X front face VDE 0106
Operating Altitude 0...9842.52 ft (0...3000 m)