Electrical distributor of high quality products to the LA and Orange County markets

Call Us Today To get a Quote
356280 – Flexible Multi-Conductor Control Unarmored, 14 AWG, 12 AWG & 10 AWG
356280
Flexible Multi-Conductor Control Unarmored, 14 AWG, 12 AWG & 10 AWG
  • Meets NEK 606 mud oil resistance requirements with ester-based muds
  • Meets UL 2225 crush and impact requirements of Type MC-HL cables
  • Permitted for Exposed Run “ER” (open wiring) use in accordance with NEC for 3 conductors or more
  • Permitted for Exposed Run, Hazardous Location “ER-HL” use in accordance with NEC for 3 conductors or more and O.D. of 1.00" or less
  • Flexible stranding to facilitate ease of cable installation and termination
  • Temperature rated @ 125°C for long life, higher ampacities and protection from thermal overloads
  • Meets cold bend test at -55°C
  • Meets cold impact test at -40°C

Brand: Prysmian Group

Add to Quote
Description
Description Flexible Multi-Conductor Control Unarmored, 14 AWG, 12 AWG & 10 AWG
Features
  • Meets NEK 606 mud oil resistance requirements with ester-based muds
  • Meets UL 2225 crush and impact requirements of Type MC-HL cables
  • Permitted for Exposed Run “ER” (open wiring) use in accordance with NEC for 3 conductors or more
  • Permitted for Exposed Run, Hazardous Location “ER-HL” use in accordance with NEC for 3 conductors or more and O.D. of 1.00" or less
  • Flexible stranding to facilitate ease of cable installation and termination
  • Temperature rated @ 125°C for long life, higher ampacities and protection from thermal overloads
  • Meets cold bend test at -55°C
  • Meets cold impact test at -40°C
Applications
  • Offshore oil and gas drilling platforms, MODUs, ships and FPSOs
  • Land-based oil and gas drilling rigs
  • Suitable for use in Class I, Division 2 and Zone 2 environments when installed in accordance with API-RP14F or NEC Article 501
  • TC-ER-HL is suitable for use in Class 1, Division 1 and Zone 1 environments when installed in accordance with API-RP14F or NEC Article 501
Compliances
  • Industry:
  • API-RP14F
  • CSA C22.2 No. 38 Type RW90
  • CSA C22.2 No. 230 Type TC
  • CSA C22.2 No. 245 Type X110
  • IEEE 1580-2010 Type P
  • IEC 60092-350
  • Mud oil-resistant
  • UL 1309 Type X110
  • UL Listed 110°C Marine Shipboard Cable
  • UL 2225 Type TC-ER-HL
  • Flame Test:
  • IEEE 1202
  • IEC 60332-3-22 Cat. A (supersedes IEC 60332-3A)
  • CSA C22.2 No. 0.3 FT4
Print • MOR® POLYRAD® XT-125 (UL) E85994 BR782 110C XX/C XXAWG TC-ER1-HL2 XHHW -- (CSA) LL 9755 SPEC 245/1309 FT4 -40C SR DIR BUR 600/1000 V 600 V RW90 XLPE TC -- IEC 1 KV 60332.3A IEEE 1580 TYPE P (ETL) 109229 YEAR OF MFG SEQUENTIAL FOOTAGE MARK
Product Construction
Conductor • 14 AWG thru 10 AWG soft annealed tinned copper flexible strand
Insulation
  • Polyrad® XT-125 Irradiated Cross-linked Polyolefin (XLPO)
  • Color Code: Per IEEE 1580 Table 22
Cable Core
  • Cabled with fillers when required
  • Core binder tape when required
Options • Other color codes available upon request
Sheath • Mud Oil-Resistant, Black Irradiated Cross-linked Chlorinated Polyethylene (XL-CPE)
Specifications
Catalog Number 356280
# Of Cores 44
Cond. Size
  • 12 (AWG)
Nominal Cable Diameter
  • 1.355 (Inches)
  • 34.42 (mm)
Cooper Weight
  • 783 (lbs/1000 Ft)
  • 1165 (kg/km)
Net Weight
  • 1325 (lbs/1000 ft)
  • 1972 (kg/km)
Ampacities 45°C Ambient-Single Banked
  • 10 (95°C)
  • 11 (100°C)
  • 12 (110°C)
  • 13 (125°C)
Documents
Royal Wholesale Electric

5.0

Powered by

Based on 2 User Reviews