Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
BMXDRC0805 – discrete output module, Modicon X80, 8 NO or NC relay outputs, 24 to 240V AC, 24 to 125V DC
BMXDRC0805
discrete output module, Modicon X80, 8 NO or NC relay outputs, 24 to 240V AC, 24 to 125V DC
Specifications
Range Of Product Modicon X80
Discrete Output Number 8 EN/IEC 61131-2
Discrete Output Logic positive or negative
Discrete Output Voltage
  • 5...125 V 5...150 V DC
  • 24...240 V 19...264 V AC
Product Or Component Type relay discrete output module
Mtbf Reliability 2650000 H
Network Frequency 50/60 Hz
Voltage Range
  • 5...150 V
  • 19...264 V
Minimum Switching Current 10 mA 5 V DC
[Ith] Conventional Free Air Thermal Current
  • 4 A 40 °C
  • 3 A 50 °C
  • 2 A 60 °C
Status Led
  • 1 LED (Green) RUN
  • 1 LED per channel (Green) channel diagnostic
  • 1 LED (Red) ERR
  • 1 LED (Red) I/O
Insulation Resistance > 10 MOhm 500 V DC
Network Frequency Limits 47-63 Hz
Protection Type
  • external short-circuit protection
  • external overload protection
  • external overvoltage protection, inductive AC
  • external overvoltage protection, inductive DC
Power Dissipation In W 3.6 W
Net Weight 0.189 kg
Electrical Connection 40 ways terminal block
Electrical Durability
  • AC-12 200000 cycles 48 VA 24 V 0-60 °C
  • AC-12 300000 cycles 48 VA 48 V 0-60 °C
  • AC-12 150000 cycles 96 VA 48 V 0-60 °C
  • AC-12 300000 cycles 110 VA 100...120 V 0-60 °C
  • AC-12 150000 cycles 220 VA 100...120 V 0-60 °C
  • AC-12 300000 cycles 220 VA 200...250 V 0-60 °C
  • AC-12 150000 cycles 500 VA 200...250 V 0-60 °C
  • AC-15 700000 cycles 10 VA 24 V 0-60 °C 0.4 )
  • AC-15 500000 cycles 24 VA 24 V 0-60 °C 0.4 )
  • AC-15 200000 cycles 48 VA 24 V 0-60 °C 0.4 )
  • AC-15 700000 cycles 10 VA 48 V 0-60 °C 0.4 )
  • AC-15 500000 cycles 24 VA 48 V 0-60 °C 0.4 )
  • AC-15 300000 cycles 48 VA 48 V 0-60 °C 0.4 )
  • AC-15 100000 cycles 96 VA 48 V 0-60 °C 0.4 )
  • AC-15 1000000 cycles 10 VA 100...120 V 0-60 °C 0.4 )
  • AC-15 300000 cycles 50 VA 100...120 V 0-60 °C 0.4 )
  • AC-15 200000 cycles 110 VA 100...120 V 0-60 °C 0.4 )
  • AC-15 70000 cycles 220 VA 100...120 V 0-60 °C 0.4 )
  • AC-15 1000000 cycles 10 VA 200...250 V 0-60 °C 0.4 )
  • AC-15 500000 cycles 50 VA 200...250 V 0-60 °C 0.4 )
  • AC-15 200000 cycles 110 VA 200...250 V 0-60 °C 0.4 )
  • AC-15 150000 cycles 220 VA 200...250 V 0-60 °C 0.4 )
  • DC-12 200000 cycles 24 W 24 V 0-60 °C
  • DC-12 150000 cycles 48 W 24 V 0-60 °C
  • DC-12 150000 cycles 40 W 48...60 V 0-60 °C
  • DC-12 100000 cycles 45 W 100...125 V 0-60 °C
  • DC-13 100000 cycles 10 W 24 V 0-60 °C
  • DC-13 60000 cycles 24 W 24 V 0-60 °C
  • DC-13 40000 cycles 48 W 24 V 0-60 °C
  • DC-13 40000 cycles 40 W 48...60 V 0-60 °C
  • DC-13 100000 cycles 15 W 100...125 V 0-60 °C
Typical Current Consumption
  • 40 mA 3.3 V DC
  • 101 mA 24 V DC
Output Overvoltage Protection
  • use discharge diode on each output DC
  • use RC circuit on each output AC
  • use ZNO surge limiter on each output AC
Output Short-Circuit Protection use 1 fast blow fuse per channel or group of channel
Output Overload Protection use 1 fast blow fuse per channel or group of channel
Response Time On Output
  • <= 10 ms activation
  • <= 13 ms deactivation
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP070204EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI0702004EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Shock Resistance 30 gn
Dielectric Strength 1780 V AC 50/60 Hz 1 min
Vibration Resistance 3 gn
Relative Humidity 0-95 % 0-60 °C without condensation
Operating Altitude
  • 0...6561.68 ft (0...2000 m)
  • 2000...5000 m with derating factor
Ip Degree Of Protection IP20
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews