Vacuum switch XMLB -1 bar – adjustable scale 2 thresholds – 1 C/O
XMLBM02V2C11
Vacuum switch XMLB -1 bar – adjustable scale 2 thresholds – 1 C/O

This XMLB electromechanicalVacuum switch has an adjustable differential for regulation of 2 thresholds and a zinc alloy body with a range scale window. This pressure switch is designed for regulation of pressure between 2 thresholds for air, fresh water and hydraulic oils at temperatures up to 70°C. It is fixed directly on tubage. It provides zinc alloy enclosure for robust performance. 3 million cycles mechanical durability for minimum required maintenance on your pressurized fluid circuits. It complies with CCC, EN/IEC 60947-5-1, CSA C22.2 No.14, LROS, UL 508, EAC, BV. Ideal for vacuum chambers with negative pressures vs.outer atmosphere.

Brand: Telemecanique

Add to Quote Catalogue
Specifications
Part Number XMLBM02V2C11
Country of Origin CZ
UPC 785901637493
UPC11 78590163749
EAN 3389110712681
Availability N
Lead Time 19
UNSPSC 39122210
ECCN EAR99
HTs Code 9032200000
Prop 65 This product can expose you to chemicals including: Di-isodecyl phthalate (DIDP) and Diisononyl phthalate (DINP) which is known to the State of California to cause Carcinogen and Reproductive harm. For more information go to www.p65warnings.ca.gov
RoHS Compliant Yes
Discount Schedule DS2
Return Indicator No
Depth 3.05 inch
Height 6.22 inch
Width 2.17 inch
Weight 2.27 pound
Characteristics
Range Of Product OsiSense XM
Product Or Component Type Electromechanical pressure sensor
Pressure Sensor Type Electromechanical vacuum sensor
Device Short Name XMLB
Pressure Sensor Size -14.50 psi (-1 bar)
Controlled Fluid Air 32…158 °F (0…70 °C)) Fresh water 32…158 °F (0…70 °C)) Hydraulic oil 32…158 °F (0…70 °C))
Fluid Connection Type G 1/4 (female) ISO 228
Electrical Connection 1 male connector EN 175301-803-A (ex DIN43650), 4 pins
Contacts Type And Composition 1 C/O
Pressure Swt Type Of Operation Regulation between 2 thresholds
Electrical Circuit Type Control circuit
Type Of Scale Adjustable differential
Local Display With
Adj Range High Setting -12.62…-0.15 psi (-0.87…-0.01 bar)
Adj Range Low Setting -14.50…-2.03 psi (-1…-0.14 bar)
Possible Diff Max At High Setg 11.60 psi (0.8 bar)
Max Perm Accidental Pressure 130.53 psi (9 bar)
Destruction Pressure 261.07 psi (18 bar)
Pressure Actuator Diaphragm
Materials In Contact Wth Fluid Nitrile 304L stainless steel Zinc alloy
Enclosure Material Zinc alloy
In Rated Current 3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1
Possible Diff Min At Low Setg 1.89 psi (0.13 bar) +/- 0.02 bar)
Possible Diff Min At High Setg 1.89 psi (0.13 bar) +/- 0.02 bar)
Max Perm Pressure - Per Cycle 72.52 psi (5 bar)
Terminal Block Type 4 terminals
Operating Rate 120 cyc/mn
Repeat Accuracy 2 %
Ui Rated Insulation Voltage 300 V UL 508 500 V EN/IEC 60947-1 300 V CSA C22.2 No 14
Uimp Rated Imp Wstd Voltage 6 kV EN/IEC 60947-1
Auxiliary Contacts Operation Snap action
Contacts Material Silver contacts
Resistance Across Terminals 25 mOhm IEC 255-7 category 3 25 mOhm NF C 93-050 method A
Short-Circuit Protection 10 A cartridge fuse gG (gl)
Mechanical Durability 3000000 cycles
Setting External
Height 6.22 in (158 mm)
Depth 3.05 in (77.5 mm)
Width 2.17 in (55 mm)
Product Weight 2.27 lb(US) (1.03 kg)
Standards CE EN/IEC 60947-5-1 CSA C22.2 No 14 UL 508
Product Certifications BV CSA EAC UL LROS (Lloyds register of shipping) CCC
Protective Treatment TC standard version
Ambient Air Temp For Op -13…158 °F (-25…70 °C)
Ambient Air Temp For Storage -40…158 °F (-40…70 °C)
Operating Position Any position
Vibration Resistance 4 gn 30…500 Hz)IEC 60068-2-6
Shock Resistance 50 gn IEC 60068-2-27
Electrical Shock Protect Class Class I IEC 1140 Class I IEC 536 Class I NF C 20-030
IP Degree Of Protection IP65 EN/IEC 60529