Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
BMXCPS3522 – redundant power supply module, Modicon X80, 125V DC
BMXCPS3522
redundant power supply module, Modicon X80, 125V DC
Specifications
Primary Voltage 125 V
Range Of Product Modicon X80
Product Or Component Type power supply module
Function Available
  • uptime duration
  • temperature sensing
  • remaining lifetime
  • redundancy information
  • redundancy test
Secondary Power
  • 18 W 3.3 V DC 0-60 °C I/O module logic power supply
  • 40 W 24 V DC 0-60 °C I/O module power supply and processor if 3.3 V not loaded
Supply Circuit Type DC
Product Compatibility all backplane
Mtbf Reliability 830000 H
Primary Voltage Limit 100...150 V
It On Activation 0.09 A.s 125 V
Status Led
  • 1 LED (Green) presence of voltages (OK)
  • 1 LED (Green) redundancy OK
  • 1 LED (Green) power supply status
I²T On Activation 2.5 A².s 125 V
Input Current 600 mA 125 V
Current At Secondary Voltage
  • 1.67 A 24 V DC I/O module power supply and processor
  • 5 A 3.3 V DC I/O module logic power supply
Insulation Resistance
  • >= 100 MOhm primary/ground
  • >= 100 MOhm primary/secondary
Net Weight 0.61 kg
Control Type RESET push-button cold restart
Maximum Power Dissipation In W 8.5 W
Electrical Connection
  • 1 connector 2 alarm relay
  • 1 connector 5 line supply, protective earth
Inrush Current 60 A 125 V
Protection Type
  • internal fuse not accessible primary circuit
  • overload protection secondary circuit
  • overvoltage protection secondary circuit
  • short-circuit protection secondary circuit
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1710011EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI1710011EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Ambient Air Temperature For Operation 0-60 °C
Immunity To Microbreaks 1 ms
Environmental Characteristic
  • 3C3 EN/IEC 60721-3-3
  • 3C4 EN/IEC 60721-3-3
Directives
  • 2014/35/EU - low voltage directive
  • 2014/30/EU - electromagnetic compatibility
Ambient Air Temperature For Storage -40-85 °C
Relative Humidity 10-95 % without condensation
Ip Degree Of Protection IP20
Dielectric Strength
  • 1500 V primary/secondary I/O module logic power supply
  • 1500 V primary/secondary I/O module power supply and processor
  • 2300 V primary/secondary sensor power supply
  • 1500 V primary/ground