Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
9600.01404318 – 600 V Power, 3/C VFD and 4/C
9600.01404318
600 V Power, 3/C VFD and 4/C
  • 3-conductor CCW power cables with three grounding wires are recommended for use with pulse-width modulated AC drives
  • CCW armor provides an impervious barrier to moisture, gas and liquids
  • CCW armor provides EMI shielding performance
  • Factory assembled and tested cable for use as an alternative to cable in conduit wiring systems
  • Meets cold impact at -40°C
  • 90˚C continuous operating temperature, wet or dry
  • 130˚C emergency rating
  • 250˚C short circuit rating

Brand: Prysmian Group

Add to Quote
Description
Description 600 V Power, 3/C VFD and 4/C
Long Description UL Type MC-HL, CSA Type HL, XLPE, 600 V, 90°C, Cable Tray Use, Sunlight-Resistant Direct Burial, UL Marine Shipboard Cable, ABS CWCMC
Features
  • 3-conductor CCW power cables with three grounding wires are recommended for use with pulse-width modulated AC drives
  • CCW armor provides an impervious barrier to moisture, gas and liquids
  • CCW armor provides EMI shielding performance
  • Factory assembled and tested cable for use as an alternative to cable in conduit wiring systems
  • Meets cold impact at -40°C
  • 90˚C continuous operating temperature, wet or dry
  • 130˚C emergency rating
  • 250˚C short circuit rating
Applications
  • Variable Frequency Drives: 3-conductor CCW armored cables with three (3) symmetrical grounding wires are the preferred wiring method for use with AC motors controlled by pulse-width modulated inverters in VFD applications
  • CCW armored cables offer an economical, rugged and reliable alternative to labor-intensive cable in conduit wiring methods
  • For use in Class I, II and III, Divisions 1 and 2; and Class I, Zones 1 and 2 hazardous locations per NEC Articles 501, 502, 503 and 505
  • For use as services, feeders and branch circuits for power, lighting, control, and signal circuits in accordance with NEC Articles 330 and 725
  • Installed indoors or outdoors, wet or dry locations, directly buried, embedded in concrete, in a raceway, as aerial cable on a messenger, in cable trays, or as exposed runs secured
  • to supports in accordance with NEC Article 330
  • Recognized for use on fixed or floating offshore petroleum facilities as recommended by the American Petroleum Institute
Compliances
  • Design Adherence:
  • ICEA S-95-658/WC70 Standard for Non-Shielded Power Cable, 2 kV or Less
  • UL 44 Rubber Insulated Wires and Cables
  • UL 1569 Metal Clad Cables
  • UL 2225 Cables and Cable Fittings for Use in Hazardous Locations
  • UL 1309 Marine Shipboard Cable
  • CSA C22.2 No. 123 Metal Sheathed Cables
  • CSA C22.2 No. 174 Cables and Cable Glands for Use in Hazardous Locations
  • Flame Tests:
  • ICEA T-29-520 (210,000 BTU/hr)
  • IEEE 383 (70,000 BTU/hr)
  • CSA FT4
  • IEEE 1202 (70,000 BTU/hr)
  • UL 1581 (70,000 BTU/hr)
  • IEC 60332-3 Cat. A
  • Compliances:
  • UL Type MC-HL, XHHW-2, SUN RES,
  • CT USE, DIR BUR, -40°C, UL File # E90496
  • UL Listed Marine Shipboard, UL File # E85994
  • American Bureau of Shipping (ABS) Listed for CWCMC
  • CSA certified1 Type RA90, XLPE, HL, SR, FT4, and -40°C, CSA File # 7319
  • RoHS Compliant
Product Construction
Spec Number 9600
Conductor
  • Bare annealed copper per ASTM B3
  • 10 AWG and smaller are Class B compressed stranding per ASTM B8
  • 8 AWG and larger are compact stranding per ASTM B496
Insulation
  • Cross-linked Polyethylene (XLPE) insulation per ICEA S-95-658 and UL 44, Listed XHHW-2
  • 6 AWG and smaller are color-coded per ICEA Method 1, Table E2
  • 4 AWG and larger are black with printed numbers per ICEA Method 4
  • Color-coded per CSA C22.2 No. 123 where applicable
Grounding Conductor(s):
  • Class B stranded bare annealed copper per ASTM B3 and B8
  • Where specified, single or three split grounding wires are sized in accordance with NEC Table 250.122
Cable Assembly_
  • Insulated conductors and grounding wire(s) are cabled together with non- hygroscopic fillers when required
  • A binder tape is applied over the cabled core
CCW Armor
  • Impervious, continuously welded and corrugated aluminum alloy sheath per UL 1569 and UL 2225
  • CCW armor conductivity meets the grounding requirements of NEC Article 250
Jacket
  • Flame-retardant, moisture- and sunlight-resistant Polyvinyl Chloride (PVC), black
  • Low temperature performance meets ASTM D746 brittleness temperature at or below -40°C
  • Meets CSA Low Acid Gas requirements
Specifications
Catalog Number 9600.01404318
Cond. Size
  • 14 (7/W) (2.08 mm²) (Awg/Kcmil)
No. Of cond. 4
Insulation Thickness
  • 30 (Inches)
  • 0.76 (Mm)
Bare Ground
  • 3 x #18 (Awg)
Nominal Core O.D.
  • 0.37 (Inches)
  • 9.4 (Mm)
Nominal Armor O.D.
  • 0.58 (Inches)
  • 14.7 (Mm)
Jacket Thickness
  • 50 (Mils)
  • 1.27 (Mm)
Nominal Overall O.D.
  • 0.69 (Inches)
  • 17.5 (Mm)
Cross- Sectional Area
  • 0.38 (Sq. In.)
Approximate Net Weight
  • 226 (Lbs/1000 Ft)
  • 336 (Kg/1000 M)
90°C Ampacity @ 30°Cambient 15
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews