Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
BJL46125LU – Circuit breaker, PowerPacT B, 125A, 4 pole, 600Y/347VAC, 25kA, lugs, thermal magnetic, 80%, control wire ON end
BJL46125LU
Circuit breaker, PowerPacT B, 125A, 4 pole, 600Y/347VAC, 25kA, lugs, thermal magnetic, 80%, control wire ON end
Specifications
Product Or Component Type circuit breaker
Product Name PowerPact B
Device Application distribution
Device Short Name BJ 125
Range PowerPact
Circuit Breaker Application HACR rated
Mounting Mode
  • clip-on 35 mm symmetrical DIN rail)
  • by screws plate)
Network Frequency 50/60 Hz
Wire Stripping Length 20 mm
Utilisation Category category A
Line Rated Current 125-125 A
[Ics] Rated Service Breaking Capacity
  • 100 kA 220...240 V AC 50/60 Hz IEC 60947-2
  • 25 kA 500...525 V AC 50/60 Hz IEC 60947-2
  • 2.5 kA 690 V AC 50/60 Hz IEC 60947-2
  • 65 kA 380...415 V AC 50/60 Hz IEC 60947-2
  • 65 kA 440 V AC 50/60 Hz IEC 60947-2
Trip Unit Technology thermal-magneticTM-D,
Trip Unit Name TM-D
Height 137 mm
Continuous Current Rating 80 %
Breaking Capacity
  • 100 kA 208Y/120 V AC 50/60 Hz UL 489
  • 100 kA 240 V AC 50/60 Hz UL 489
  • 65 kA 480/277 V AC 50/60 Hz UL 489
  • 65 kA 480 V AC 50/60 Hz UL 489
  • 25 kA 600Y/347 V AC 50/60 Hz UL 489
  • 50 kA 250 V DC UL 489
[Ui] Rated Insulation Voltage 800 V IEC 60947-2
Connection Pitch 27 mm
Mechanical Durability 15000 cycles IEC 947-1 Annex K ed 5.2
Suitability For Isolation yes IEC 60947-2
[Ue] Rated Operational Voltage 690 V AC 50/60 Hz UL 489
Tightening Torque
  • 5-5 N.m 2.5-16 mm² (AWG 14...AWG 4)
  • 9-9 N.m 25-95 mm² (AWG 3...AWG 3/0)
Electrical Durability 10000 cycles IEC 947-1 Annex K ed 5.2 440 V In
Breaking Capacity Code J
9 Mm Pitches 12
Poles Description 4P
Local Signalling presence of auxiliary contacts flag green)
Quantity Per Set set of 1
Number Of Slots
  • 1 auxiliary switch OF plug-in)
  • 1 voltage release MN or MX plug-in)
  • 1 alarm switch SD plug-in)
Protected Poles Description 4t
Awg Gauge
  • AWG 6...AWG 2/0 fine stranded aluminium/copper
  • AWG 14...AWG 3/0 rigid or stranded aluminium/copper
Color Gray RAL 7016)
Width 108 mm
Electrical Connection
  • Everlink lug line
  • Everlink lug load
Depth 80 mm
Net Weight 1.441 kg
[Uimp] Rated Impulse Withstand Voltage 8 kV IEC 60947-2
Control Type toggle
China Rohs Regulation Product out of China RoHS scope. Substance declaration for your information.
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP1610005EN
Sustainable Offer Status Green Premium product
Pvc Free Yes
Eu Rohs Directive Compliant
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Halogen Content Performance Halogen free product
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Ik Degree Of Protection IK07 IEC 62262
Ambient Air Temperature For Operation -25-70 °C
Pollution Degree 3 IEC 60947-1
Ambient Air Temperature For Storage -50-85 °C
Standards
  • NEMA AB1
  • EN/IEC 60947-2
  • NMX J-266
  • CSA C22.2 No 5
  • GB 14048.2
  • EN/IEC 60947-5-1
  • UL 489
Quality Labels CE
Product Certifications
  • UL
  • IEC
  • CCC
  • EAC
  • CSA
  • NOM
Operating Altitude
  • 6561.68 ft (2000 m) without derating
  • 5000 m with derating
Ip Degree Of Protection front cover IP40 IEC 60529
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews