Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
5310.01111 – Diesel Locomotive Cable Types RHH/RHW-2
5310.01111
Diesel Locomotive Cable Types RHH/RHW-2
  • Rated 90°C wet or dry per UL 44/CSA C.22.2-38
  • Flexible tinned copper stranding
  • Excellent resistance to oils, gear lubricants, ozone, sunlight, heat and flame
  • Designed to withstand continuous flexing

Brand: Prysmian Group

Add to Quote
Description
Description Diesel Locomotive Cable Types RHH/RHW-2
Long Description UL Types RHH/RHW-2 2000 V and C(UL) RW90 1000 V Flexible, Oil-, Sunlight- and Ozone-Resistant, Flame-Retardant, -40°C to 90°C
Features
  • Rated 90°C wet or dry per UL 44/CSA C.22.2-38
  • Flexible tinned copper stranding
  • Excellent resistance to oils, gear lubricants, ozone, sunlight, heat and flame
  • Designed to withstand continuous flexing
Applications
  • For use up to 2000 V as power cables in wind turbine generator applications per UL Subject 6140
  • Diesel electric locomotives
  • Mining and earth-moving equipment
  • General purpose use as flexible power leads
  • Flexible power leads in cable trays in sizes 1/0 AWG and larger
  • Accepted for listing as flame-resistant by MSHA
Compliances
  • Industry Compliances:
  • Type RHH/RHW-2 per UL 44, UL File # E90494
  • c(UL)US Type RW90 per CSA C.22.2-38, UL File # E90494
  • National Electrical Code (NEC)
  • ICEA S-95-658/NEMA WC70
  • For CT Use” on 1/0 AWG and larger in accordance with NEC®
  • Accepted for listing as flame resistant by MSHA
  • RoHS Compliant
  • Flame Test Compliances:
  • UL 2556 VW-1
  • IEEE 1202/CSA FT4 for sizes 1/0 AWG and larger
Print GENERAL CABLE® (MFG LOCATION) DIESEL LOCOMOTIVE 2000 V P-07-KA120005-MSHA C(UL)US TYPE RHH OR RHW-2 VW-1 (SIZE) AWG/kcmil (MM2) EP FOR CT USE* SR -40ºC FT4 OR RW90 EP 1000 V ROHS MONTH/YEAR OF MFG SEQUENTIAL FOOTAGE MARK
Product Construction
Conductor 14 AWG (2.08 mm) thru 1111.1 kcmil (562 mm) Class I fully annealed flexible stranded tin coated copper per AAR 589
Insulation Flame-retardant, lead-free Cross-linked Ethylene Propylene (EP) with separator tape over the conductor to facilitate stripping
Jacket
  • Black, flame-retardant, sunlight-, ozone- and oil-resistant, lead-free Cross-linked Chlorinated Polyethylene (XL-CPE)
  • Colors available upon request
Specifications
Catalog Number 5310.01111
Cond. Size
  • 1111.1 (Awg/Kcmil)
  • 562 (mm)
Cond. Strand 2745W
Nominal Cond O.D
  • 1.328 (Inches)
  • 33.7 (Mm)
Nominal Ins. Thickness
  • 0.115 (Inches)
  • 2.9 (Mm)
Jacket Thickness
  • 0.095 (Inches)
  • 2.4 (Mm)
Nominal O.D
  • 1.77 (Inches)
  • 44.9 (Mm)
Approx. Net Wt
  • 4232 (LBS/1000 FT)
  • 6298 (kg/km)