Part Number | ATV212W075N4C |
---|---|
Country of Origin | ID |
UPC | 606480322600 |
UPC11 | 60648032260 |
EAN | 3606480322600 |
Availability | N |
Lead Time | 43 |
UNSPSC | 26111503 |
ECCN | EAR99 |
HTs Code | 8504404000 |
Prop 65 | This product can expose you to chemicals including: Lead and lead compounds which is known to the State of California to cause Carcinogen & Reproductive harm. For more information go to www.p65warnings.ca.gov |
RoHS Compliant | Yes |
Discount Schedule | CP4D |
Return Indicator | No |
Depth | 7.56 inch |
Height | 11.69 inch |
Width | 8.46 inch |
Weight | 16.53 pound |
Range Of Product | Altivar 212 |
---|---|
Product Or Component Type | Variable speed drive |
Device Short Name | ATV212 |
Product Destination | Asynchronous motors |
Product Specific Application | Pumps and fans in HVAC |
Assembly Style | With heat sink |
Network Number Of Phases | 3 phase |
Motor Power kW | 0.75 kW |
Motor Power Hp | 1 hp |
[Us] Rated Supply Voltage | 380...480 V - 15...10 % |
Supply Voltage Limits | 323…528 V |
Supply Frequency | 50...60 Hz - 5...5 % |
Emc Filter | Class C1 EMC filter integrated |
Line Current | 1.4 A 480 V 1.7 A 380 V |
Apparent Power | 1.6 kVA 380 V |
Prospective Line Isc | 5 kA |
Continuous Output Current | 2.2 A 380 V 2.2 A 460 V |
Max Transient Current | 2.4 A 60 s |
Speed Drive Output Frequency | 0.5…200 Hz |
Nominal Switching Frequency | 12 kHz |
Switching Frequency | 6...16 kHz adjustable 12...16 kHz with derating factor |
Speed Range | 1…10 |
Speed Accuracy | +/- 10 % of nominal slip 0.2 Tn to Tn |
Torque Accuracy | +/- 15 % |
Transient Overtorque | 120 % of nominal motor torque +/- 10 % 60 s |
Async Motor Control Profile | Voltage/frequency ratio, automatic IR compensation (U/f + automatic Uo) Voltage/frequency ratio, 2 points Voltage/frequency ratio - Energy Saving, quadratic U/f Flux vector control without sensor, standard Voltage/frequency ratio, 5 points |
Regulation Loop | Adjustable PI regulator |
Motor Slip Compensation | Adjustable Not available in voltage/frequency ratio motor control Automatic whatever the load |
Local Signalling | DC bus energized 1 LED red) |
Output Voltage | <= power supply voltage |
ISOlation | Electrical between power and control |
Type Of Cable | Without mounting kit 1 IEC cable 113 °F (45 °C), copper 90 °C / XLPE/EPR Without mounting kit 1 IEC cable 113 °F (45 °C), copper 70 °C / PVC With UL Type 1 kit 3 UL 508 cable 104 °F (40 °C), copper 75 °C / PVC |
Electrical Connection | VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES terminal 0.00 in² (2.5 mm²) / AWG 14 L1/R, L2/S, L3/T terminal 0.01 in² (6 mm²) / AWG 10 |
Tightening Torque | 11.51 lbf.in (1.3 N.m), 11.5 lb.in L1/R, L2/S, L3/T) 5.31 lbf.in (0.6 N.m) VIA, VIB, FM, FLA, FLB, FLC, RY, RC, F, R, RES) |
Supply | Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 A overload and short-circuit protection Internal supply 24 V DC 21…27 V), <200 A overload and short-circuit protection |
Analogue Input Number | 2 |
Analogue Input Type | VIA switch-configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits VIB configurable voltage 0...10 V DC 24 V max 30000 Ohm 10 bits VIB configurable PTC probe 0...6 probes 1500 Ohm VIA switch-configurable current 0...20 mA 250 Ohm 10 bits |
Sampling Duration | 2 ms +/- 0.5 ms F discrete 2 ms +/- 0.5 ms R discrete 2 ms +/- 0.5 ms RES discrete 3.5 ms +/- 0.5 ms VIA analog 22 ms +/- 0.5 ms VIB analog |
Response Time | FM 2 ms +/- 0.5 ms analog FLA, FLC 7 ms +/- 0.5 ms discrete FLB, FLC 7 ms +/- 0.5 ms discrete RY, RC 7 ms +/- 0.5 ms discrete |
Accuracy | +/- 0.6 % VIA) for a temperature variation 60 °C +/- 0.6 % VIB) for a temperature variation 60 °C +/- 1 % FM) for a temperature variation 60 °C |
Linearity Error | VIA +/- 0.15 % of maximum value input VIB +/- 0.15 % of maximum value input FM +/- 0.2 % output |
Analogue Output Number | 1 |
Analogue Output Type | FM switch-configurable voltage 0...10 V DC 7620 Ohm 10 bits FM switch-configurable current 0...20 mA 970 Ohm 10 bits |
Discrete Output Number | 2 |
Discrete Output Type | Configurable relay logic FLA, FLC) NO - 100000 cycles Configurable relay logic FLB, FLC) NC - 100000 cycles Configurable relay logic RY, RC) NO - 100000 cycles |
Minimum Switching Current | 3 mA 24 V DC configurable relay logic |
Maximum Switching Current | 5 A 250 V AC resistive cos phi = 1 L/R = 0 ms FL, R) 5 A 30 V DC resistive cos phi = 1 L/R = 0 ms FL, R) 2 A 250 V AC inductive cos phi = 0.4 L/R = 7 ms FL, R) 2 A 30 V DC inductive cos phi = 0.4 L/R = 7 ms FL, R) |
Discrete Input Type | F programmable 24 V DC level 1 PLC 4700 Ohm R programmable 24 V DC level 1 PLC 4700 Ohm RES programmable 24 V DC level 1 PLC 4700 Ohm |
Discrete Input Logic | Positive logic (source) F, R, RES), <= 5 V, >= 11 V Negative logic (sink) F, R, RES), >= 16 V, <= 10 V |
Accel And Decel Ramps | Automatic based on the load Linear adjustable separately from 0.01 to 3200 s |