Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
56054 – Rectangular sensor L2 type, VigiPacT, 470mmx160mm, 3200A
56054
Rectangular sensor L2 type, VigiPacT, 470mmx160mm, 3200A

This toroid is dedicated to VigiPacT type A residual current protection and monitoring relays. It allows the measurement of a current rating up to 3200A for VigiPacT monitoring and protection relays. The transformer ratio is 1/1000. The inner dimensions of the toroid are 470mm X 160mm and the weight is 20kg. The wiring size must be from 0.5 to 2.5 mm². The wiring length should not exceed 10m.

Brand: Schneider Electric

Add to Quote Catalogue
Specifications
Range Compatibility
  • VigiPacT RH10M residual current protection relay
  • VigiPacT RH10P residual current protection relay
  • VigiPacT RH21M residual current protection relay
  • VigiPacT RH21P residual current protection relay
  • VigiPacT RH68M residual current protection relay
  • VigiPacT RH86M residual current protection relay
  • VigiPacT RH86P residual current protection relay
  • VigiPacT RH99M residual current protection relay
  • VigiPacT RH99P residual current protection relay
  • VigiPacT RH197M residual current protection relay
  • VigiPacT RH197P residual current protection relay
  • VigiPacT RHU residual current protection relay
  • VigiPacT RHUs residual current protection relay
  • VigiPacT RMH residual current protection relay
Product Or Component Type earth leakage current sensor
Range VigiPacT
[Ie] Rated Operational Current 3200 A
Current Transformer Type rectangular sensor
Device Application equipment monitoring and control
Device Short Name L
Warranty 18 months
Mounting Mode
  • fixed cables)
  • fixed busbar)
Height 281 mm
Residual Short-Circuit Withstand Current 85 kA / 0.5 s
[Uimp] Rated Impulse Withstand Voltage 12 kV
Connections - Terminals screw connection 0.2-2.5 mm²
Depth
  • outside 72 mm
  • inside 72 mm
Net Weight 21.16 kg
Height
  • outside 281 mm
  • inside 160 mm
Width
  • outside 572 mm
  • inside 470 mm
Width 572 mm
Overvoltage Category IV
Depth 72 mm
[Icw] Rated Short-Time Withstand Current 100 kA 0.5 s
Transformer Ratio 1/1000
Rohs Exemption Information Yes
Mercury Free Yes
Toxic Heavy Metal Free Yes
Reach Regulation Free of Substances of Very High Concern above the threshold
California Proposition 65 WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
Reach Free Of Svhc Yes
Weee The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation Pro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs Directive Compliant
Product Certifications CE
Ambient Air Temperature For Operation -35-80 °C
Standards IEC 60947-2
Environmental Characteristic
  • exposure to damp heat not in service 25...55 °C, RH 95 %) 28 cycles IEC 60068-2-30
  • salt mistKb/2 IEC 60068-2-52
  • exposure to damp heat in servicecategory C2 48 hours IEC 60068-2-56
Ambient Air Temperature For Storage -55-100 °C
Ip Degree Of Protection
  • connectors IP20
  • IP30
Documents