Specifications
Product Destination asynchronous motors
Range Of Product Altivar 212
Product Or Component Type variable speed drive
Ip Degree Of Protection IP55
Motor Power Kw 30 kW
Phase 3 phase
Line Current
  • 44.4 A 480 V
  • 58.2 A 380 V
[Us] Rated Supply Voltage 380...480 V - 15...10 %
Communication Port Protocol
  • LonWorks
  • APOGEE FLN
  • BACnet
  • METASYS N2
  • Modbus
Supply Voltage Limits 323-528 V
Product Specific Application pumps and fans in HVAC
Emc Filter Class C1 EMC filter integrated
Maximum Horse Power Rating 40 hp
Device Short Name ATV212
Supply Frequency 50...60 Hz - 5...5 %
Warranty 18 months
Prospective Line Isc 22 kA
Electrical Connection
  • VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 2.5-2.5 mm² / AWG 14
  • L1/R, L2/S, L3/T terminal 25-25 mm² / AWG 3
  • U/T1, V/T2, W/T3 terminal 50-50 mm² / AWG 1/0
Network Frequency 47.5...63 Hz
Discrete Input Logic
  • positive logic (source) F, R, RES), <= 5 V, >= 11 V
  • negative logic (sink) F, R, RES), >= 16 V, <= 10 V
Type Of Cable
  • without mounting kit 1 IEC cable 45 °C, copper 90 °C / XLPE/EPR
  • without mounting kit 1 IEC cable 45 °C, copper 70 °C / PVC
  • with UL Type 1 kit 3 UL 508 cable 40 °C, copper 75 °C / PVC
Height 720 mm
Acceleration And Deceleration Ramps
  • linear adjustable separately from 0.01 to 3200 s
  • automatic based on the load
Analogue Output Type
  • FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits
  • FM switch-configurable current 0...20 mA 970 Ohm 10 bits
Speed Drive Output Frequency 0.5-200 Hz
Discrete Output Type
  • configurable relay logic FLA, FLC) NO - 100000 cycles
  • configurable relay logic FLB, FLC) NC - 100000 cycles
  • configurable relay logic RY, RC) NO - 100000 cycles
Transmission Frame RTU
Torque Accuracy +/- 15 %
Asynchronous Motor Control Profile
  • voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo)
  • voltage/frequency ratio, 5 points
  • voltage/frequency ratio, 2 points
  • voltage/frequency ratio - Energy Saving, quadratic U/f
  • flux vector control without sensor, standard
Maximum Switching Current
  • 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R)
  • 5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R)
  • 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R)
  • 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R)
Communication Service
  • write single register (06)
  • monitoring inhibitable
  • write multiple registers (16) 2 words maximum
  • read device identification (43)
  • time out setting from 0.1 to 100 s
  • read holding registers (03) 2 words maximum
Transient Overtorque 120-120 % of nominal motor torque +/- 10 % 60 s
Insulation Resistance >= 1 mOhm 500 V DC for 1 minute
Response Time
  • FM 2 ms +/- 0.5 ms analog
  • FLA, FLC 7 ms +/- 0.5 ms discrete
  • FLB, FLC 7 ms +/- 0.5 ms discrete
  • RY, RC 7 ms +/- 0.5 ms discrete
Data Format 8 bits, 1 stop, odd even or no configurable parity
Apparent Power 44.6 kVA 380 V
Dielectric Strength
  • 3535 V DC between earth and power terminals
  • 5092 V DC between control and power terminals
Net Weight 58.5 kg
Type Of Polarization no impedance
Frequency Resolution
  • display unit 0.1 Hz
  • analog input 0.024/50 Hz
Accuracy
  • +/- 0.6 % VIA) for a temperature variation 60 °C
  • +/- 0.6 % VIB) for a temperature variation 60 °C
  • +/- 1 % FM) for a temperature variation 60 °C
Switching Frequency
  • 6...16 kHz adjustable
  • 8...16 kHz with derating factor
Maximum Transient Current 64.4 A 60 s
Connector Type
  • 1 RJ45
  • 1 open style
Analogue Input Number 2
Motor Slip Compensation
  • automatic whatever the load
  • not available in voltage/frequency ratio motor control
  • adjustable
Discrete Output Number 2
Minimum Switching Current 3 mA 24 V DC configurable relay logic
Analogue Output Number 1
Physical Interface 2-wire RS 485
Continuous Output Current
  • 58.5 A 380 V
  • 58.5 A 460 V
Number Of Addresses 1-247
Tightening Torque
  • 0.6 N.m VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES)
  • 4.3 N.m, 38 lb.in L1/R, L2/S, L3/T)
  • 24 N.m, 212 lb.in U/T1, V/T2, W/T3)
Discrete Input Type
  • F programmable 24 V DC level 1 PLC 4700 Ohm
  • R programmable 24 V DC level 1 PLC 4700 Ohm
