Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
ATV630U75S6X – Variable speed drive, Altivar Process ATV600, ATV630, 10 HP, 600 V, IP21
ATV630U75S6X
variable speed drive, Altivar Process ATV600, ATV630, 10hp, 600V, IP21
Specifications
Prospective Line Isc 70 kA
Product Destination
  • asynchronous motors
  • synchronous motors
Line Current
  • 11.9 A 480 V normal duty)
  • 10.5 A 380 V heavy duty)
  • 9.2 A 480 V heavy duty)
  • 9.9 A 600 V normal duty)
Emc Filter without EMC filter
Asynchronous Motor Control Profile
  • optimized torque mode
  • constant torque standard
  • variable torque standard
Variant standard version
Product Or Component Type variable speed drive
Apparent Power
  • 7.6 kVA 480 V heavy duty)
  • 10.3 kVA 600 V normal duty)
Switching Frequency
  • 4...12 kHz with derating factor
  • 2...12 kHz adjustable
Communication Port Protocol
  • Modbus serial
  • Modbus TCP
Product Specific Application process and utilities
Safety Function STO (safe torque off) SIL 3
Maximum Horse Power Rating
  • 7.5 hp heavy duty
  • 10 hp 600 V normal duty
Supply Frequency 50...60 Hz - 5...5 %
Option Card
  • slot A communication module, PROFINET
  • slot A communication module, DeviceNet
  • slot A communication module, Modbus TCP/EtherNet/IP
  • slot A communication module, CANopen daisy chain RJ45
  • slot A communication module, CANopen SUB-D 9
  • slot A communication module, CANopen screw terminals
  • slot A/slot B digital and analog I/O extension module
  • slot A/slot B output relay extension module
  • slot A communication module, Ethernet IP/Modbus TCP/MD-Link
  • communication module, BACnet MS/TP
  • communication module, Ethernet Powerlink
  • slot A communication module, Profibus DP V1
Degree Of Protection UL type 1 UL 508C
Range Of Product Altivar Process ATV600
Speed Drive Output Frequency 0.1-500 Hz
Ip Degree Of Protection
  • IP20IEC 60529
  • IP21IEC 61800-5-1
Motor Power Kw 5.5 kW heavy duty)
[Us] Rated Supply Voltage 600 V
[Us] Rated Supply Voltage 600 V - 15...10 %
Discrete Input Logic 16 preset speeds
Type Of Cooling forced convection
Continuous Output Current
  • 12.7 A 4 kHz heavy duty
  • 13.5 A 4 kHz normal duty
Nominal Switching Frequency 4 kHz
Device Short Name ATV630
Synchronous Motor Control Profile
  • synchronous reluctance motor
  • permanent magnet motor
Discrete Input Logic
  • positive logic (source) DI1...DI8), < 5 V, > 11 V
  • negative logic (sink) DI1...DI8), > 16 V, < 10 V
Analogue Output Type
  • software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits
  • software-configurable current AQ1, AQ2 0...20 mA 10 bits
  • software-configurable current DQ-, DQ+ 30 V DC
  • software-configurable current DQ-, DQ+ 100 mA
Discrete Output Type
  • relay outputs R1A, R1B, R1C 250 V AC 3000 mA
  • relay outputs R1A, R1B, R1C 30 V DC 3000 mA
  • relay outputs R2A, R2C 250 V AC 5000 mA
  • relay outputs R2A, R2C 30 V DC 5000 mA
  • relay outputs R3A, R3C 250 V AC 5000 mA
  • relay outputs R3A, R3C 30 V DC 5000 mA
Maximum Switching Current
  • relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC
  • relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC
  • relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
  • relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC
Exchange Mode half duplex, full duplex, autonegotiation Ethernet/Modbus TCP
Power Range 7-11 kW 480-500 V 3 phase
Phase 3 phase
Net Weight 5.5 kg
Type Of Polarization no impedance
Relay Output Type
  • configurable relay logic R2 sequence relay NO 100000 cycles
  • configurable relay logic R3 sequence relay NO 100000 cycles
  • configurable relay logic R1 fault relay NO/NC 100000 cycles
Frequency Resolution
  • analog input 0.012/50 Hz
  • display unit 0.1 Hz
Maximum Transient Current
  • 19.1 A 60 s heavy duty)
  • 14.9 A 60 s normal duty)
Analogue Input Number 3
Motor Slip Compensation
  • can be suppressed
  • automatic whatever the load
  • adjustable
Discrete Output Number 0
Method Of Access slave Modbus TCP
Discrete Input Number 8
Local Signalling
  • for embedded communication status 3 LEDs (dual colour)
  • for communication module status 4 LEDs (dual colour)
  • for presence of voltage 1 LED (red)
  • for local diagnostic 3 LEDs
Linearity Error
  • AO1, AO2 +/- 0.2 % analog output
  • AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
Number Of Addresses 1-247 Modbus serial
Width 171 mm
Transmission Rate
  • 10, 100 Mbits
  • 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps
Depth 233 mm
Analogue Input Type
  • AI1, AI2, AI3 software-configurable voltage 0...10 V DC 31.5 kOhm 12 bits
  • AI1, AI2, AI3 software-configurable current 0...20 mA 250 Ohm 12 bits
  • AI2 voltage analog input - 10...10 V DC 31.5 kOhm 12 bits
Discrete And Process Manufacturing
  • food and beverage processing other application
  • mining mineral and metal fan
  • mining mineral and metal pump
  • oil and gas fan
  • water and waste water other application
  • building - HVAC screw compressor
  • food and beverage processing pump
  • food and beverage processing fan
  • food and beverage processing atomization
