Altivar Soft Starter ATS480 is intended to start and stop asynchronous motors supplied from 208V to 690V. It meets the requirements of the most demanding applications in normal and heavy duty. With an operational rated current of 590A in normal duty, it supplies motor from 160kW to 560kW according to mains voltage. Designed for digitization, connected, optimized to meet cybersecurity standard, it simplifies project execution and maximizes the availability of applications. Its torque control (TCS) masters acceleration and deceleration. It efficiently stops high inertia application thanks to the dynamic braking and DC injection. It could be connected in-line or inside the delta to reduce its operational current. The embedded test routine simplifies the commissioning inside the delta. Its dimensions are 400mm (width) x 314mm (depth) x 670mm (height) and it weighs 51,4kg. Altivar Soft Starter ATS480 is designed to address process, infrastructures and industrial machines. It conforms to IEC/EN60947-4-1. It is certified CE, cULus, UKCA, CCC, RCM, EAC, and Marine certified DNV, ABS, BV and CCS. Display terminals, remote mounting kit, communication modules are common with Altivar Drives. Line chokes, DNV kits are common with ATS48. ATS480 is compatible with ATS48, it has same footprint, fixing, torque control algorithm, I/O, menus… The integration of Altivar Soft Starter ATS480 in EcoStruxure drastically simplifies architecture selection, detailed design and execution in automation and electrical systems. It is a Green Premium product designed to take the environmental considerations beyond current directives and regulations, compliant with RoHS and REACH.
Brand: Schneider Electric
Add to Quote CatalogueProduct Destination | asynchronous motors |
---|---|
Range Of Product | Altivar Soft Starter ATS480 |
Product Or Component Type | soft starter |
Maximum Permanent Current | 480.0 A at 40 °C heavy duty |
Motor Power Kw |
|
Phase | 3 phase |
Utilisation Category |
|
[Ie] Rated Operational Current | normal duty 590.0 A 40 °C) |
[Us] Rated Supply Voltage | 208...690 V - 15...10 % |
Product Specific Application | process and infrastructures |
Torque Control | true |
Maximum Horse Power Rating |
|
Device Short Name | ATS480 |
Ip Degree Of Protection | IP00 |
Supply Frequency | 50...60 Hz - 20...20 % |
Option Card |
|
Product Certifications |
|
Device Connection |
|
Height | 670.0 mm |
Standards |
|
Transmission Frame | RTU |
Analogue Output Type | current output AQ1 0...20 mA or 0...10 V 500 Ohm |
[Uc] Control Circuit Voltage | 110...230 V AC 50/60 Hz - 15...10 % |
Maximum Switching Current |
|
Relay Output Number | 3 |
Data Format | 8 bits, configurable odd, even or no parity |
Marking |
|
Output Current Drift | 150-700 % |
Display Screen Available | true |
Net Weight | 51.4 kg |
Relay Output Type |
|
Connector Type | 1 RJ45 |
Analogue Input Number | 1 |
Communication Data Link | serial |
Function Available |
|
Discrete Output Number | 2 |
Communication Port Protocol | Modbus serial |
Discrete Input Type |
|
Minimum Switching Current | 10 mA 24 V DC relay outputs |
Analogue Output Number | 1 |
Physical Interface | 2-wire RS 485 |
Method Of Access | slave Modbus serial |
Integrated Motor Overload Protection | true |
[In] Rated Current Pwr Loss Specifctn | 590.0 A |
Discrete Input Number | 4 |
Accuracy Class | class 10E |
Power Loss Per Device Current Dependent | 1711.0 W |
Number Of Addresses | 0-227 Modbus serial |
Apparent Power | 0.125 kVA |
Operating Position | vertical +/- 10 degree |
Power Loss Static Current Independent | 25.0 W |
Type Of Polarization | no impedance Modbus serial |
Width | 400.0 mm |
Transmission Rate | 1200...256000 bit/s |
Depth | 314.0 mm |
Discrete Input Logic | programmable digital input < 5 V |
Protection Type |
|
Discrete Output Type |
|
Rohs Exemption Information | Yes |
Mercury Free | Yes |
Environmental Disclosure | ENVPEP2102013EN |
Sustainable Offer Status | Green Premium product |
Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
Weee | The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins. |
China Rohs Regulation | X |
Circularity Profile | ENVEOLI2102013EN |
Upgradeability | Upgraded components available |
Eu Rohs Directive | Pro-active compliance (Product out of EU RoHS legal scope) |
Maximum Acceleration Under Vibratory Load (During Transport) |
|
Maximum Acceleration Under Shock Load (During Transport) | 100 m/s² at 11 ms |
Maximum Deflection Under Vibratory Load (During Operation) | 1.5 mm at 2...13 Hz |
Maximum Acceleration Under Shock Impact (During Operation) | 150 m/s² at 11 ms |
[Uimp] Rated Impulse Withstand Voltage | 6 kV |
Pollution Degree | level 3 |
Electromagnetic Compatibility |
|
Ambient Air Temperature For Operation |
|
Maximum Deflection Under Vibratory Load (During Transport) | 1.75 mm at 2...9 Hz |
[Ui] Rated Insulation Voltage | 690 V |
Maximum Acceleration Under Vibrational Stress (During Operation) | 10 m/s² at 13...200 Hz |
Maximum Acceleration Under Vibratory Load (During Storage) |
|
Ambient Air Temperature For Storage | -25-70 °C |
Relative Humidity | 0-95 % without condensation or dripping water EN/IEC 60068-2-3 |
Operating Altitude |
|
Maximum Acceleration Under Shock Load (During Storage) | 100 m/s² at 11 ms |
Environmental Class (During Operation) |
|
Maximum Deflection Under Vibratory Load (During Storage) | 1.75 mm at 2...9 Hz |