Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
381800IG – Flexible Variable Frequency Drive Power Unarmored
381800IG
Flexible Variable Frequency Drive Power Unarmored
  • Meets NEK 606 mud oil resistance requirements with ester-based muds
  • Meets UL 2225 crush and impact requirements of Type MC-HL cables
  • Permitted for Exposed Run “ER” (open wiring) use in accordance with NEC
  • Flexible stranding to facilitate ease of cable installation and termination
  • Temperature rated @ 125°C for long life, higher ampacities and protection rom thermal overloads
  • Meets cold bend test at -55°C
  • Meets cold impact test at -40°C

Brand: Prysmian Group

Add to Quote
Description
Description Flexible Variable Frequency Drive Power Unarmored
Features
  • Meets NEK 606 mud oil resistance requirements with ester-based muds
  • Meets UL 2225 crush and impact requirements of Type MC-HL cables
  • Permitted for Exposed Run “ER” (open wiring) use in accordance with NEC
  • Flexible stranding to facilitate ease of cable installation and termination
  • Temperature rated @ 125°C for long life, higher ampacities and protection rom thermal overloads
  • Meets cold bend test at -55°C
  • Meets cold impact test at -40°C
Applications
  • AC motor variable frequency drives
  • Offshore oil and gas drilling platforms, MODUs, ships and FPSOs
  • Land-based oil and gas drilling rigs
  • Suitable for use in Class I, Division 2 and Zone 2 environments when nstalled in accordance with API-RP14F or NEC Article 501
Compliances
  • Industry:
  • API-RP14F
  • CSA C22.2 No. 38 Type RW90
  • CSA C22.2 No. 230 Type TC
  • CSA C22.2 No. 245 Type X110
  • IEEE 1580-2010 Type P
  • IEC 60092-350
  • Mud oil-resistant
  • UL 1309 Type X110
  • UL Listed 110°C Marine Shipboard Cable
  • Flame Test:
  • IEEE 1202
  • IEC 60332-3-22 Cat. A (supersedes IEC 60332-3A)
  • CSA C22.2 No. 0.3 FT4
Print MOR® POLYRAD® XT-125 VFD (UL) E85994 BR782 110C 3C XXAWG+3GRNDS HIELDED TC-ER RHW -- (CSA) LL 9755 SPEC 245/1309 FT4 -40C SR 2000 V RW90 XLPE TC (ETL) US 109229 IEEE 1580 -- IEC 1 KV 60332.3A DAY/MONTH/YEAR SEQUENTIAL MARK
Product Construction
Conductor • 8 AWG thru 777 kcmil soft annealed tinned copper flexible strand
Insulation
  • Polyrad® XT-125 Irradiated Cross-linked Polyolefin (XLPO)
  • Color Code: All black with printed numbers
Shield • Overall tinned copper braid with aluminum/polyester tape – 100% coverage for enhanced shield effectiveness required by VFD applications
Ground • 3 split green insulated flexible tinned copper conductors sized to UL 1277
Options
  • Overall braid wire armor
  • Larger sized insulated ground wires
  • Uninsulated ground wires
Sheath • Mud Oil-Resistant, Black Irradiated Cross-linked Chlorinated Polyethylene (XL-CPE)
Specifications
Catalog Number 381800IG
# Of Cores 3
Cond. Size
  • 2 (AWG)
Grounding Cond Size
  • 3 x #10 (AWG)
Nominal Cable Diameter
  • 1.235 (Inches)
  • 31.37 (mm)
Cooper Weight
  • 778 (lbs/1000 Ft)
  • 1158 (kg/km)
Net Weight
  • 1384 (lbs/1000 ft)
  • 2059 (kg/km)
Ampacities 45°C Ambient-Single Banked
  • 116 (95°C)
  • 122 (100°C)
  • 131 (110°C)
  • 161 (125°C)
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews