13349.340300.CA – Anaconda® Brand Type SHD-GC Power, Shielded Round Portable w/Ground-Check, EPR/CPE – 2000 Volts
13349.340300.CA
Anaconda® Brand Type SHD-GC Power, Shielded Round Portable w/Ground-Check, EPR/CPE - 2000 Volts
  • Flexible insulation shield provides shock hazard protection
  • Excellent heat, moisture, steam, oil, chemical and radiation resistance
  • Flexible for easy handling
  • Resists cutting, impact, abrasion, flame and sunlight
  • Excellent thermal stability and physical properties over a broad temperature range
  • Two-layer jacket is reinforced to provide maximum protection from mechanical damage— the cause of most portable cable failures

Brand: Prysmian Group

Add to Quote
Description
Description Anaconda® Brand Type SHD-GC Power, Shielded Round Portable w/Ground-Check, EPR/CPE - 2000 Volts
Features
  • Flexible insulation shield provides shock hazard protection
  • Excellent heat, moisture, steam, oil, chemical and radiation resistance
  • Flexible for easy handling
  • Resists cutting, impact, abrasion, flame and sunlight
  • Excellent thermal stability and physical properties over a broad temperature range
  • Two-layer jacket is reinforced to provide maximum protection from mechanical damage— the cause of most portable cable failures
Applications
  • Designed for use as trailing cables on AC mining equipment:
  • Where a ground-check conductor is required for fail-safe monitoring
  • With Bretby-type cable handling devices on longwall shearers
  • Where induced voltages in the grounding system will not produce a hazard
  • On low- and medium-voltage AC circuits where shielding is desired or required
Compliances
  • ICEA S-75-381 Portable and Power Feeder Cables for use in mines and similar applications
  • Meets flame test requirements and is accepted for listing by MSHA
  • Approved by the Pennsylvania Department of Environmental Protection
  • Meets CAN/CSA C22.2 No. 96 Portable Power Cables and is certified by Natural Resources Canada
Product Construction
Conductor • 6 AWG thru 500 kcmil coated annealed copper, bunched wires, rope-lay-stranded per ASTM B172
Insulation Ethylene Propylene Rubber (EPR) insulation
Grounding Conductor(s):
  • Coated copper, rope-lay-stranded per ASTM B172
  • Two conductors in contact with the flexible copper braid shield
Jacket Reinforced, two-layer, extra-heavy-duty, lead- cured Chlorinated Polyethylene (CPE)
Options
  • Colored jackets are available
  • TPU (Thermoplastic Polyurethane) jacket
  • Anamaxx® jacket
Jacket Marking GENERAL CABLE® ANACONDA® BRAND (SIZE) 3/C TYPE SHD-GC 2000 VOLTS (-50C) FT1 FT5 CSA LR 27161 P-7K-102-045 MSHA
Specifications
Catalog Number 13349.340300.CA
No. Of Cond. 3
Cond. Size
  • 3 (Awg/kmcil)
Cond. Strand 259
Nominal Insulation Thickness
  • 0.070 (Inches)
  • 1.8 (mm)
Ground Conductor Size
  • 7 (AWG)
Ground-Check Cond. Size
  • 10 (AWG)
Nominal Jacket Thickness
  • 0.170 (Inches)
  • 4.3 (Mm)
Nominal Cable O.D
  • 1.51 (Inches)
  • 38.3 (mm)
Cooper Weight
  • 831 (lbs/1000 Ft)
  • 1237 (kg/km)
Net Weight
  • 1680 (lbs/1000 ft)
  • 2500 (kg/km)
Ampacity 140