  • RES programmable 24 V DC level 1 PLC 4700 Ohm
Speed Range 1-10
Isolation electrical between power and control
Local Signalling for DC bus energized 1 LED (red)
Linearity Error
  • VIA +/- 0.15 % of maximum value input
  • VIB +/- 0.15 % of maximum value input
  • FM +/- 0.2 % output
Specific Application HVAC
Output Voltage <= power supply voltage
Nominal Switching Frequency 8 kHz
Width 284 mm
Transmission Rate 9600 bps or 19200 bps
Braking To Standstill by DC injection
Depth 315 mm
Protection Type
  • overheating protection drive
  • line supply undervoltage drive
  • against input phase loss drive
  • thermal protection motor
  • motor phase break motor
  • with PTC probes motor
  • thermal power stage drive
  • short-circuit between motor phases drive
  • input phase breaks drive
  • overcurrent between output phases and earth drive
  • overvoltages on the DC bus drive
  • break on the control circuit drive
  • against exceeding limit speed drive
  • line supply overvoltage and undervoltage drive
Supply
  • internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection
  • internal supply 24 V DC 21-27 V), <200 A overload and short-circuit protection
Analogue Input Type
  • VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits
  • VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits
  • VIB configurable PTC probe 0...6 probes 1500 Ohm
  • VIA switch-configurable current 0...20 mA 250 Ohm 10 bits
Sampling Duration
  • 2 ms +/- 0.5 ms F discrete
  • 2 ms +/- 0.5 ms R discrete
  • 2 ms +/- 0.5 ms RES discrete
  • 3.5 ms +/- 0.5 ms VIA analog
  • 22 ms +/- 0.5 ms VIB analog
Speed Accuracy +/- 10 % of nominal slip 0.2 Tn to Tn
Option Card communication card LonWorks
Rohs Exemption Information Yes
Mercury Free Yes
Environmental Disclosure ENVPEP111244EN
Sustainable Offer Status Green Premium product
Reach Regulation Reference contains Substances of Very High Concern above the threshold
California Proposition 65 WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation X
Circularity Profile ENVEOLI111242EN
Eu Rohs Directive Pro-active compliance (Product out of EU RoHS legal scope)
Product Certifications
  • CSA
  • UL
  • C-tick
  • NOM 117
Standards
  • EN 61800-3
  • EN 61800-3 environments 2 category C3
  • EN 61800-3 environments 2 category C2
  • EN 61800-3 environments 2 category C1
  • EN 61800-3 environments 1 category C1
  • IEC 61800-5-1
  • EN 61800-5-1
  • IEC 61800-3 category C1
  • IEC 61800-3 environments 2 category C3
  • IEC 61800-3 environments 1 category C2
  • IEC 61800-3
  • IEC 61800-3 environments 1 category C1
  • IEC 61800-3 environments 1 category C3
  • EN 55011 group 1 class B
  • EN 61800-3 environments 1 category C2
  • EN 61800-3 environments 1 category C3
  • EN 61800-3 category C1
  • IEC 61800-3 environments 2 category C2
  • IEC 61800-3 environments 2 category C1
Electromagnetic Compatibility
  • electrostatic discharge immunity test level 3 IEC 61000-4-2
  • radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3
  • electrical fast transient/burst immunity test level 4 IEC 61000-4-4
  • 1.2/50 µs - 8/20 µs surge immunity test level 3 IEC 61000-4-5
  • conducted radio-frequency immunity test level 3 IEC 61000-4-6
  • voltage dips and interruptions immunity test IEC 61000-4-11
Ambient Air Temperature For Operation
  • -10-40 °C without derating)
  • 40-50 °C with derating factor)
Shock Resistance 15 gn 11 ms IEC 60068-2-27
Environmental Characteristic
  • classes 3C1 IEC 60721-3-3
  • classes 3S2 IEC 60721-3-3
Marking CE
Vibration Resistance
  • 1.5 mm 3-13 Hz)EN/IEC 60068-2-6
  • 1 gn 13-200 Hz)EN/IEC 60068-2-8
Noise Level 59.9 dB 86/188/EEC
Pollution Degree 3 IEC 61800-5-1
Regulation Loop adjustable PI regulator
Ambient Air Temperature For Storage -25-70 °C
Relative Humidity
  • 5-95 % without condensation IEC 60068-2-3
  • 5-95 % without dripping water IEC 60068-2-3
Assembly Style with heat sink
Ip Degree Of Protection
  • IP55 EN/IEC 61800-5-1
  • IP55 EN/IEC 60529
Operating Altitude
  • 3280.84...9842.52 ft (1000...3000 m) limited to 2000 m for the Corner Grounded distribution network with current derating 1 % per 100 m
  • <= 3280.84 ft (1000 m) without derating
Operating Position vertical +/- 10 degree