9800.25003306 – 5 kV 133%/8 kV 100% Power, Shielded, 3/C VFD
9800.25003306
5 kV 133%/8 kV 100% Power, Shielded, 3/C VFD
  • CCW armor provides an impervious barrier to moisture, gas and liquids and meets the grounding requirements of UL 1072 and the NEC
  • Triple Extrusion: The strand shield, EPR insulation and insulation shield are all extruded in one operation
  • General Cable’s EPR insulation system has outstanding corona resistance and high dielectric strength, and it provides electrical stability under stress
  • Cable meets cold impact at -40°C
  • 105˚C continuous operating temperature, wet or dry
  • 140˚C emergency rating
  • 250˚C short circuit rating

Brand: Prysmian Group

Add to Quote
Description
Description 5 kV 133%/8 kV 100% Power, Shielded, 3/C VFD
Long Description
  • CCW® Armored Power, 5 kV 133%/8 kV 100%, Shielded, 3/C VFD
  • UL Type MC-HL or MV-105, CSA Type HL, EPR, 105°C, Cable Tray Use, Sunlight-Resistant Direct Burial, ABS CWCMC
Features
  • CCW armor provides an impervious barrier to moisture, gas and liquids and meets the grounding requirements of UL 1072 and the NEC
  • Triple Extrusion: The strand shield, EPR insulation and insulation shield are all extruded in one operation
  • General Cable’s EPR insulation system has outstanding corona resistance and high dielectric strength, and it provides electrical stability under stress
  • Cable meets cold impact at -40°C
  • 105˚C continuous operating temperature, wet or dry
  • 140˚C emergency rating
  • 250˚C short circuit rating
Applications
  • Variable Frequency Drives: 3-conductor CCW armored cables with three (3) symmetrical grounding wires are the preferred wiring method for use with AC motors controlled by pulse-width modulated inverters in VFD applications
  • CCW armored medium-voltage power cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods
  • For use on feeders and branch circuits in industrial power distribution systems per NEC Articles 328 and 330
  • For use in Class I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2 hazardous locations per NEC Articles 501, 502, 503 and 505
  • Installed on metal racks, troughs, in raceways, in cable trays or secured to supports spaced not more than six feet apart
  • Installed in both exposed and concealed work, wet or dry locations, directly buried or embedded in concrete
  • Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute
Compliances
  • Design Adherence:
  • ICEA S-93-639/WC74, 5-46 kV
  • Shielded Power Cable
  • AEIC CS8 Specification for Shielded Power Cable, 5-46 kV
  • UL 1072 Medium-Voltage Power Cables
  • UL 1569 Metal Clad Cables
  • UL 2225 Cables and Cable Fittings for Use in Hazardous Locations
  • UL 1309 Marine Shipboard Cable
  • CSA 68.10
  • Flame Tests:
  • ICEA T-29-520 (210,000 BTU/hr)
  • IEEE 383 (70,000 BTU/hr)
  • CSA FT4
  • IEEE 1202 (70,000 BTU/hr)
  • UL 1072
  • IEC 60332-3 Category A
  • Compliances:
  • UL Type MV-105 or MC-HL, SUN RES, CT USE, DIR BUR, -40°C, FT4, UL File # E90501
  • UL Listed Marine Shipboard, UL File # E85994
  • CSA Type HL, SR, FT4, -40°C, CSA File # 27161
  • American Bureau of Shipping (ABS) Listed for CWCMC
Product Construction
Spec Number 9800
Conductor
  • Bare annealed copper per ASTM B3
  • Compact stranding per ASTM B496
Insulation 115 mils Ethylene Propylene Rubber (EPR) insulation per ICEA S-93-639 and UL 1072
Grounding Conductor(s):
  • Three (3) split Class B stranded bare annealed copper grounding conductors
  • Sized in accordance with UL 1072 and NEC Article 250
Cable Assembly_
  • Insulated and grounding conductors are cabled together with non-hygroscopic fillers when required
  • Binder tape is applied over the cabled core
CCW Armor
  • Impervious, continuously welded and corrugated aluminum alloy sheath per UL 1072 and UL 1569
  • CCW armor conductivity meets
  • the grounding requirements of NEC Article 250
Shield 5 mil annealed bare copper tape with 25% overlap
Jacket
  • Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), yellow
  • Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C
Specifications
Catalog Number 9800.25003306
Cond. Size
  • 250 (37/W) (127 mm²) (Awg/Kcmil)
No. Of cond. 3
Insulation Thickness
  • 115 (Inches)
  • 2.9 (Mm)
Bare Ground
  • 0.80 (Awg)
Nominal Core O.D.
  • 20.3 (Inches)
  • 3 x #6 (Mm)
Nominal Armor O.D.
  • 2.01 (Inches)
  • 51.1 (Mm)
Jacket Thickness
  • 2.23 (Mils)
  • 56.6 (Mm)
Nominal Overall O.D.
  • 60 (Inches)
  • 1.52 (Mm)
Approximate Net Weight
  • 2.36 (Lbs/1000 Ft)
  • 59.9 (Kg/1000 M)
Ampacity
  • 4,060 (In Air)
  • 6,042 (Direct Burial)
Documents