  • oil and gas electro submersible pump (ESP)
  • oil and gas water injection pump
  • oil and gas jet fuel pump
  • oil and gas compressor for refinery
  • water and waste water centrifuge pump
  • water and waste water positive displacement pump
  • water and waste water electro submersible pump (ESP)
  • water and waste water screw pump
  • water and waste water lobe compressor
  • water and waste water screw compressor
  • water and waste water compressor centrifugal
  • water and waste water fan
  • water and waste water conveyor
  • water and waste water mixer
Sampling Duration
  • 5 ms +/- 1 ms DI5, DI6) - discrete input
  • 5 ms +/- 0.1 ms AI1, AI2, AI3) - analog input
  • 10 ms +/- 1 ms AO1) - analog output
  • 2 ms +/- 0.5 ms DI1...DI4) - discrete input
Electrical Connection
  • motor screw terminal 6...10 mm² AWG 10...AWG 8
  • line side screw terminal 4...6 mm² AWG 12...AWG10
  • control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16
Maximum Output Frequency 500 kHz
Height 409 mm
Acceleration And Deceleration Ramps linear adjustable separately from 0.01...9999 s
Transmission Frame RTU
Relay Output Number 3
Data Format 8 bits, configurable odd, even or no parity
Accuracy
  • +/- 1 % AO1, AO2 for a temperature variation 60 °C analog output
  • +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
Connector Type
  • RJ45 on the remote graphic terminal)Modbus serial
  • RJ45 on the remote graphic terminal)Ethernet/Modbus TCP
Input Compatibility
  • DI5, DI6 discrete input level 1 PLC IEC 65A-68
  • STOA, STOB discrete input level 1 PLC EN/IEC 61131-2
  • DI1...DI6 discrete input level 1 PLC EN/IEC 61131-2
Permissible Temporary Current Boost
  • 1.5 x In 60 s heavy duty)
  • 1.1 x In 60 s normal duty)
Mounting Mode wall mount
Analogue Output Number 2
Physical Interface
  • Ethernet
  • 2-wire RS 485
Minimum Switching Current relay output R1, R2, R3 5 mA 24 V DC
Refresh Time relay output R1, R2, R3)5 ms +/- 0.5 ms)
Enclosure Mounting wall mounted
Isolation between power and control terminals
Output Voltage <= power supply voltage
Quantity Per Set 1
Braking To Standstill by DC injection
Discrete Input Type DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V)
Protection Type
  • safe torque off motor
  • motor phase break motor
  • thermal protection drive
  • safe torque off drive
  • overheating drive
  • overcurrent between output phases and earth drive
  • overload of output voltage drive
  • short-circuit protection drive
  • motor phase break drive
  • overvoltages on the DC bus drive
  • line supply overvoltage drive
  • line supply undervoltage drive
  • line supply phase loss drive
  • overspeed drive
  • break on the control circuit drive
  • thermal protection motor
Supply
  • internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection
  • internal supply for digital inputs and STO 24 V DC 21-27 V), <200 mA overload and short-circuit protection
  • external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection
Mercury Free Yes
Reach Regulation Reference contains Substances of Very High Concern above the threshold
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Upgradeability Upgraded components available
Rohs Exemption Information Yes
Environmental Disclosure ENVPEP1707007EN
Sustainable Offer Status Green Premium product
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Circularity Profile ENVEOLI1707007EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • ATEX INERIS
  • UL
  • ATEX zone 2/22
  • CSA
  • TÜV
Power Dissipation In W
  • forced convection 44 W 380 V 4 kHz
  • natural convection 105 W 600 V 4 kHz
Standards
  • EN/IEC 61800-3
  • EN/IEC 61800-3 environment 1 category C2
  • EN/IEC 61800-3 environment 2 category C3
  • EN/IEC 61800-5-1
  • IEC 61000-3-12
  • IEC 60721-3
  • IEC 61508
  • IEC 13849-1
  • UL 508C
Insulation Resistance > 1 MOhm 500 V DC for 1 minute to earth
Shock Resistance 15 gn 11 ms IEC 60068-2-27
Vibration Resistance
  • 1 gn 13-200 Hz)IEC 60068-2-6
  • 1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6
Noise Level 52 dB 86/188/EEC
Regulation Loop adjustable PID regulator
Operating Altitude
  • 1000...4800 m with current derating 1 % per 100 m
  • <= 3280.84 ft (1000 m) without derating
Overvoltage Category III
Pollution Degree 2
Electromagnetic Compatibility
  • radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
  • electrical fast transient/burst immunity test level 4 IEC 61000-4-4
  • 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5
  • conducted radio-frequency immunity test level 3 IEC 61000-4-6
  • electrostatic discharge immunity test level 3 IEC 61000-4-2
Ambient Air Temperature For Operation
  • 50-60 °C with derating factor)
  • -15-50 °C without derating)
Volume Of Cooling Air 103 m3/h
Pollution Degree 2 EN/IEC 61800-5-1
Noise Level 56 dB
Ambient Air Temperature For Storage -40-70 °C
Relative Humidity 5-95 % without condensation IEC 60068-2-3
Operating Position vertical +/- 10 degree
Maximum Thdi <48 % with external line choke IEC 61000-3-12
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews